BLD2013-0562 CHCSC 23320 Hwy99.doc MEMORANDUM Date:June 17, 2013 To:Ms. Rebecca Cook rebeccacook@millerhayashi.com Miller Hayashi Architects 206.634.0177 From:Fire Marshal John J. Westfall 425.771.0213 Subject:BLD2013-0562 CHCSC 23320 Highway 99 This Review is conducted in accordance with 2009 IFC and Edmonds Community Development Code. Fire Services provides the following comments: 1. Sheets AA1.01 Code Plan & A2.02. Add RN QUIET occupant loads to TEAM POD area occupant loads on floor 2. 2. Sheets AA1.01 Code Plan & A2.02. Rooms may use pocket/barn door configuration for means of egress when the space serves less than 10 occupant load (1008.1.2 exception 9). At TEAM POD areas, reconfigure pocket doors to side-hinged, or pivot-type providing egress from these areas. 3. Sheet A2.42. Update door types from above for doors 210A, 207C, 220A & 220B. 4. Sheet A2.01. Rename MED GAS room 117 to MED STORAGE or other approved name. 5. Sheet A4.11. Provide ROOF ACCESS identification signs at Stair B/Stair 002. 6. Sheet A2.42. Provide FIRE CONTROL signage at sprinkler riser room door 255A 7. No electric plans were submitted. Please assure that emergency pathway lighting is provided throughout. 8. Sheet A2.42. Install a Fire Department KNOX box at the FIRE CONTROL entry. Call 425.775.7720 for approval form. 9. Sheet A3.00. Post “23320” building address on contrasting background that is legible and viewable from Highway 99. City of Edmonds Office of Fire Marshal  