16525 74TH PL W.PDF16525 74TH PL W RZA MAERITTENHOUSE-ZEMAN & ASSOCIATES, INC. Geotechnical & Hydrogeological Consultants 1400 140rh Avenue N.E. Bellevue. Washington 98005 (206) 746-8020 1 July 1988 ST _ ET -FILE W-5722 Joe & Jan Conner/, 14537 N.E. 43rd Place, #N1302 Bellevue, Washington 98007 ,Subject: Subsurface Exploration and Geotechnical Engineering Report Residential Lot 16521 - 74th Place West Edmonds, Washington Mr. and Mrs. Conners: This letter report presents the results of our subsurface exploration and geotechnical engineering study relative to the foundation and construction considerations for the proposed project. This report has been prepared for the exclusive use of Mr. and Mrs. Conners and their agents, for specific application to this project in accordance with generally accepted geotechnical engineering practices. SITE AND PROJECT DESCRIPTION The residential lot is located on the east side of 73rd Avenue West in the Meadowdal e area of the City of Edmonds, Washington. The lot slopes upwards towards the east, with a shallow gully running up the south side of the lot and a deeper gully running near the northern margin of the property. The property is covered with native evergreen and deciduous trees and an understory of blackberry brush, fern and nettle. Horse tails were also noted at the bottom of the. property, next to the street. We understand that conventional, two-story, wood -frame residence with a daylight garage is to be constructed near the center of the property. A cut on the order of 10 to 12 feet will be required for the back of the garage. area. The garage elevation will be approximately 18 feet, first -story elevation 28 feet and second -story elevation 38 feet. '3c'� n - Conners W-5722 1 July 1988 Page 2 Subsurface Conditions Four test pits were excavated with a rubber-ti red backhoe on 13 June 1988, contracted by you. Approximate test locations are indicated on the attached site plan. Test pit logs are presented at the end of this letter report. The relative soil densities indicated on the test pit logs are interpretive descriptions based on the conditions observed during the excavation. Test pit TP-1, located on the upper portion of the property, encountered topsoil over a loose zone of silty, gravelly sand with some roots. This loose zone extended to a depth of 2-1/2 feet. and typically results from weathering of the soil and root penetration. Below this loose zone, the native, silty, gravelly sand increased in density to medium dense and then dense at a depth of 6 feet. Test pit TP-3, located the southern end of the proposed residence within the shallow gully, encountered the same material type and sequence as test pit TP-1. Both test pits were wet to saturated at depth. Test pit TP-2 was located on the upper portion of the lot at approximately the first -story elevation. This test pit encountered topsoil over a loose, weathered zone to a depth of 2-1/2 feet. Below the weathered zone, dense to very dense, silty, gravelly sand (glacial till) was revealed to the full depth of the test pit. Test pit TP-4 was located near the garage area of the proposed house. It encountered the same depth of topsoil over the loose, weathered zone as the other test pits. The test pit then revealed medium dense, silty, fine sand grading to dense, silty, gravelly sand with cobbles at a depth of 7 feet. No ground water was encountered in any of our test pits, however much of the native soil, revealed in our test pits, was classified as wet to saturated at depth. Also, water -seeking vegetation (horse tails) were noted at the lower portion of the property near the street, indicating that near -surface ground water exists year-round in these areas. It is likely that the majority of the ground water seepage may be following the line of the shallow gully on the south side of the property. It should be noted that the ground water conditions may vary with changes in the season, precipitation, site utilization or other factors. d444-4-4ay ConnerX 1 July 1988 W-5722 Page 3 CONCLUSIONS The proposed residence is to consist of a conventional, two-story, wood -frame structure with a daylight garage. In our professional 'opinion, subject to the conditions set forth herein, the risk of local instability on the site and from neighboring sites will be minimal as defined by the City of Edmonds, if the recommendations set forth in this report are followed. The risk of probability of earth movement is less than 30 percent within a 25-year period for the site, using the procedure described in a report by Geoengineers, Inc. dated 28 February 1985, in its present configuration and after the completion of the proposed development. In our opinion, the site will be stable during construction, if our recommendations in this letter report are followed. No indications of previous movement on the site was observed by us on the surface of the site or in our test pit explorations. The site soils are silty in nature and should be considered moisture -sensitive. Special construction precautions will be required, especially on the lower portion of the property, such as subsurface drains and a sand and gravel.blanket to cover the exposed subgrade of the driveway area immediately after reaching the desired elevation. Additional recommendations for site preparation and structural fill placement are provided in the following sections of this report. Site Preparation Due to the silty nature of the site soils, special considerations are appropriate if construction proceeds during cool, damp or wet weather, or in wet site conditions. To reduce the seepage occurring across the lower portion of the site, we recommend a trench drain be installed along the street draining to the steep gully on the north margin of the property. The trench drain should consist of a perforated pipe surrounded by pea gravel or washed rock on all sides and which backfills the remainder of the trench. Silty on -site soil should be used to cap the upper 1 foot of the trench, separated by filter fabric between the drain rock and silty soil, to prevent direct surface water inflow into the trench drain. Additional trench drains can then be installed up the slope, such as up the shallow gully and possibly above the house, which are connected to this lower drain. ..� Q_ i - _�C'N dill D—day ConnerX 1 July 1988 W-5722 Page 4 The footing areas, any slab -on -grade floor area, the driveway area, or any area to receive structural fill should be stripped of all topsoil, brush and any uncontrolled fill. The site soils are silty and very moisture -sensitive. The soils are prone to disturbance and wet site conditions. The contractor should minimize traffic across the prepared subgrade areas. In very wet conditions and where traffic cannot be avoided, such as the driveway, the use of a working surface of quarry spal 1 s or sandy gravel may be required to protect the subgrade, especially from vehicular traffic. We recommend a minimum 1 foot thickness of sand and gravel be placed in the area of the driveway immediately after reaching the desired subgrade elevation. If the naturally occurring soils exposed by the stripping possess the required minimum density of at least 90 percent of the modified Proctor maximum dry density (as determined by the ASTM:D 1557 test procedure) no further site preparation will be required in those areas. Should the site soils not exceed this minimum standard, we recommend that the building and driveway areas be compacted with a roller or other suitable heavy equipment to a firm and non -yielding condition in order to achieve this minimum compaction level. Any excessively soft, wet, or significantly organic areas disclosed by the pre -rolling should be overexcavated as necessary and backfilled with structural fill as described subsequently. We anticipate that the upper, loose, weathered zone soils may be excessively wet, depending on the recent weather conditions, and may not be able to be properly compacted. In this case, the contractor may attempt to dry the native, silty soils to within a couple of points of their optimum moisture content for proper compaction as described further in the following section. However, if the soils cannot be effectively dried, removal of the west, silty soils may be necessary and replaced with imported soil as described subsequently. If the subgrade exposed by stripping or overexcavation is at least medium dense, but more than several percent over its optimum moisture content, at the concurrence of the geotechnical engineer, no compaction should be applied to the subgrade. Conner 1 July 1988 W-5722 Page 5 The subgrade should be cleaned as much as possible of any loose or soft material, and a layer of clean, sand and gravel or quarry spalls placed before compaction is applied. Structural Fill All fill placed in the building area, as well as under pavements or sidewalks, should be placed in accordance with recommendations for structural fill. All surfaces to receive fill should be prepared as previously recommended prior to placement of structural fill. Structural fill should be placed in loose, iifts not exceeding 8 inches in thickness. Individual lifts should be compacted such that a density of at least 90 percent of the modified Proctor maximum dry density (ASTM:D 1557) is achieved. We recommend that a representative of our firm be present during placement of structural fill .to observe the work and perform a representative number of in -place density tests. In this way, the adequacy of the earthwork may be evaluated as grading progresses. The suitability of soils to use for structural fill depends primarily on the soil particle size, gradation and moisture content of the material when it is placed. As the amount of fines, (that soil fraction passing the U.S. No. 200 sieve) increases, the soil becomes increasingly sensitive to small changes in moisture content and adequate compaction becomes more difficult or impossible to achieve. Any soil containing more than about 5 percent fines by weight (such as the site soils) cannot be consistently compacted to a firm, non -yielding condition when.the moisture content is about 2 percent above optimum. The use of an imported, clean, granular soil would expedite wet site or wet weather site construction. The existing topsoil and any soil containing organics at the site is not considered suitable for structural fill application. These soils may be used for landscaping purposes. We anticipate the remaining site soils that would be available for fill use, as the result of site grading, would primarily be silty, gravelly sand or silty, fine sand. These silty soils will be difficult to use as structural fill, except during dry summer months when the water content may be carefully -controlled by aeration and drying. %_)OQ_ �, &" ail l A -dap Conners 1 July 1988 W-5722 Page 6 Even during the summer, delays in grading may occur due to precipitation. If inclement weather occurs, the upper wetted portion of the site soils may need to be scarified and dried prior to further earthwork. If it is not practical to dry the wet, silty soils, it may be necessary to remove the wet materials and replace them with clean granular materials to accommodate wet site or adverse weather conditions. Soil used for structural fill should have a maximum particle size on the order of 6 inches and be free of organics, debris or any other deleterious material. If grading must occur during damp or wet weather, fill should consist of a select material containing no more than 5 percent by weight passing the No. 200 sieve, when measured on the minus No. 4 fraction. This material would have to be imported to the site. Spread Footing Foundation The proposed structure may be supported by conventional shallow spread footings and continuous wall footings. These footings may be founded in at least medium dense native soil, recompacted loose native soil, or imported structural fill placed above suitable native deposits. All footings should have a minimum width of at least 12 inches. The base of the exterior footing should be located at least 18 inches below the lowest adjacent ground surface or top of floor slab, for frost protection. Interior footings need only penetrate 12 inches below the lowest surrounding grade or slab surface. Based on these conditions, we recommend that the foundation elements be designed with a maximum allowable bearing pressure of 2000 pounds per square foot (psf). This alowable bearing pressures may be increased by up to one-third to accommodate seismic or transient loads. All footings must be founded in the prescribed bearing stratums. The foundations should not be set in or above loose or disturbed soils or any existing uncontrolled fill. As the site soils are silty, site work when the soils are wetter than optimum, could result in disturbance to the bearing stratum. The contractor should avoid disturbance to the soils and limit traffic across the building pad and foundation area when the ground is wetter than optimum. To minimize disturbance associated may Conners 1 July 1988 W-5722 Page 7 with foundation form work and reinforcement bar placement, the use of a sand and gravel blanket, quarry spall blanket or a "mud mat" may be required in the footing excavation. Assuming the foundations are founded in the above recommended stratums, we anticipate that total settlements should be less than 3/4 inch with differential settlements between footing elements on the order of one-half that total for foundations in similar soils. Most of the settlement should occur during the construction of the building. However, if any disturbed or soft materials are left within the footing areas prior to concrete placement, settlements may be increased. For that reason, the condition of the footing subgrade should be checked by the geotechnical engineer or his representative prior to concrete placement, to see that the condition of the bearing soils are consistent with those assumed during design. Slab -On -Grade Floors We recommend that any organic material be removed from beneath the floor slab within the building area and any loose, native soils recompacted. The slab -on - grade should be founded on prerolled native ground or structural fill as per our recommendations outlined previously. We recommend that the floor slab be underlain by a minimum 4 inch -thickness of clean, coarse sand and gravel, crushed rock or pea gravel to serve as a capillary break and working surface. The fines content (percent passing No. 200 sieve) of the capillary break should be limited to less than 5 percent. An impervious moisture barrier should also be placed beneath the slab. Backfilled Retaining Malls All backfill placed behind walls or around foundation units should be placed as per our recommendations for structural fill and drainage considerations as described in this report. -The following recommended earth pressures, presented as equivalent fluid unit weights, are based on the assumption of a uniform, level, granular backfill and no buildup of hydrostatic pressure behind the wall. Surcharges due Conner 1 July 1988 W-5722 Page 8 to adjacent footings, sloping ground, structures, vehicles, construction equipment, hydrostatic pressures, etc., should be added to these values. To minimize lateral earth pressures and prevent buildup of hydrostatic pressures, the wall backfill should consist of free -draining, granular material with drainage provided as discussed in the subsequent "Drainage Considerations" section of this report. If the backfilled walls are structurally restrained from lateral movement at the top, we recommend that they be designed for an equivalent fluid unit weight of 50 pounds per cubic foot (pcf). If the top of the walls are free to move, laterally or rotate to delect at least to 0.1 percent of the wall height, the walls may be designed for an equivalent fluid unit weight of 35 pcf. The above equivalent fluid unit weights assume that the wall backfill is compacted to approximately 90 percent of laboratory maximum dry density (ASTM:D 1557). Additional compaction adjacent to the wall will increase the lateral pressure while a lesser degree could permit excessive post -construction settlements. If settlement -sensitive facilities are to be 1 ocated wi thi n or at the top of the back fi 11 , we shoul d be contacted to review the options available for their protection, as well as lateral surcharges to the backfilled wall. Lateral loads transmitted to the footings could be resisted by a combination of base friction and passive earth pressure. An ultimate base friction coefficient of 0.4 and an allowable passive pressure of 250 pounds per cubic foot (pcf), should be used for footings which are extended into at least medium dense native soils or properly compacted structural fill. If the on -site silty materials are used for backfill behind the retaining walls, far greater lateral pressures can be expected to act on the wall. It is difficult to evaluate what lateral earth pressures will actually be imposed onto the retaining wall due to the use of this low permeability soil. The density of the soils, as well as the moisture content, play a significant role. If much of the soil material is loose, the soil will readily absorb water and become a saturated mass, even further increasing wall pressures (as the water pressure and soil components are t ayr Conner W-5722 1 July 1988 Page 9 additive). Also, the fines of the on -site silty soils if used for backfill can plug the washed rock or the footing drain itself and thereby allow a full hydrostatic pressure to develop against the wall. The on -site materaisl are only recommended for use as wall backfill, if a free -draining, granular zone at least 24-inches wide is placed adjacent to the wall through the full backfill height. Drainage Considerations The majority of the soils encountered in our test pits were classified as wet and saturated. Although no seepage was noted into our test pits, horse tails were noted along the lower portion of the site, indicating a near -surface ground water at these locations. Site soils are silty and highly susceptible to disturbance when wet. Prior to construction, surface water should be routed away from the construction and building area as much as possible. We recommend that the building be provided with a perimeter footing drain system to collect available water. The footing drain should consist of a perforated pipe surrounded by at least 4 inches of pea gravel on all sides. The gravel drainage material should extend up the full -height of the backfill, in a width of at least 24 inches. The drainpipes should lead away from the building via gravity to a storm sewer or other suitable discharge. Site grades should be planned to slope away from the building. Roof and surface runoff should not discharge into the footing drain system. Instead, a separate tight -line drain network should be installed or splash blocks should be used. CLOSURE The conclusions and recommendations presented in this report are based on the explorations accomplished for this study. The number, location and the depth of the explorations were completed within the site and proposal constraints so as to yield the information used to formulate our recommendations. Our recommendations are directed at addressing sloughing and small-scale earth movements on the property, and are not meant to prevent or address deep-seated or large-scale earth failure. The integrity and performance of the building foundation depend on proper site preparation and construction procedure. We are available to provide 4-ill fir —Jay- Conner W-5722 1 July 1988 Page 10 geotechnical engineering services during earthwork and foundation construction phases of the project. If variations of the subsurface conditions are observed at that time, we would be able to provide additional geotechnical recommendations to minimize delays as the project develops. We appreciate this opportunity to be of service to you. If you have any questions, please do not hesitate to call. Respectfully submitted, J. AM�q RITTENHOUSE-ZEMAN & ASSOCIATES, INC. Q.�,......., y? ;V. ;e GIs Mark J. rein, P.E. Project ineer Alvin R. Zeman, P .�� � President ��NAL ���STER�� i Enclosures: Site and Exploration Plan Test Pit Logs TP-1 through TP-4 EXPLANATION i . Ao i I TP-2 I � � 1 I PROPOSED RESIDENCE I DTP-4 \ (APPROXIMATE. J / \ LOCATION) // \ 6'0 I 1 TP-1 TP-3 , o PROPERTY LINE / T P-4 K 60 1 f INDICATES TEST PIT NUMBER AND APPROXIMATE LOCATION EXISTING GROUND SURFACE CONTOURS JAN 3 0 ru-- CT-,7 MfT COUNTER CONNERS RESIDENCE SITE & EXPLORATION PLAN j FIGURE 1 Z A �o W.O. BY W - 5 7 2 2 M J A RITTENHO USE-ZEMAN & ASSOCIATES, INC. I Geotechnical & H.ydrogeological Consultants DATE J U N 1988 1400 140rh .Avenue N. E. SCALE N.T.S. I Bellevue. Washingron 98005 Depth (feet) TEST PIT LOGS Soil Classification Test Pit TP-1 )Ft-r.fi�iV F— JAN 30 rr,Yll W-5722 0.0 - 0.8 TOPSOIL - Root Mat 0.8 - 2.5 Loose, wet, dark brown, silty, gravelly SAND with some roots 2.5 - 6.0 Medium dense, wet, gray with some rust mottling, silty, gravelly SAND 6.0 - 9.0 Dense, wet, gray, silty, gravelly SAND No seepage No caving Test Pit TP-2 0.0 - 1.0 TOPSOIL - Root Mat 1.0 - 2.5 Loose, wet, brown, silty, gravelly SAND 2.5 - 7.0 Dense to very dense, moist, gray, silty, gravelly SAND (Glacial Till) No seepage No caving Test Pit Logs Page 2 Depth (feet) Soil Classification Test Pit TP-3 W-5722 .J AN 3 0 fill 17'11 1T COUNTER 0.0 - 1.0 TOPSOIL - Root Mat 1.0 - 2.5 Loose, wet, brown, silty, fine SAND with some gravel and roots 2.5 - 7.0 Medium dense, wet, brown, silty, fine SAND with some gravel 7.0 - 9.5 Dense, saturated, gray, silty, gravelly SAND with cobbles to 6 inches No seepage No caving Test Pit TP-4 0.0 - 1.0 TOPSOIL - Root Mat 1.0 - 2.5 Loose, wet, brown, silty, gravelly SAND with some roots 2.5 - 7.0 Medium dense to dense, wet to saturated, gray, with some rust mottling, silty, gravelly SAND No seepage No caving STREET FILE CITY OF EDMONDS W;w LARRY S. NAUGHTEN 250 - 5TH AVE. N. • EDMONDS, WA 98020 • (206) 771-3202 MAYOR COMMUNITY SERVICES: PETER E. HAHN !IM7F Public Works • Planning • Parks and Recreation • Engineering DIRECTOR 89p.19 h"_ J'j (0 �-7 /?/ June 7, 1991 Robert and Jan Conner 16525 - 74th P1. W. Edmonds, WA 98020 Re: Paving driveway Dear Bob and Jan, In October of last year, I finalized your residence before your driveway was paved so that you could meet your closing date. I was assured that the driveway would be paved. It has been almost eight (8) months since my final inspection and the work has not been done. When the driveway is paved, the utility patch in the road needs to be paved also. If the work is not complete by June 28, 1991, we will attach the frozen account and have the work done. If you have any questions, please call me. Sincerely, ADDISON L. CHRISMAN IV Engineering Inspector ALC/sdt c: Sharon Nolan, Permit Coordinator CONNER/TXTST530 Mk Albert • Incorporated August 11, 1890 0 Sister Cities International — Hekinan, Japan _ t ��.+ -�.,.. :,; : • :. � v .' '^ -,- �. ..,o � a _ .. _ 3niKi r T+iedn�1i'"ri r�. � � r s'z' . r w ,,,1c 1L _ _ _ ,, . -. . �••-i,f ti,.�,.,,4� ir�6-`q��.•-ih.,H• .drey w`'�v�4wr'ni�•$•'..�u,sf''t -'i�=� fN�a�';cy7'hYr+�T+ �" 'j��n'�ta�*`T%N`¢ 1/!14M�rv$",�n,:a�.�•a�;gia"(,+¢r:V.•�'°wt!''-iwr...:,i,--N�G�, � CITY OF.EDMONDS Permit No. 7 r) 0 3 COMMUNITY SERVICES DEPARTMENT FILE RIGHT-OF-WAY CONSTRUCTION PERMSTIRE: Issue Date A. • Owner: 9 --4^1 4c 4Z A/Pit B. • Contractor: 16n 7��e Name Name Mail' g Address Mailing Address Of City. State Zip City State Zip State License Number'telephone Number C. • Address or Vicinity of Construction: f ��o% �11 � Type of Work to be Done: 4� _ j P 14 1- 4 4+- D. • Work in Connection With: • ❑ Sub. or Plat GJ-Single Family. , ❑ City Projects ❑ Comrriercial ❑ Multifamily ❑ Utility A E. • Pavement Cut: ©'Y El N F. • Size of Cut:— X �E — APPLICANT TO READ AND SIGN INDEMNITY: Applicant understands and by his signature to this application, :agrees to hold the City of Edmonds harmless from any injuries, damages, or claims of any kind or description whatsoever, forseen or unforseen, that may be made against the City of Edmonds, or any of its departments or employees, including or not limited to the defense of any legal proceedings including defense costs, court costs, and attorney fees by reason of granting this permit. THE CONTRACTOR IS RESPONSIBLE FOR WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FOLLOWING THE FINAL INSPECTION AND ACCEPTANCE OF THE WORK. Estimated restoration fees will be held until the final street patch is completed by City forces, at which time a debit or credit will be processed for issuance to the applicant. • A 24 hour notice is required for inspection; Please call Engineering: 771-3202 • Work is to be inspected during progress and at completion. • Restoration to be in accordance with City Code. • Street to be kept clean at all times. • Traffic Control to be in accordance with City regulations. • All street -cut ditches must be patched with asphalt or. City approved material prior to end of working day; NO EXCEPTIONS. I understand the above and that this permit must be available at the job site for inspection purposes at all times. Signature- Date:, Owner ontractor This Permit Must be Posted at the Job Site For Inspection Purposes Call DIAL -A -DIG Prior to Beginning Work APPROVED BY: nd • /6.rP� '� 3 Z Time Authorized: Void after days. O m Special Conditions: PERMIT FEE: i D Restoration Fee: Receipt No.: ,I! _� / Fund III Fee: Street Cut Dimensio�nss/f URELEASED BY( Date £-rINSPECTED BY Date O , NO WORK TO BEGIN PRIOR TO PERMIT ISSUANCE Eng. Di'v..March 1989 FIELD INSPECTION NOTES (Fund I I I - Route copy to Street Dept.) Comments: Diagram: CONTRACTOR CALLED FOR INSPECTION ❑ YES ❑ NO Partial Work Inspection by P. W.: Work Disapproved By: Date: FINAL APPROVAL BY: Date: Eng. Div. July ] e,r-.:.�• .r G".L.—T rry-'G,.7?�°�,ocrlNr'^�{3w-r7L+Tzl'�`�jkc! FF,R"f3Try ,�'rrr` ry'_."4'v�if":�:�::».+::Y'�:-n�#�"YTt'pifJr�i�'G^f �,.p,'^Vy""�'w�.:.e:..;�.M:.�.a..'.�W^5w' •,iy,»�in.;:��•wry^,�:r=?1^p•l-.zv!„yrZ,.fsy-�vt ��"a �:=3.�'i�r.F �,pr.+,r,. -V . ;CITY OF EDMONDS Permit No. 9 X COMMUNNY SERVICES DEPARTMENT RIGSTREET Fit 0 HT -OF -WAY CONSTRUCTION PERMIT ssue Date a Z O w V) U O L1. A. • Owner: ny�✓ 011P "L `r l B. • Contractor: /Lv li Ti5,4k& "7; 'AAA4 Name Name Mai{ e �d g Address Mailing Address (71— 0-I h� 9 /mad y weu f�,v,'/4_ City State Zip City State Zip lei State License Number Telephone Number C. • Address or Vicinity of Construction:111/ Type of Work to be Done: D. • Work in Connection With: Sub or Plat 'Single Family ❑ City Projects Commercial ❑ Multifamily ❑ Utility E. • Pavement Cut: © Y ' ❑ N F. • Size of Cut: �? X _, APPLICANT TO READ AND SIGN INDEMNITY: Applicant understands and by his -'signature to this application, agrees to hold the City of Edmonds harmless from any injuries, damages, or claims of any kind or description whatsoever, forseen or unforseen, that may be made against the -City of Edmonds, or any of its departments or employees, including or not limited to the defense of any legal proceedings ncluding defense costs, court costs, and attorney fees by reason of granting this permit. THE CONTRACTOR IS RESPONSIBLE FOR WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FOLLOWING THE FINAL INSPECTION AND ACCEPTANCE OF THE WORK. Estimated restoration fees will be held until the final street patch is completed by City forces, at which time a debit or credit will be processed for issuance. to -the applicant. • A 24 hour notice is required for inspection; Please call Engineering: 771-3202 • Work is to be inspected during progress and at completion. , • Restoration to be in accordance with City Code. • Street to be kept clean at all times. • Traffic Control to be in accordance with City regulations. .• All street -cut ditches must be patched with asphalt or City approved material prior to end of working day; NO EXCEPTIONS. I understand the above and that this permit must be available at the job site for inspection purposes at all times. Signature- oe Date:t�J� Owner Qr ontractor This Permit Must be Posted at the Job Site For Inspection Purposes Call DIAL -A -DIG Prior to Beginning Work APPROVED BY: w-I • 1&&C' Time Authorized: Void after 3 !� days Special Conditions: PERMIT FEE: 3 0, Restoration Fee: Receipt No.: / a l Fund 111 Fee: Street Cut Dimensions: x = S /08' RELEASED BY:( Z- 1 //IW-4" — Date - 7` 90 INSPECTED BY Date NO WORK TO BEGIN PRIOR TO PERMIT ISSUANCE Eng. Div. March 1989 f ru+a �a'r* rinF'�vij +d?r% 9ii �r �tIF�v` >►�t'at,hxtriw�, ~" CITY OF EDMONDs SIDE SEWER PERMIT �8yp ,9"0 _ PERMIT € 2 8233 Address of Construction: _%/�,67 � ' IAI Property Legal Description (Include all easements): e_k_a,e JL Owner and/or Contractor: 3r'. J State License No. d&alnK ` Building Permit No L7 Single Family ❑ Multi -Family (No. of Units ) ❑ Commercial ❑ Public Invasion into City Right -of -Way: ❑ No ®-Yes RW Construction Permit No. Cross other Private Property: ❑ No ❑ Yes Attach legal description and copy of recorded easement I er ify that I have read a d shall comply with all cityrequirements as indicated on the back of the Permit Card. Date * CALL DIAL -A -DIG (1-800-424-5555) BEFORE ANY EXCAVATION OFFICE USE ONLY * FOR INSPECTION CALL 771-3202, PUBLIC WORKS DEPT. O C� Permit Fee: Issued By Trunk Charge: S CU Date Issued: - Assessment Fee: A;k �f3rL ^ ' Receipt No.: Lid No.: / � Partial Inspection�y --� - -�'% 4- 1 ��� �¢M`G p y Date�_2F!qlnitial CornmerYs Reason Rejected: Date —Initial — Final lnspection,Approved: l Date Initial ** PERMIT MUST BE POSTED�ON JOB SITE ** White Copy: I'de Green Copy: Inspector Buff Copy: Applicant • Revised 3 �90 �Revised ;,,/90 STREET , I SIDE SEWER PERMIT k IREMENTS 1. Side sewer permits shall be posted at job -site and available to inspector at time of inspection;. Inspection during normal working hours only. One (1) working day notice required. Side sewers must be left uncovered until inspected. A water test is required. 2. Property owners can obtain a permit to install side sewers on private property. Licensed side sewer contractors must be employed to construct side sewers in the City right-of-way. Invasion into City right-of-way requires a separate permit. 3. The side sewer contractor assumes full responsibility for each installation for one (1) year. 4. Trenches within City right-of-way must be restored to original conditions. Street restoration fees shall be paid in advance under a.right-of-way permit. Contractors shall be responsible for right-of-way failure due to poor compaction of fill. -5. No down spouts, footing drains or floor drains can be connected to a side sewer system. 6. Pea gravel is required for bedding when installing sewer lines through other than granular soil. 7. Cleanouts at property line and at house will have risers installed to within 12" of surface grade with removable cap. 8. Commercial establishments require a minimum of six inch (6") side sewer line. 9. Side sewers may not be installed closer than thirty inches (30") to any structure. 10. Cleanouts are required at 30"-60" from each plumbing exit line and at minimum intervals of 100' along sewer line run. 11. Side sewer lines must be laid at a minimum grade of 2% (1.150) and maximum grade of 100% (450). 12. No turn in side sewer gre$ter than 450 (1/8 bend) is allowed be Veen cleanout. All 90 turns must be constructed of a 45 (1/8 bend) and wye with removable cap for cleanouts. 13. No cleanout shall be paved over. If located in pavement, cast iron lids will be installed. 14. All connections will be of gasketed type. No solvent joints unless prior approval is granted. CITY OF EDMONDS NEW ❑ ADDITION ❑ RETIREMENT ASSET INFORMATION SHEET STREET FILE ASSET NO. ADDITION TO ASSET NO. DESCRIPTION \ A \ SERIAL NO. LOCATION t C DEPT. NO. * * PURCHASE ORDER NO. * PROJECT NUMBER \/\i C)7�y Sd C Z PURCHASE ORDER DATE PROJECT COMPLETION DATE ^ 30 " 1� COST COST l v2�T • 0 B.A.R.S. ACCOUNT NO. -7 / I. D U D C� V. iESTIMATED LIFE 5 VI rS INITIATED BY DATE APPROVED BY **SUBMIT ASSET INFORMATION SHEET WITH FINAL PAYMENT REQUEST *SUBMIT ASSET INFORMATION SHEET UPON CLOSE OF PROJECT ACCOUNTING ONLY DEPRECIATE MONTHLY DEPRECIATION AMOUNT ANNUAL DEPRECIATION AMOUNT 0 G.L. ENTR REFERENCE VERIFIED BY PROCESSED BATCH NO. DATE b P INITI DEPARTMENT FILE t Sd,� .....3+.h j,,Y��r �.r �':a�:• ae.k'�iyr,;�'kyra,;"•'�.,;,',:r...�,..�i�-:us�.t ���-'�r,�.-�:�."1'�+}jt1+�' ��` �vV,�����;`A STREETTIL.E.,..'. CITY OF�EDMONDS SIDE SEWER PERMIT, , �89p 19�0 PERMIT NO 8 2 3 3' PUBLIC } Wouq Address of Construction: �� 5'� i ! y %�� u% Property Legal Description (Include all easements): U � , EY7NNW7070D LINE r Owner and/or Contractor: X/5''4.1 id-. O A1V-r- t -4ie a ;121/WAIF eZ-12 T,. State License No. NO -lei' Z Building Permit No 8Single Family 0 ❑ Multi -Family (No. of Units ) ❑ Commercial ❑ Public P Invasion into City Right -of -Way: ❑ No I7'I�es RW Construction Permit No. Cross other Private Property: ❑ No ❑ Yes Attach legal description and copy of recorded easement I e ify that I have read a d shall comply with all city+:requirements as indicated on the back of the Permit Card. Da e a * CALL DIAL -A -DIG (1-800-424-5555) BEFORE ANY EXCAVATION OFFICE USE ONLY * FOR INSPECTION CALL 771-3202, PUBLIC WORKS DEPT. Permit Fee: 3 Issued By C 4 ,Trunk Charge: 159 S .'rDate Issued: a 3 —fn Assessment Fee: Receipt No.: Lid No.: , Partial Inspection: Date —Initial — Comments Reason Rejected: Date Initial 4 iFinal Inspection, Approved: Date o' Initial< �-" ** PERMIT MUST BE POSTED ON JOB SITE ** White Copy: File Green Copy: Inspector Butt Copy: Applicant <> Revised 3190 The City of Edmonds Side Sewer Drawing EASEMENT NO--------------------------------------------- •� NEW CONSTRUCTION REPAIRS R LID NO . .................. ASMT. NO. ----------------- OWNER.... ------------------------------------------------------------------ ------------------------- CONTRACTOR ------------------------------------------------------------------------------------ PERMIT NO. 9-'QZ(S-9- TH .lz JOB-OADDRESS44ne.-S ... ---------- P ----- L ---------- \ --- X-f. ------------ LEGAL DESCRIPTION: LOT NO- ------- ------------------------------ BLOCK NO. ---------------- ------------------- --------------------------------------------------------------------------------------- - -------------------------------------------------------- LLYNNWOOD LINE OFADDITION ------------------------------------------------ — — - -------------- ----------- -------------------------- L 6(0 Za St L4-"*P.V.c- C,(L) D e 1) CA"q 1-,4 k 0j 5(LP-Oi- P -V-c, j1NIT-ri L{ I PWW-0001-11/75 (REV.11/78) zj0P,&%J0 JA10,ra& F. Ael Approved: DATE...... e ....... �.p ............. By Z� .............. f a STA EET FI C V CITY OF ENONDS P OJECT NAr ," CONNER RESIDENCE Err:'IR3';';�',TA! .ASSESS 1:r;T DATE SUB'1ITTED NOVEMBER 30, 1988 The information on this form will be used to determine the effect of your action upon the environment of the City of Edmonds. Please answer each question as thoroughly as possible. 9 Y 1. LA,;0 Area 50,313 sq.ft. Soils Type Glacial Till Limitations Description of topography (% slope) Sloped lot, varies from level to 75% NOTE: If grading or filling will Grading: Estimated cubic yards 400 exceed 500 cubic yards a grddinz and filling plan r,;;st be sub- mitted with the a;piication. Estimated area to be paved (including buildings) 4,000 s q.f t. Estimated area in open space (pervious surface) 46,000 sq. ft. 2. VA77. StreaT. - Estimated flow (cubic feet per second) Not applicable (N/A) W'i11 strea- be altered? N/A If yes, to what degree? N/A Other water boG'ie's? None 3. Im;act on store drainage None County storm sewer AdJacent t0 shorelines zone? N o V 7 r:r7�71 Method of handling runcff No Connected to Type and approxi-mate number of trees Cedar, Hemlock, Fir, Maple, Alder M1inimim dia-eter of trees to reimain 3" to 4' A of trees to be re- 1% Ground cover Blackberries, Ferns 0V' to be remnoved 10% Proposed landscaping, if any Some grass area,, flower & vegetable garden, majority left natural. 4. EXISTING LA:;-63 US. WITHIN 300 FEET RADIUS OF PR30CS-70 DEVE! Oa."!�--'1i; Single Nilti- Vacant Family F27i1y Cor^e -cizi North South East West 3. CIRCULATION Estimated increase in auto trips daily 6 Availability of public transportation Unknown 6. AREA OF IMPACT Neighborhood X City-wide Regional 7. EFFECT ON AIR QUALITY Smoke & Bi-products from fireplace B. CHANGES IN NOISE GENERATION None expected JAN [ . ?�!ilT COUNTER • 170, ENVIRONMENTAL CHECKLIST J A N 3 © 'p'.7" PERNAIT COUNTER Purpose of Checklist: The State Environmental Policy Act (SEPA), chapter 43.21C RC\X'. requires all governmental acencics to consider the environmental impacts of a proposal btforc making decisions. An environmental impact statement (EIS) must be prepared for all proposals with probable significant adverse impacts on the quality of the environment. The purpose of this checklist is to providc information to help you and the agency identify impacts from your proposal (and to reduce or avoid impacts from thc'proposal, if it can be done) and to help the agency, decide whether an EIS is required. Instructions for Applicants: This environmental checklist asks you to describe some basic information about your proposal. Governmental agen- cies use .this checklist to determine whether the environmental impacts of your proposal arc significant, requiring preparation of an EIS. Answer the questions briefly, with the most precise information known, or give the best dc- scription you can. You must answer each question accurately and carefully, to the best of your knowledge. In most cases, you should be able to answer the questions from your own observations or project plans without the need to hire experts. If you really do not know the answer, or if a question does not apply to your proposal, write "do not know" or "does not ap- pl; "Complete answers to the questions now may avoid unnecessary delays later. Sore questions ask about governmental reeula:ior.s, such as zoning, shoreline, and landmark designations. Answer these questions if ;you can. If you have problems, the governmental ascncies can assist you. . The checklist questions apply to all parts of your proposal, even if you plan to do them over a period of time or on diffcrcnt parcels of land. Attach any additional informa.Lion that will help describe your proposal or its environmental effects. The accncy to which you submit this c:tcckiist may ask you to explain your answers or provide additional in- formation reasonably related to determining if the.-: ray be significant adverse impact. Use of checklist for nonproject proposa!s: Complete this checklist for nonproject proposals, cevca though questions may be answered "dots not apply." IN AD- DITION, complete the SUPPLEMENTAL SHEET FOR NONPROIECT ACTIONS (part D). For nonproject actions, the references in the the=Mist to the words "project," "applicant," and 'property or site" should be read as "proposal," "proposer," and "a,`fccttd geographic area," respectively. A.BACFGROUND 1. l�amt of proposed project. if applicable THE CONNER RESIDENCE 3. ?Fame of applicant: Robert A. & Janice CONNER 3. Address and phone number of applicant and contact person: 14537 NE 43rd Place, N1302 Bellevue, WA 98007 4. Date checklist prepared: November 22, 1988 S. Agency requesting checklist: City Of Edmonds 6. Proposed timing or schedule (including phasing, if applicable): Construction start February 1, 1989, Completion June 1, 1989 7. Do you havc any plans for future additions, expansion, or further activity related to or connected with this proposal? If ycs, explain. None known at this time S. List am environmental information you knov, about that hay been prepared. or will be prepared, directly related to this proposal. None known 9. Do you knoµ• whether applications arc pending for governmental approvals of other proposals directly affecting the property covered b\ your proposal? If yes, explain. None known 10. List any government approvals or permits that will be needed for your proposal. if known. Building Permit by City of Edmonds I I. Give brief, complete description of your proposal, including the proposed uses and the size of the project and site. There are several questions later in this checklist that ask you to describe certain aspects of your proposal. You do not need to repeat those answers on this page. (Lead agencies may modify this form to include additional specific infor- mation on project description.) Development of an approximate 3;700 sq.ft. residence 12. Location of the proposal. Give sufficient information for a person to understand the precise location of your pro- posed project, including a street address, if any, and section, township. and range, if known. If a proposal would occur over a range of area. provide the range or boundaries of the site(s). Provide a legal description, site plan, vicinity map, and topographic map, if reasonably available. While you should submit any plans required by the agency, you are not required to duplicate maps or detailed plans submitted with any permit applications related to this checklist. See attached legal description TO BE COMPLETED BY APPLICANT EVALUATION FOR AGENCY USE ONLY B. ENVIRONMENTAL ELEMENTS 1. Earth a. General description of the site (circle onc): Flat, rolling, hilly, tcep slopes, mountainous, other b. What is the steepest slope on the site (approximate percent slope)? 75% -2- TO BE COMPLETED BY APPLICANT EVALUATION FOR AGENCY USE ONLY c. What general types of soils arc found on the site (for example, clay, sand, gravel, peat, muck)? If you know the classification of agricultural soils, specify them and note any prime farmland. Glacial Till, gravelly Sand d. Are there surface indications or history of unstable soils in the immediate vicinity? if so. describe. Meadowdale slide area is in the vicinity, but this property does not appear to show any signs of unstable soils. (See Soils Report .Conclusion - Page 3) e. Describe the purpose, type, and approximate quantities of any filling or grading pro- posed. Indicate source of fill. - Free draining fill required for driveway and slab on grade portion of the house, plus backfill for the foundation. The fill and cut will be balanced on the site. f. Could erosion occur as a result of clearing, construction, or use? If so, generally describe. No erosion is expected. Normal erosion control measures will be used during construction. g. About what percent of the site will be covered with impervious surfaces after project construction (for example. asphalt or buildings)` 8% h. Proposed measures to reduce or control erosion, or other impacts to the earth, if an} - Standard erosion control measures used in the construction industry. 2. Air a. What types of emissions to the air would result from the proposal (i.e.. dust, automobile. odors, industrial wood smoke) durine construction and when the project is completed''. If any, generally describe and give approximate quantities if known. During construction the project will produce dust from heavy equipment plus burning of the brush and slash on the site. The project will produce smoke from fireplaces after completion. b. Are there any off -site sources of emissions or odor that may affect your proposal'' If so, generally describe. None known c. Proposed measures to reduce or control emissions or other impacts to air, if any: Standard construction practices will be used to reduce dust during construction. -3- TO HL COMPLETED Bl APPLICANT EVALUATION FOR AGENCY USE ONLY 3. Water a. Surface: 1) Is there any surface water bode on or in the immediate vicinity of the site (including near —round and seasonal streams, saltwater, lakes, ponds, wetlands)? If yes, describe type and provide names. if appropriate, state what stream or river it flows into. Small stream.on north side of the project. 2) Will the project require an\ work over, in, or adjacent to (within 200 feet) the described waters? If yes, please describe and attach a%-ailablc plans. The project will be built within 200 feet of the stream. 3) Estimate the amount of fill and dredge material that would be placed in or removed from surface water or wetlands' and indicate the area of the site that would be affected. In- dicate the source of till material. No fill or dredge material will be placed or removed from the stream. 4) Will the proposal require surface water withdrawals or diversions? Give general de- scription, purpose, and approximate quantities if known. No such modifications are expected. 5) Does the proposal lie within a 100—year floodplain? If so, note location on the site plan. None known 6) Does the proposal involve any discharges of waste materials to surface waters? If so, describe the type of waste and anticipated volume of discharge. The project is not expected to discharge waste material to surface water. b. Ground: 1) Will ground water be withdrawn, or will water be discharged to ground water? Give general description, purpose, and approximate quantities if known. No such action is expected. 2) Describe waste material that will be discharged into the ground from septic tanks or other sources, if any (for example: Domestic sc\vage; industrial, containing the following chemicals . . .; agricultural, etc.). Describe the general size of the system, the number of such systems, the number of houses to be served (if applicable), or the number of animals or humans the system(s) arc expected to serve. Waste material will be discharged into the public storm and sanitary waste sewers. _a TO BE COMPLETED BY APPLICANT EVALUATION FOR AGENCY USE ONLY e. Water Runoff (including storm water): 1) Describe the source of runoff (including storm water) and method of collection and disposal, if and, (include quantities, if known). Where will this water flow? Will this water flow into other waters? If so, describe. The storm water will be collected from the house gutters and stored in the storm water retention tank, this feeds into the public storm sewer system.. 2) Could waste materials enter ground or surface waters? If so, generally describe. N-o such effect is expected. d. Proposed measures to reduce or control surface, ground, and runoff water impacts, if any: Storm water retention system will be used. 4. Plants Check or circle tv es of v getation found on the site: deciduous tree: I r a le aspen, other evergreen tree it cedar pine, other shrubs crass _ pasture _ crop or °rain _ wet soil plants: cattail, buttercup, bullrush, skunk cabbage, other _ water plants: water lily, eelgrass, milfoil, other _ other types of vegetation b. What kind and amount of vegetation will be removed or altered? One 4' diam. Fir, one 1' diam. Cedar, plus 10 Alder will be removed. Miscellaneous brush and blackberries for clearing the site for constructi.or c. List threatened or endangered species known to be on or near the site. No threatened or endangered species are known to be on the property. d. Proposed landscaping, use of native plants, or other measures to preserve or enhance vegetation on the site, if any: As many of the major trees are planned to be left,as is and to use the native growth on site for landscaping. S. Animals a. Circle any birds and animals which have been observed on or near the site or are known to be on or near the site: birds* aw heron, eagle, son bi other: Quail mammals: deer, bear, elk, beaver, other: 5Cjuil Tel'S , '(ga'co'oris' fish: bass, salmon, trout, herring, shellfish, other: ...... b. List any threatened or endangered species known to be on or near the site. No threatened or endangered species are known to exist on the site. -5- a TO BE COMPLETED BY .APPLICANT e. is the site part of a migration route? If so, explain. The project is not known to be on a migration route. d. Proposed measures to preserve or enhance wildlife, if any: Bird and racoon feeding during the winter. 6. Energy and ?natural Resources a. What kinds of enerey(electric, natural gas, oil, wood stove, solar) will be used to meet the completed projectneeds? Describe whether it will be used for heating. manu- facturing, etc. Electrical for lighting and general use. Natural Gas for heating. Wood Stoves. b. Would your project affect the potential use of solar energy by adjacent properties? If so. generally describe. No, such effect is expected. EVALUATION FOR AGENCY USE ONLY c. What kinds of energy conservation features are included in the plans of this proposal? List other proposed measures to reduce or control energy impacts, if any: Will be designed to meet the Washington State Energy Code. 7. Environmental Health a. Are there any environmental health hazards, including exposure to toxic chemicals, risk of fire and explosion, spill, or hazardous waste, that cou4_occur as a result of this proposal? If so, describe. No such effects are expected. I) Describe special emergency services that might be required. Public fire and police services. 2) Proposed measures to reduce or control environmental health hazards, if any: No such measures are expected to be necessary. b. Noise 1) What types of noise exist in the area which may affect your project (for example: traffic, equipment, operation, other)? None known 2) What types and levels of noise would be created by or associated with the project on a short—term or a long—term basis (for example: traffic, construction, operation, other)? Indi- cate what hours noise would come from the site. Short term effects during the construction activities, 7am - 5pm Car,traffic from project on a long term basis. TO BE COMPLETED BY APPLICANT 3) Proposed measures to reduce or control noise impacts, if any: No such measures are expected to be necessary. 8. Land and Shoreline Use a. What is the current use of the site and adjacent properties? Residential b. Has the site been used for agriculture? If so, describe. EVALUATION FOR AGENCY USE ONLY No such use is evident or known to of occured on the site. c. Describe any structures on the site. No structure present on site, d. Will any structures be demolished? If so, what? None e. What is the current zonine classification of the site'. Residential, single family f. What is the current comprehensive plan designation of the site? Residential, single family g., if applicable, what is the current shoreline master program designation of the site? Not applicable h. Has any part of the site been classified as an "environmentally sensitive" area? 11 so, specify. The site is known to be on an environmentally sentive area. i. Approximately how many people would reside or work in the completed project? It is expected that 2 people would reside on the site. j. Approximately how many people would the completed project displace'? None k. Proposed measures to avoid or reduce displacement impacts, -if any: No such measures are expected to be necessary. 1. Proposed measures to ensure the proposal is compatible with existing and projected land uses and plans, if any: The project will be built to comply with local code zoning -7- TO BL COMPLETED R1 APPLICANT EVALUATION FOR AGENCY USE ONLY 9. Housinb a. Approximately how mane units would be provided, if any? Indicate whether high, mid- dle, or low—income housing. The project is composed of one single family residence. b. Approximately how many units, if any, would be eliminated? Indicate whether high, middle, or lo%%—income housing. None e. Proposed measures to reduce or control housing impacts, if any: No such measures are expected to be necessary. 10. Aesthetics a. What is the tallest height of any proposed structure(s), not including antennas; what is the principal exterior building material(s) proposed? Project restricted to 25' height limitation. Project will have a (�riQk ant0 Cedar s� di.ng . b. �� hat views tote immediate vicinity would be altered or obstructed? The two residences located to the East would be altered by the ppro �ect. Current views wowld not b.F obstructed. c. Piopos�d measures to reduce or control acstnettc impacts, ► any: No such measures are thought to be necessary. 11. Light and Glare a. What type of light or glare will the proposal produce? What time of day would it mainly occur? Light would be generated during evening and morning hours for general lighting of the project. b. Could light or glare from the finished project be a safety hazard or interfere with views? No such effect is expected. c. What existing off —site sources of light or glare may affect your proposal? No off site sources are expected to effect the site. d. Proposed measures to reduce or control light and glare impacts, if any: No such measures are expected to be necessary. 12. Recreation a. What designated and informal recreational opportunities are in the immediate vicinity? No such opportunities are known. b. Would the proposed project displace any existing recreational uses? If so, describe. None expected to be effected. U I • TO BE COMPLETED BY APPLICANT EVALUATION FOR AGENCY USE ONLY c. Proposed measures to reduce or control impacts on recreation, including recreation op- portunities to be provided by the project or applicant, if any: No such measures are expected to be necessary. 13. Historic and Cultural Preservation a. Are there any places or objects listed on, or proposed for, national, state, or local preser- vation registers known to be on or next to the site'' If so, generally dcscribe. No such places are known to exist in the adjacent areas. b. Generally describe any landmarks or evidence of historic, archaeological, scientific, or cultural importance known to be on or next to the site. No such items are known to exist next to the site. C. P70DOsed me_sures to reduce or control i—v 5, if any: No such measures are known to be necessary.. 14. Transportation a. Identify public streets and highways se--ving the site, and describe proposed access to the existin,2 sire_, system. Show on site plans. if any. Driveway from project to the street to be built. b. Is site currently served by public transit'.' If not. what is the :approximate distance to the nearest transit stop'? No, nearest transit stop is unknown. c. How many parkin: spaces would the completed project have? How many would the project e!iminate? A three car garage will be included in the project, no parking d. Will the proposal require any ne%v roads or streets. or improvements to existing roads or , e 1 im i n a t e d . streets. not inc!udin__ driveways` If so. ::ener;ally dcscribe (indicate whether public or private). No such improvements are known to be required. e. Will the project use (or occur in the immediate vicinity uf) water, rail, or air transporta- tion" If so, generally describe. No such requirements are expected. F. How many vehicular trip, per day would be generated by the completed project*.' If known, Indic ate when peak volumes wuuld uccur. Normal traffic from single family residence is expected TO BE COMPLETED BY APPLICANT EVALUATION FOR AGENCY USE ONLY g. Proposed measures to reduce or control transportation impacts, if any: e No such measures are expected to be necessary. 15. Public Services a. Would the project result in an increased need for public services (for example: firc pro- tection, police protection, health care, schools, other)? if so. generally describe. No such incT.eases are expected to be necessary. b. Proposed measures to reduce or control direct impacts on public services, if any. No such measures are expexted to be necessary. 16. utilities a. Circle utilities curr tefi Iv available at the site: ectricit�V' natural eas, water, cruse ser•- ic telephone anitary sewer septic system other. b. Describe the utilities that are proposed for the project, the utility providing the service, and the general construction activities on the site or in the immediate vicinity which might be needed. Extension of Natural Gas to the site by Washington Natural Gas C�-,. Extension of the existing utilities from the street to the project. Electricity - Puget Power Telephone - GTE Sanitary Sewer - City of Edmonds C. SIGNATURE The above answers are true and complete to the best of my knowledge. I understand that the lead agency is relying on them to make its decision. Signature:............................................................... Date Submitted: .......................................................... -10- EVALUATION FOR TO BE COMPLETED BY APPLICANT AGENCY USE ONLY D. SUPPLEMENTAL SHEET FOR NONPROIECT ACTIONS (Rezones, Code Changes, Annexations, etc•) (do not use this sheet for project actions) -Because these questions are very general, it may be helpful to read them in conjunction with the list of the elements of the environment. When answering these questions, be aware of the extent the proposal, or the.types of activities likely to result from the proposal, would affect the item at a greater intensity or at a faster rate than if the proposal were not implemented. Respond briefly and in general terms. 1. How would the proposal be likely to increase discharge to water; emissions to air; pro- duction, storage, or release of toxic or hazardous substances; or production of noise? Proposed measures to avoid or reduce such increases are: ?. How would the proposal be likely to affect plants. animals, fish, or marine life? Proposed measures to protect or conserve plants, animals, fish, or marine life are: 3. How would the proposal be likely to deplete energy or natural resources? Proposed measures to protect or conserve energy and natural resources are: 4. How would the proposal be likely to use or affect environmentally sensitive areas or ar- eas designated (or eligible or under study) for governmental protection; such as parks, wil- derness, wild and scenic rivers, threatened or endangered. species habitat, historic or cultural sites, wetlands, floodplains, or prime farmlands? Proposed measures to protect such resources or to avoid or reduce impacts are: S. How would the proposal be likely to affect land and shoreline use, including whether it would allow or encourage land or shoreline uses incompatible with existing plans? 1i TO BE COMPLETED B1APPLICANT EVALUATION FOR AGENCY USE ONLY Proposed measures to avoid or reduce shoreline and land use impacts arc: 6. How- would the proposal be likely to increase demands on transportation or public scr- vices and utilities' Proposed measures to reduce or respond to such demand(s) are: 7. Identify, if possible, whether the proposal may conflict with local, state, or federal laws or requirements for the protection of the environment. Description of proposal STREET FILE -15- 7 DETERMINATION OF NONSIGNIFICANCE Single familv residence Proponent Joe & Jan Conner Location of proposal, including street address, if any 16525 74th Pl. W. Edmonds, WA 98020 Lead agency Edmonds Planning Division FILE # The lead agency for this proposal has determined that it does not have a prob- able significant adverse impact on the environment. An environmental impact statement (EIS) is not required under RCW 43.21C.030(2)(c). This decision was made after review of a completed environmental checklist and other information on file with the lead agency. This information is available to the public on request. f-vl There is no comment period for this DNS. This DNS is issued under 197-11-340(2); the lead agency will not act on . this proposal for 15 days from the date below. Comments must be submitted by Responsible official Richard Schipanski Position/title Code Enforcement Technician Phone 771-3202 Address 250 5th Ave. N. Date Mav 5, 1989 Signature You may appeal this determination of nonsignificance to Hearing Examiner at 250 5th Ave. N., Edmonds, WA 98020 no later than 5:00 P.M., May 15, 1989. by letter You should be prepared to make specific factual objections. Contact Rich Schipanski to read or ask about the procedures for SEPA appeals. 177 There is no agency appeal. al . STREET FILE FAD CITY OF EDMONDS Z CONSTRUCTION PERMIT APPLICATION1 OWNER NAME: NAME OF BUSINESS ZMAILING ADDRESS 0 14537 NE 43rd Place, N1302 CITY TELEPHONE NUI Bellevue, WA 98007 1883-3055 NAME PERAGINE, Christopher F- w ADDRESS C/o ARC Architects. 1201 E Howell Cc CITY TELEPHONE NUMBER ,Seattle, WA 322-3322 NAME. Goodnight Construction Co. ADDRESS ° 7522 Woodscreek Road U = CITY TELEPHONE NUMBER Monroe, WA 252-7129 STATE LICENSE NUMBER GOODNCI146C5 Legal Description of Property - include all easements _ (show below or attach two copies) As attached. PARCELS B & C 5131-000-088-0600 IAdJ NEW IC GI RESIDENTIAL Li PLUMBING ADDIALTER COMMERCIAL 1:1MECHANICAL REPAIR APT. BLDG. El SIGN TE El(ENCE DEMOLISH OR FILL x—Fn CARPORT REMODEL GARAGE SWIM POOL WOO RETAINING WALL/ ❑ SERTTVEI ROCKERY a RENEWAL NUMBER OF STORIES NUMBER OF 2 DWELLING UNITS 1 NATURE OF WORK TO BE DONE (ATTACH PLOTPLAN) PERMIT NUMBER 74th Place W. EDMONDS, WA �- 2 i 0 PUBLIC RIGHT OF WAY PER OFFICIAL STREET MAP. TESCP EXISTING - 6-0.....- REQUIRED DEDICATION-0......-. APPROVED BY PROPOSEK: RIGHT OF WAY CONSTRUCTION PERMIT REQUIRED STREET USE PERMIT REQUIRED . IEW BY SEE ENGINEERING MEMO DATED _ �_ ,If i REMARKS i�i' u,ld � � h11y�6 .1_sT/406/7e) / ,tea METES VSI ��I BUILDINSUPPLY SIZE FIXTURE �1N�S REM r ZEQib SIGN AREA ENV. REVIEW ADS NO. ALLOWED I PROPOSED I COMPLETE I EXEMPT VARIANCE OR CU PLANNING REVIEW BY DATE SETBACKS - FEET HEIGHT I LOT COVERAGE FRONT SIDE REAR CKED BY TYPE OF CONSTRUCTION C%OCD�E HEIGHT , ' ` CIAL INSPECTOR AREA OCCUPANCY OCCUPANT GROUP LOAD [REQUIRED YES NO ARKS OGRESS INSPECTIONS PER UBC 305 � W214MW 60AE� PLAN CHECK FEE BUILDING PLUMBING MECHANICAL This Permit covers work to be done on private property ONLY. GRADINGIFILL Any construction on the public domain (curls, sidewalks, driveways, marquees, etc.) will require separate permission. STATE SURCHARGE Permit Application: 180 Days ENERGY CODE Permit Limit: 1 Year - Provided Work is Started Within 180 Days "Applicant, on behalf of his or her spouse, heirs, assigns and N successors in interest, agrees to indemnify, defend and hold w harmless the City of Edmonds, Washington, its officials, 7i employees, and agents from any and all claims for damages of G1 whatever nature, arising directly or indirectly from the issuance i of this permit. Issuance of this permit shall not be deemed to PLAN CHECK DEPOSIT 0 7 modify, waive or reduce any requirement of any city ordinance = nor limit in any way the City's ability to enforce any ordinance TOTAL AMOUNT DUE provision." I hereby acknowledge that I have read this application; that the information given is correct; and that I am the owner, or the duly ATTENTION authorized agent of the owner. 1 agree to comply with city and THIS PERMIT state laws regulating construction; and in doing the work authoriz- AUTHORIZES ed thereby, no person will be employed in violation of the Labor ONLY THE Code of the State of Washington relating to Workmen's Compensa- WORK NOTED tion Insurance. INSPECTION DEPARTMENT SIGNATURE (OWNER OR AGENT) TE SIGNED r1.30.89 1 CITY OF EDMONDS A�ETION 771-3202 IT IS UNLAWFUL TO USE OR OCCUPY A BUILDING OR STRUCTURE UNTIL A FINAL INSPECTION HAS BEEN MADE AND APPROVAL OR A CERTIFICATE OF OCCUPANCY HAS BEEN GRANTED. UBC 'I-'AP-_R ,t VALUATION FEE 52r --200 %90-T- APPLICATION APPROVAL This application is not a permit until signed by the Building Official or his Deputy; and fees are paid, and receipt is acknowledged in space provided. OFFICIAL'S SIGNATURE DATE RELEASED BY: DATE ORIGINAL — File YELLOW — Inspect PINK — Owrer GOLD — Assess6k cr w Z 0 Z w M Uj a 3 0 Z 0 m 4.2z Ole?" ly6V* 45" Sg'l 372 70 367.9E �B� 09,2 7-57 z Z.Vuu z F 9 0,1740 fT L-r-7 53 410' oc 303.80 57 zo / ��c�,,er�rr JE e4e to -T- c cp CO W W A 4b, I. th ,� • .. Q / CJJT 9 MEMO TO: Permit Coordinator, Building Division FROM: Dan Smith, Engineering Inspector ADDRESS: 5- %�l 14"liYl� OWNER: After review of the subject building permit application, we have the following comments: 1) Construction hours are: WEEKDAYS 7:00am to 10:00pm WEEKENDS/HOLIDAYS 10:00am to 6:00pm 2) A Right -of -Way construction permit is required for any work on City property. 3) Connection to City water system required. 4) Connection to City sanitary sewer system required; obtain separate permit. 5) Water and sewer lines to -be separated by 10 foot minimum.' 6) Driveway must be paved a minimum of 20 feet back from City right-of-way; separate permit required. 7) Driveway slope not to exceed-14%. It t% Cy4,1Wr&-4 8) Back water valve -required if downstairs.plumbi.ng i.s below elevation of upstream manhole. 9) Builder/Owner responsible for containing all temporary runoff and erosion control on site. Construction may not impact neighboring properties in any way. 10) No burning of construction refuse without approval from Fire Dept. 11) Street to be kept clean of debris, dirt, mud, and construction materials. Contractor responsible for dust control. 12) Inspection required on drainage system, catch basin installation, driveways, and sidewalks. A final engineering inspection is required prior to the building division granting occupancy.' ! i Ll 0:0514 40 fr— 44VATr:- 6w 1616 Yam' OF 45i KAW U �-Ar- F9 " , ��� � � zaps 3C5 A 1-40kc,'g 96rTy VP AT 14 MW* -Ay A4---A j,,4N,.( z�E4oF Hgowy ��TCIC'S.tG:tft.�i•.! TAG , # . wqlcr� A .Gil " kvm�e, rp?m Z21n Poll _ rz'-►ice" I•t't""--- ; 1 F� i1 4riNO:o!5:44 r6rInNe,v= ii4+ff Q�6 ! kiply ma6r op ��44 Gc� � IG 'c'A � 4f 6if P UI- F9 f+-w = 1067 't" a c -� �- ��0011 STREET FILE 'sq �'TO _ � i"�-,�Z.�IC� = �..I-�Z', fr'+�'' t�l-�"(t1F✓1 I �Z�� ,, , M'$..�`*�s"��."� � �,� ,,4�' e "IV " ' 1m U 1-'1 wf I4&rf- " (A'e� e,f .4&T'" t �' 'T� '' 1� ,, `tom r _... _� � � '�yS+?' �1��✓✓a" s . � f 1� y�i+��'�" ' .'�,'` tC✓ . �:���"r" �,,,' �G"Y� fi Yl � r rl ' rpmr Of 90NIJNDS UK DEPT. CONDITIONAL PERMIT WORK-,5/C ADDRESS- /6.52,57 7q /°L OWNER- I /VI%',zp_ APPROVED DATE - BY BLDG. OFFICIAL KEEP THESE STAMPED PLANS ON JOBSITE FOR ALL INSPECTIONS PERMIT NO. SHE © l OF r { Y + ,.... ,�,�. r. xe�«�•w._^*�_ .. max. -rear, �• �; �. ---- \ -�" . FLU �. �=tJ E%�'� � E' Se � "-" •!�� ,,, � � � � •- - u rs �� I �4' A rLbt,15110 1W d Y' ` a I P w �,A P AI--�• w=a s' Lr rly c i ty N J � �i i i � �.. �,1.� Cvr I ." 1 F'# 'al 4r- -4- 7141,14...n ,... ,._.._..�......�.__...�...w. �' �/♦ ;�ryy /� ✓ y��[� }.}_ yt y�Y � J yam {y� t 6sA5 _74-N' PL - 'der._"" ^�' M�iy I� ywy % ,.A��I1 �Y^ �(/ �1�`I • . l M" i" i fYF-'i�l 1 �� - i III► 1 ' i bi ice' . 1`` 1 c t { e �� % `�`" x'�i }� f,.• r /'i J 4r:"�r"r•r"• .r-• y 14 1 ,r� iw/* yyr'�. ?�' ^! ( ',a..•' 'f tplAI we'i �w+ W�*++'-�wr' f:, `;r �' i !�"*rx}"''" 1 '` 1 •iZ ` �:� f �; "* , ', x, J �, '' f - r✓' f !'! e•'i.,,. y f'"� � y _.,�, - ,� - •. 11aw ✓1 �' �R } ��{ ,*' f � � � I I JAY, JJ�r 1 iP '� rG'" " ✓ / L+" i'i A •� i �y i (m ./?' x x ��a„ ,w i` i f ��'i '^�c.r !`f 'I� e+ - . , ,_ .. j'� '• i 7"'�i"11 �',i - � ��� C ��'�#• i�. M"-'::"gC �� � '' ' � � 't�;�' 1 , 1 � � � �y �ti/ ��y g �,r ,� � f( .� _ � ,�r l't� _. �! s�,,•�,,,, 'u ir' y/ J+"'�1 i t' �'"- F 4r.+�� - ]J} y i �y�� _ 1 _ F ` `;t Y >-..�` �{ T- i _�. ...•.....r.-..«+ +..,,,..,>-r��' �""'r ." i ♦. it 1 �4� 1� J 2 • :,� "'` .1"' > 1 t l (�� Of 0 I �' M •;t � ._. ._ � - l � i,.11 Af ��/�� '1 ♦ � � _ , - 0 �j t� � �-_ . � , � ,. x �,� .✓ x - �. / � � -i � 'jq x, - � • } �� i - i�i � ,; "' ' n� �" - � t r •-i � � A � ,/ i j(j yf � - rl 1:�_" • rl ZONE SETBACKS: FRONT SIDE REAR OTHER HEIGHT _---...._..._,.. Rir;cir;IvF.D MAR 3 1 RE'q A'ewa PERMIT COUNTER �uL s�T j 1 1 F11 oW I �"lp I © 'do- � M �1��* � ,c>fl-" f-, *� fr-0 ,lam p�K CCU ., --r;o 000 S ,�'�::: •ICI t'1 }4Y� ��ht"'"' ���..�-,� ; I • J . t a i ntfi` 1 j_•w / i • +4'yrr,�y.r`6r' J r ,' zr���� ?"� 1' .�,j3 a.. �.t � ..."e"•"'. 'G'i Gr'r "�,) � ;y 1 ( { j �� � I�T , � ����. ' *^ `' .,�-� � • -..�„ , A � r� ° � ,� ,'. ��.. , x � ,�s' � ...X{ r .its, � � � 1 1 •� � � t x `. �� � I � � �-.. � `�� � � � ' n� � - �� � � _ ! Ik `' t '. .'yi 13 i S � � � � i � � •\� S% �0 i� i �+, F. � w�� � I • V .A woo .�"'� /�r / y�r„% , J, r � � . {f a % •r � ;{ � �} 4 y • ' j f �' ply-i.3�t�% t . 144 g i i' I� t SSasX� aj