20924 80TH PL W.PDF111111111111 7316 20924 80TH PL W STREET FILE Rea, wtaaa" & 4"Oaar", 970te. ENGINEERS a SURVEYORS e PLANNERS 324 Main Street 6 Fdrnonds, Washin0on 98020 December 19, 1978 File No..7159 Revised January 26, 1979 STORM DRAIN RETENTION CALCULATIONS FOR TRI-PLEX OF JOHN ECKER 1. Area'= 68.90(20)+93.90(67-50) = 7716.3 = 0.177 ac. -4-3, —560- 43,56o 2. Slope = 103.0 - 100.0 = 2.65% from NW corner to SE corner 113.0 3. Site condition: Jight grass to bare ground 4. Existing coefficient of runoff = CEX = 0.20 Using the Yrjanainen - Warren method to determine the retention volume necessary to detain 100% of a 10 year frequency storm: Longest distance from headwaters to point of diskcarge = 113 feet Overland flow velocity 1.63 f-P-s- 2.65% @ site conditions noted above - Chart I Time to concentration L/V(60) + 10 (113)/(1.63)6o + io = 11.16 min. Intensity ilo = 1.53 in/hr from Seattle curve for 10 year storm - Chart 10 Qallowable Qexisting = Cexij0A = (0.20)(1-53)(0-177)-0.054 c.f.s. Prorate future -coefficient of runoff: W35) Gravel 0.028 ac. @ 0.70 V3,560 = 0.020 ac. I Roof & concrete 25,252 0.058 ac. @ 0.90 43,560 = 0.052 ac. Asphalt driveways 63.2(27-3)+5(26) 0.042 ac. 0--85 = 0.036.ac. TT560 Planter area 0.177 - 0.128 0.049 ac. 0.20 = 0.010 ac. 0.177 ac. OTI ac. Cfut 0.118 ac 0.667 0-177ac. QO Qal 1 0.054 0.459 c.f.s./AC - -F Cfut AT (0.667)0.T-77 T -:2 5 +V T17�6:2:-' - 2 5 + /17 6 2 36-97 min. Q 00 o \/TO-V59) Vs (2820)T 40QoT (2820)(36-97) - 40(0.459)(36-97) 1003 .6 ft.3/ACfut T+25 (61-97) Vtotal = Vs(A)Cfut = (1003,6)(0-177)(0.667) = jig ft.3 KI H N I C I PA L 1: N C, I N FE. k I H 0 W A 1 1: R '*, 1) I'P L Y WA �', 1 1: 1 K I A I N1 L N I '. I 1 1: V I Y'� ", (. A 1, A 1. 1 1., A I I � I t, I r 11 1 k I N A I I? I'0 R 1 11 1. A t,j r,i i r,j c. r, n i i c. rJ 0 1\1 A P I N A S P0 k 1 1, 1 H 1) 11 '. I R I A 1 1) 1 \1 I I I' K I I H I * I I A ', I It I I I I I I 1 1) 1 1 December 19, 1978 File No. 7159 Revised January 26, 1979 Page 2 STORM DRAIN RETENTION CALCULATIONS FOR TRI-PLEX OF JOHN ECKER (cont Size the retention system: Vol. provided by surface ponding = 119 ft.3 0, Use at least a 20-Nt wide pond x 68'x 0.5'deep at one end only (see diagram below) H ___T - "�o Vol- ( AA + FA AB + A .3 3 A B)ft 68 (5+ 5(l.8)+1.8) = 222 I't.3">reauired o.k. /c I 11c or i I' i ce: W �_ ^ do r i f VAC6-� Qex = 0.054 c.f.s. .63)_ head = max water surface less invert t�r gh elevation F 0-5 —4F----" x 12 1.38 in. = 452-59 - 451-53 = 1.06 r( 0 - 6 3 ) —17-PT __NT Use 1-3/8 in. orifice (restrict the 4" P.V.C. to 1-3/8" dia6eter using a metal'plat,e) See cross-section on drawing. Assumptions: I. The south three stalls will be ponded 0.5 ft. deep(only over'the catch basin), as shown on drawing for approximately 60 min. It will average 3" deep for 3Q min. covering only half of these stalls. 2.' Any flow over a 10 year storm will overflow out the driveway and south to the existing catch basin. 17-1 V 7, I- I i- al -or --t F --I C)l t i j A, 1, -j I -I :tz r5Z. 70 03�Z.S) MAX. V TER 5 URF9 CE 452.6 NIN AnZ A. C. PAR.KING—. LOT %jol- A 49�-Aq "V� 4,P 1 10 P .4 le �52 A -,,--7L -F - 4"P Y C. 58-90' FLOW --,N. go 80 PL W* Ae 'y -IFT it Reid, Middleton & Assok es, Inc. Engineers (D Surveyors Q Planners 324 Main St. Edmonds, Washington Oel 09 , MEET FILE DATE 7 151. ro '�& Phone 775-3434 ZFC /-[/J. 1--lVAleenty pqo/ 6j� 0�4110otlh )Cellff 6 tyd-51. U'O WV& > Hect )O.f 6-h 4 e be.. "-a411145- -ow. back O.Owd— RTRFET FILE BUILDING DEPARTMENT Applicant Fill Inside Heavy Lines PERMIT APPLICATION NAME (OR NAME OF BUSINESS) Aw 1�'Ii -R w MAILING ADDRESS z 3: 7/11 0 CITY TEL PHZINE �NUMBER A716- 4� r7 _3 NAME U W ADDRESS u m . T E LEPHONE NUMBER It LY 13 7 NAME iiW7 0 ADDRESS u. 2 CITY TELEPHONE NUMBER Z A y/i/V 0 9 o U STATE LICENSE NUMBER CITY LICENSE NUMBER C Legal Description of Property (Show Below or Attach Four Copies) j 'r"r -4 --? / A,-VVt11),t1 z U IA W a .J W J GAS NEW RESIDENTIAL 11 L:NE I FRONT FIRE ZONE ADD El NON-RESIDENTIAL DEMOLISH EXCAVATE ALTER OR FILL r [:] S G N F_j RETAINING WALL FENCE D SPECIAL INSPECTOR REQUIRED El YES El N 0 PLAN CHECKED BY Fl REPAIR PRE -MOVE 1:1 INSP. swim POOL . REMARKS Z NUMBER OF STORIES Num ER OF DWELLING UNITS NATURE OF WORK TO BE DONE Ir u W m 0 PLAN CHECK FEE P.ROPOSED USE K PLOT PLAN JINDICATE BUILDING SETBACKS. IBUILDING ABUTTING STREETS) VO) -Applicant, on behalf of his or her spouse, heirs, :issigns and W _J successorh iii inmei. ai!rcc, I,) indcmnil'�, defend and hold harmicss I. the City of Edmonds, Washington, its.01licials, employees, anti agents from any'and all claims I'm damar" id whawyer witure, T mkhi)� dit- ik, i-r iii(Iii,-ciiN f1mil flic PLUMBING MECHANICAL FENCE SIGN RETAINING WALL USE PERMIT ZONE NUMBER JOB ADDRESS oclols — EGAL NAME SUBDIVISION NO. YES ONO 7 PUBLIC RIGHT OF WAY PER ORDINANCE NO. EXISTING RIGHT OF WAY PROPOSED RIGHT OF WAY DEFICIENCY OF RIGHT OF WAY STREET/UTILITY WORK REQUIRED 9YES NO PERMIT FOR WORK IN PUBLIC R/W �tYES 0 NO UNDERGROUND WIRING REQUIRED ES 0=0 CONNECTION TO SANITARY SEWER �yy ES Cl NO SEPT�C TANK PERMIT REQUIRED YES NO SEPT C TANK PERMIT NO. SEE MEMO DATED REMARKS CHECKED BY METER SIZE UILOING SUPPLY SIZE it I B SIGN AREA ENV. REVIEW ALLOWED I PROPOSED C OMPLETE1 EXEMPT N j [�_ REMARKS VARIANCE OR CU PLANNING REVIEW BY DATE YARDS LOT COVERAGE SIDE REAR] PE OF CONSTRUCTION ICODE 7HEIGHT AREA OCCUPANCY OCCUPANT GROUP LOAD THIS SITE IS LOCATED IN THE CITY OF EDMONDS. LOCAL SALES TAX SHOULD BE CODED 31 . 04. VALUATION I FEE 0 U a. 2 W 3: ;WIMMING POOL MEMO TO: FROM Date — Building Division Community -Development Department Engineering Division Public Works Department SUBJECT: E'�'C:)909- nc) t:�LW -�CtN 11 V I After review of the subject building permit application, we have the following comments: I>ZT I- /-7 /-7 4L�- /7 Coordination of the location of any structure with respect to utilities, streets, property lines and driveway grades is the responsibility of the contractor. The contractor is required to keep the abutting streets cleaned of dirt and debris caused by the construction. The "Right -of -Way Construction Permit" is required, from the Engi ' neering Division.of Public Works, forany work within the Public Right -of -Way or publiceasement. Driveway slope not to exceed 14%. Connection to sanitary sewer required. Sep.tic Tank Permit required, submit design. Fire hydrant required, submit.design. Si te drainage per code # Curb /-7 Sidewalk See approved plans V/' Paving required Bond.required.for public improvements. Submit cost estimate. Underground wiring required. Approved Engineering Plans required when applicable. 7/78 P.E. City Engiticer D,,-I)arLMCIIL of 11tiblic Works V* .0 Z 51 SJUBLIC.WORKS DEPART%,01n' CliEcno BUILDING PERMIT REVIEW Date -OCC104 F�;�4pLk4dress 'Street Right -of -Way Existing REQD Access Easements Existing —_r*34 E: REQD Utility Easement Existing REQD Lot per Subdivision 1,,,r Plat Assessor Map Site Plan Checked for Accuracy --icl Undergr ound Wiring Reqd. Check Accuracy of Legal Description 77 -1 LLm4,4y_' ADO, Enviromientally Sensitive Area. Environmental Checklist Reqd. Flood Hazard Zone '.Shqrpline Management Area Slope, Soil, Vegetation .Stream, Creek, Drainage Basin Edsting Zoning Per Code Amenities Design Board Approval Reqd. ADB # Approval .Board,of Adjustment Ap-Rroval.Reqd- ReVie.w'., By: Date- 2_7 - t Z5 Existing Water T�Iain Size Cl/I Water -Main Reqd. IV A .,Service Line Reqd. Hydrant Size Existing. Hydrant Reqd. Per Fire.Code Size Detector Check Meter Reqd. Cross Connection Inspection Fire Department-, Cdanents Water Meter Charge Rcqd. RevieuT by: Date: tic Tanlr, Desim Awroved i I t-, uate: U I bh- Septic Tank Permit Reqd. Permit No.. �j Sanitary- Sewer Availability Proi. Drawing No., File No. Side Sewer Availability Sanitary Sm,7er Connection FeeReqd. L_��cj Revia.; By: AID ----A Date: #'j 0 4v= a -<f VV% I V1 I W3 U t" -A � F or q.)en Ditc1i Existing,' Reqd.. Culvert Rcqd. Size. p Catch Ba.-,in.Reqd. Tndicate'on Site Plan — Shoulder drainage mailitain collection on suale open runoff .-ht-I]iole re4d. indicate on Site Plan, Soil Conditions md Crowd Water Fie Id Cliecked 4 Fwss F zz— Review by a., t W Street Paving Reqd. H - Curb and Gutter Reqd. Sidowalk Reqd. Curb Cut for Driveway Req.d. eeq Right-of-1,.1ay Construction Pem t d. Bond Reqd. for Public Inproven-ents Street N, i)e Sign Reqd. PLher Signing Reqd. . . . . . . . . . . re Per-mit, Sl�te Inspo'ction mide on BY S R u W, 1%YffER �C4 SIRaT ENIGINE TUNG ..to oominity ev opi-mnt De s listed i C D el Speci.-A Requirei-iient III kmemo partamnt C 11f;', 01N.LS1011 BY Date 0 X, All itu-ns filled' in on Building e 't Appli(�ation re IN BY -ite Dz 1. Drawings Staiiped and Notations �! I �, Dc <4 �jApproved by Public '%.,W-ks Depa.rti-,miL RE.-vi-Sed: 1.v 10-1977 Z PUBLIC.1-.URKS) DE1'AM*M1'-',NC C11]-:CKf,1ST BUILD NG PEMIT REVIB4 Street Right -of -Way Existing - / 5-- 7c/' W--QD — Access Easements Existing REQD Utility Easement Existing :s REQD Lot per Subdivision J,fr 'J Plat Assessor Map Site Plan,Checked for Accuracy I --ici U-iderground Wiring Reqd. Chec1c Accuracy of Loegal Description -a-t 'Ici Lk )OAA)?— a'00 EnvircTuixantally Sensitive Area Envirormiental Check -list Reqd. Flood Hazard Zone Ilk # Shoreline Manacrement Aiea e Slope, Soil, Vegetation l )I btre.-n, ureek, urainage basm Existing Zoning Per Code 4 Amenities Design Board Approval'Reqd. ADB # Approval I e �N%' Board of Adjustment Apqr WN RevieT,-7 Bv: iS�isting Nater MlaiWiSlize Reqd. Date: Water Main Reqd. AIA W 11 v. I Service Line Reqd. P4 t Hydrant Size Existing E-4 W"I 4 i vs Hydrant Reqd. Per Fire Code NA Size Detector Check Xleter Reqd. Cross Connection Inspection Septic Tank Permit Reqd. --ALI Pennit No. 1'i I t, Proj. Sanitary Sewer Availabilivr_--�C-� ess, 0"-- I Drawing No. File No. L__ X2. 1 cc Side Sewer Availability C ;4 Sanitary Sewer Connection Fee Reqd. kj<�, C V) Revia,; By: Date: C) )'BUILDING .,,NAME DEPARTMENT PERMIT APPLICATION Applicant Fill Inside Heavy Lines USE PERMIT ZONE NUMBER.. R mL- JOB - _j LIP ADDRESS a 0 (OR NAME OF BUSINESS) W z 3: 0 ec C El EGAL LOT ES ONO PLAT NAME L L J`114K, SUBDIVISION NO. Lo T- # 7 0 3: U IL MAILING ADDRESS �74 PUBLIC RIGHT OF WAY PER ORDINANCE NO. EX I STING RIGHT OF WAY - PROPOSED RIGHT OF WAY DEFICIENCY OF RIGHT OF WAY CITY TELCPHONE NUMBER U . t 1 U It NAME ADDRESS - . I :)L'—;I Jz' STREET/UTILITY WORK REQUIRED 9YES El NO PERMIT FOR WORK IN PUBLIC R/W YES C ]NO >k UNDERGROUND WIRING REQUIRED ?CY ES 0 CONNECTION TO SANITARY SEWER YES El NO X SEPTIC TANK PERMIT REQUIRED El YES NO SEPTIC T�NK PERMIT NO. CITY ITELEPHONE NUMBER ct 13 7 0 U NAME ADDRESS /loy "'C�' 0 1, 6 . Rs o .2 ��_ / /­ SEE MEMO DATE 0 .( M z 0 CITY X L//J/V WC) 0 TELEPHONE NUMBER '�S 69?) REMARKS STATE LICENSE NUMBER CITY LICENSE NUMBER CHECKED BY C rj AMS wCr Legal Description of Property (Show Below or Attach Four Copies) L 0 4:/ METER SIZE B UILDING SUPPLY SIZE w I`_ REMARKS z 0 IL SIGN AREA ENV. REVIEW ADB NO. m U In ALLOWED PROPOSED COMPLETE EXEMPT SHORELINE REMARKS VARIANCE OR CU NNING RE 7 VIEW BY DATE YARDS . FRONT SIDE REAR ILOT COVERAGE GAS NEW RESIDENTIAL LINE ADD NON-RESIDENTIAL S ' IGN F� RETAINING DEMOLISH WALL ALTER EXCAVATE FENCE DOR FILL I— X—FT1 REPAIR El PRE -MOVE: swim INSP. POOL FIRE ZONE TYPE OF CONSTRUCTION I . . I .1CODE HEIGHT SPECIAL INSPECTOR JAREA REQUIRED 1-1 Y E: S . 0 NO OCCUPANCY GROUP I OCCUPANT LOAD PLAN CHECKED BY THIS SITE IS LOCATED IN THE CITY OF EDMONDS. LOCAL SALES TAX SHOULD BE CODED 31.04. REMARKS Z It. U tA w 0 z w CL w NUMBER OF STORIES 1"UMB ER OF DWELLING UNITS NATURE OF WORK TO BE DONE —,-' PLAN CHECK FEE VALUAT'ION FEE PROPOSED USE w U in w 0 I CL 0 J w w (3 PLOT PLAN. (IN"DICATE BUILDING TBACKS ABUTTING STREETS) BUILDING 1> PLUMBING MECHANICAL FENCE t z 0 U SIGN in in W, .J 2 r Applicant, ill behalt' of lik or her spouNe. heirs. assigi I successors ill iliteresl' avrecs to &ICild 311d hold harmless tile City of F(JI1101lds, Washiii,,imi, its officials, employees, anO agents from ;mN, aml all chims for ilaiwq�vs it' whatever ilattire,' alisilly dilovily m illklilvclk fl�jlll Ill,' d till, l".111lit. ksll- RETAINING WALL :;WIMMING POOL a CITY OF E0MF0PJDS CIVIC CGNT�R - GDMONDS, VASHINGTON 98026 - (206) 775-2525 COMMUNITY DEVELOPMENT DEPARTMENT June 13, 1979 30 John M. Ecker 7119-165th Pl. S.W. Edmonds, Wa.'98020 CHANGE OFADDRESS FOR -TRIPLEX HAVE H. HARRISON . MAYOR Building permit'#790068 was issued to you on February'23rd of this year for a triplex with the address of 20904-80th Place West. We find it necessary to change the address to 20924 80th Place West. We will notify our Utility Billing Department I �' and it is your responsibility to notify all other interested parties.. Harry M. Whitcutt Building -Official HMW/ ae cc: Utility Billingvl--,< C , . STREET FILE CITY OF EDMONDS 200 DAYTON ST- EDMONDS. WASHINGTON 98020-(206) 775-2525 DEPARTMENT OF PUBLIC WORKS October 18, 1979 Ms. Phyllis Davidson Olympic Bank 4325 198th Street SW Lynnwood, Washington 98036 Dear Ms. Davidson: SUBJECT: �JOHN ECKER FROZEN FUND ACCOUNT HARVE H. HARRISON MAYOR Receipt of your letter.dated October 115, 1979,,above- subject is acknowledged. It is a policy of the City of Edmonds that all bonds or correspondence regarding bonds be received on bank letterhead. Please retype the letter on Olympic Bank letterhead and return to this office. Thank you for your cooperation. j ak Yours very truly, JAMES E. ADAMS, P.E. City Engineer 0 C T 17 1979 October 16, 1979 L)lf. Uj MIDE'�' VWNS City Of Edmonds Attn: James E. Adams Edmondst Wa. -98020 Dear Mr. Adams: I am writing today in reference to your letter regarding John &kerls frozen fund acc— ount, The account was opened here with us on Sept. 149 1979 in the amount of $1539-00 and will be due on Sept. 14, 1980. If you would like the bank to hold this bond in our collater— al box for you pleasw advise us and we will do so, We do hope this matter has been taken care of to your satisfaction and if there is anything more you need regarding this please feel free to give me a call. Phy;trulyp. t 10_44�� iZsDa'vidson Olympic Bank Lynnwood Branch STREET FILE CITY -OF EDM,1�3NDS CIVIC CENTER - FIDMONDS, WASHINGTON 98020 - (206) 775-2.525 DEPARTMeNT OF PUBLIC WORKS September 26, 1979 OlymDic Bank Attn: Phyllis Davidson P. 0. Box 2400 Lynnwood, Wa. 98036 Dear Phyllis: HARV� H. HARRISOH MAYOR SUBJECT: FROZEN FUND ACCOUN-T-----'rOR----------,---- JOHN ECKER�(20 9 2 4 80TH PL. W..). We request verification that the subject frozen fund account has been established in the amount of $1,539.00. Please advise us of the terms and conditions of this account. BF: vlw il Frankli dt. Yours very truly, JAMES E. ADAMS,' P.E. City Engineer 10-1-5--79 STREET FILE COMMIUNITY DEVELOPMENT DEPARTMENT Building.Division DATE: September 10, 1979 TO: FARR"MMMAIN PUBLIC WORKS DEPT. SUBJECT: John Ecker, TriDlex at 20924 80th Place West Please review and advise any ' outstanding requirements on above, in order that they may be given final approval and a Certificate of Occupancy issued.. PLEASE RETURN AS SOON AS POSSIBLE. THANK YOU. A*.- %Aj Ar D P, A I'FJ A C, 6- WO-F APPAOV67D Ows -r-A L L Ali o i�j V 6T %FV *PJ C_ 2 0 Harry M. Whitcutt Building Official HMq1 a e V E D 1979 V/Orks TY PUBLIC WORKS DEP FOR INSPECTION SIDE SEWER PERMIT 775-2525 Ext. 220 Permit N? 6315 Issue Date �gllll_ �5(THEt�j J-pEg�ET MUST BE POSTED ON JOB SITE 1. Address of Construction to-Z 0 Wn aip 2. Property Legal Description (include all, easements) Lrj7- #-7 Lvmay (Wdiba-A 3. Single Family Residence Multi -Family 1,� No. of Units Commercial t/ r i _P lex) 4'. Owner and,ler- Rui1der at_)h Eckje_�r 5. Contractor & License No. 'Bloom Cbn&fVVC-*0-A 6. Invasion into City Right -of -Way: No 1-100" Yes (If Yes Right-of- way Construction Permit Required - Call Dial Dig (342-5344) before excavation). 7. Cross other private property: Yes Noj��Easement required - attach legal description and county easement number. READ THE FOLLOWING AND SIGN: a. Property owners must obtain a permit to install side sewers on their property. A licensed side sewer contractor must be employed to construct side sewers in the public' right-of-way b. The side sewer contractor assumes full r';ponsibility for each installation for one year * C. Commercial establishment requires a minimum of a six inch (6")- side sewer line. d. Side sewers may not be installed closer than thirty inches ('30") to any structure. e. Side sewer lines must be laid at a minimum grade of 2% (1.150) and maximum grade of 100% (450). 0 f. No turn in side s8wer greater than 45 (1/8;bend) is 0 allowed between cleanout. All 90 turns must be constructed of a 45 (1/8 bend) and Wye with removable cap. g. No down spouts, footing drains or floor drains can be connected to side sewer system. h. Pea gravel is required for bedding when installing sewer lines through other than granular soil. i. Cleanouts are required at 30"-60" from each plumbing exit line and at minimum intervals of 100' along sewer 'line run. j. Trenches within City right-of-way must be'restored to original conditions. Contractors shall be responsible for ri ght-of-way failure due to poor compaction of fill. k.. Side sewer must be left uncovered until inspected and approved by the City. . 1. Inspection during normal working hours only. Two (2) working days notice required. DATE: -7 q . (r�i I cer*fy that Y have reaT_ 1:-117 and dhall comply With the above PERMIT FEE: Z,) DISAPPROVE D BY: Date: V By: -Date: CONNECTION FEE: WR APPROVED By: Date: * PERMIT MUST BE POSTED ON JOB SITE * VN 'A ROLE 4087 MIR B NK,,, NIX AL BON] Olyrilpic Bank will pay, at the Tammin rl Office, tile sum of 5 accordance with, &,ts-ps indicated below: FILE Issued To: john M. EOker �tiiq 165th P1. S. W. Edmonde, Wa. 98020 Date of issue Interest will be: 9-14-79 0 Added to the balance; Maturity date 0 Remitted by bank check; Intere�&_ 0 -Credited to: V I Social Security Number 573-64-5760 This ins(rurrient shall be constriied as a time certificate yee may present this hond for payment at any of deposit and is sub�jcct to all applicable R U I es a n (ate or within ten clays following any maturity Regulations with respect thereto, now or hereart" . is C1 ISS late. o interest will be paid for the 10 day redemption by the regulatory authorities and or posted in (he to -iod if redeemed during said period. the Bank. This ins(rument is assignable only on Interest shall be compounded daily on all bonds and of the issuing Branch. paid oi- added to the bond balance (11-larterly at the rate set This bond is payable in c l] r rent flinds I ts r- forth above. On monthly income bonds, interest shall be render, properly endorsed, on the 11111 17 is I c d paid monthly. above or at any subsequent maturit, cafter . The rate during any renewal period shall be the rate agreed that this boi i urity, be set forth above. The Bank maintains (he option of giving provided. 1( is , automatically renewed for succc i clual to the registered owners written notification of intent to change original term. The Bank may re i bond at any (tic rate and.of changing the rate on the following renewal maturity clate if it has given 30 days I written notice of date. If payable to two or more persons, (his bond is its intention to redeem. Notice of redemption to be mailed payable to either party or the survivor of either. to the depositor's last known address as shown on the Bank's records. &N, Authot-ized Sigtiature wgidati ... 1.% re'll'i'v a mh.,Ianlial ime)v.tt peftalo, 1,,r wifildfawal ,f Prior to Ille penally f,,r var�v vilhdai,val ahr) applimi to Non-Negoliable a renewat pel iod. ��A-I-WMXW- L4 ki I': IIDL F'I /z, .-.I- I-- + _77 % 4� J. -B. Asphalt Paving_., ASPHALT PAVEMENT SPECIALTIES 30 Pa�rking Lots, Prkveways,�Pafio s Patching and Sealer Work 22228 95th PL.W. Edmonds,WA 98020 (206) 774-6537 PROP AL SUBMITTgD TO 7n "!f� DATE 7-7 ADDRESS PHONE ,1013�!NfAME AND LOCATION 41 Z-a 7 We hereby submit specifications and est i mates, subject to all terms and conditions as set forth. 96 �/r. 14 -0Z Y -30 44e ywl�o As i-i a p,<4-7- Quotations subject to change or cancellation after 30 days. This notice is provided to you in accordance with the Federal Truth in Lending Law. A FINANCE CHARGE of 1% per month (which is an ANNUAL PERCENTAGE RATE of 12 % ) will be imposed on--Aay-pGkion--cf-.yovT--accm.nt=not-pai"ithin=3&-d���� We cannot -be responsible for subgrade failures. WE PROPOSE hereby to furnish material and labor complete in accordance with above specifications, for the sum of: -dollars ($ CJ )K WK C7 17 S' v Authorized Note: This proposal may be withdrawn by us if Signature not accepted within days. of Estimator///. I c.-7 il. -- )�'T' U .ACCEPTED: The above -prices, sped I icat ions and conditions are satisfactory and are hereby accepted. -You are. authorized to do the wo as specified. Signature Payment will be made as outlined above. 11,41, Date Signat4; MEMO TO: FROM: Date May 11, 1979 John B. Hitchell, Water/Sewer-Di- MEET FILt Fred F..Herzberg City Engineer SUBJECT: SEWER CONNECTION CHARGES -t-,-Pdmonds, Washin 80th Pl-ace Wes gton (S tree t'-Addres-i�T John Ecker (Legal.Owner) Single Family Residence Subdivision.- Plat P.R.D. Multiple - X Commercial Triplex LEGAL DESCRIPTION. Lot 7, Lumar Addition Z.F.F. Calculation: f�Connection Z.-F.F. x $ 0 Fee Lateral x( ---- $ 0 Lateral Chai--�,,e $ T' e nijival nL C�iinc �%7hen , applicable) 3 Un . it(s) x( $25- $ 75.00 Trunk Charge $ 10.00 Permit cc: 'Owner APPROVED BY: Leif R. Larson. Director of Public Works $ 85.00 TOTAL Sam �es E. Adams, Acting City.Engineer 10/78 Engineering Department Februar.v 27, 1916 We have examined the situation of ' sewer service and connection charge to the subject.property. At the southorly,qnd of 80th Place W., north of 212th, a sewer was installed by Late Comer Agreement. 'At a later date, a sewer main I was extended more than 200 feet in length which would serve the.subject lot. The Late Comer Apreement did not specifY the area of conne . ction charges so we are assuming that it only covers the property directly adjacent to the sewer. Also,, it is noted that the Late Comer Agreement expi I'll- res May 12, -197G. Since the T)ldtl'installed the set..er, it has been determined that there is no connection charge due on Lot 7.- E Date db May 11, 1979 STREET FILE MEMO TO: John B. Mitchell, Supt. Water/Sewer.Division FROM: Fred F. Herzberg City Engineer SUBJECT: SEWER CONNECTION CHARGES 20904 80th Place West, Edmonds, Washington (Street Address) John Ecker (Legal Owner) Single'Family Residence Subdivision Plat P.R.D. Multiple x Commercial Tr—ip—I—ex LEGAL DESCRIPTION: Lot 7, Lumar Addition Z.F.F. Calculation: Z.F.F. x Lateral x( ---- 3 ) Unit(s) x( $25 CC: Owner APPROVED BY: Leif R. Larson. Director of Public Works $ 0 Connection Fee' $ 0 Lateral Charge. $ Equivalent Count $ 75.00 .(I.,7hen applicable) 10.00 Trunk Charge $ Permit $ . 85.00 TOTAL -�qmj�es E. Adams, Acting City Engineer 10/78 00 Engineering Department February 27, 1916 We have examined the situation of sewer service and connection charge to the subject property. At ' the southerly end of 80th Place W., north of 212th, a sewer was installed by Late Comer Agreement. At a later date, a sewer main was extended more than 200 feet in length which would serve the subject lot. The Late Comer Agreement did not specify the area of connection charges so we are assuming that it only covers the property directly adjacent to the sewer. Also, it is noted that the Late.Comer Agreement expires May 12, 1976. Since the platf / - f�stalled the sewer, it has been determined that there is no connection charge due on Lot 7. CITY of EDMONDS Edrn TREET. FeLEe (206) 775-2525 200 Dayton Street onds, W Department of Public Works DATF: ?? TO: 9 TRANSIMTTI ING: --Ilzf>44�K Gar - AS YOU REQUESTED: FOR YOUR FILE: FOR'YOUR INFO: AS WE DISCUSSED: FOR YOUR APPROVAL: RE'1ARKS: . REVIEW & COMMENT: COMMENT F, RETURN: FOR APPROPRIATE ACTION: Vo*' PUBLIC WORKS DEPARTIMENT BY: CITY OF EDIVIaNDS HARVE H. HARRISON MAYOR CIVI C CENTER - EDMONDS, . WASHINGTON 98020 - (206) 775-252 'E" FILE . STIR t: I D61)ARTM�NT OF PUBLIC WORKS January 8, 1979 Mr. Dean Hough Reid, Middleton & Associates 324 Main Street Edmonds, Washington 98020 Dear Dean: SUBJECT: DRAINAGE -PLAN FOR THE JOHN ECKER TRIPLEX 2b926 80TH ]PLACE WEST, EDMONDS The,sublect drainage plan is not approved. The Yrjanainen- Warren method of determining storage volume assumes the system is capable of discharging Q (allowable). This assumption has not been checked using the perc data for this project. A preliminary check indicates the assumption has not been met by the proposed trench. Please review your drainage plan and submit the needed additional calculations. If *ou should have any questions regarding this, please y contac * t Bob Franklin, Storm Water Management Engineer, 775-2525, extension 220. BF: j ak SWMEng� 'Dt Dt. Yours very truly, /qtRED F. HERZBERG, P.E. Ci City Engineer P.W_ Dir. Dt. I - gyREET -eye 7a r �5Vel� P57-5AP-1041 SYS7"Zl�f /V1AF 7 IfJ P15- X 0 r ,..)6J)AI ECRE'R 7e-e 1;7_5kl�V w I h cap m /�,7cc. C917 o Z_,F oF 6 C,:�A —/Z, r -*690- — 7Z:- 7-07A-L - -0759 PIC Rea, 7ftWer" .4"4em&a, lac, ENGINEERS SURVEYORS' PLANNERS 324 Main Street Edmonds, Washington 98020 1206,1 711�.3,134 December 19,,.1978 File No. 7159 Revised January 26., 1979 STORM DRAIN RETENTION CALCULATIONS FOR TRI-PLEX OF JOHN ECKER 1. Area 68.90(20)+93.90(67-50) 7716.3 0.177 ac. _0 437,56-0 3—, 5-6 103 0 - 100.0-= 2. S-lope = '�` 2.65% from NW corner to SE'corner 113.0 3. Site condition: Light grass to bare ground 4. Existing coefficient of runoff = CEX =-0.20 Using the Yrjanai-nen - Warren method to determine the retention volume necessary to -detain 100% of a 10 year frequency storm: Longest distance from headwaters to point of diskcarge = 113 feet Overland flow velocity 1.63 f-P.S. 2.65% @ site conditions noted above Chart 1 Time to concentration L/V(60) + 10 (113)/(1.63)6o + lo = 11.16 mi,h. Intensity ilo = 1.53 in/hr from Seattle curve for 10 year storm - Chart 10 Qallowable Qexisting = CexilOA = (0.20)(1,.53)(0-177)-0.054 c.f.s. Prorate future coefficient of runoff: Gravel (1235) 0.028 ac. @ 0.70 43,56o— � 0.020 ac. Roof & concrete 25,252 0.058 ac. @ 0.90 43,560 = 0.052 ac. 6 3. 2 (2 7 - 3 ) +5 2 6 nc. (,,, 0.85 Asphalt driveways 113,5W o.olo 0.03e, ac. .Planter area 0.177 - 0.128 0.049 ac. (,0 0.20 0.010 ac. 0.177 ac. 0.118 ac Cfut 0.667 0.177ac. Qall. 0.054 0.459 c.f.s./AC QO Cfut(A) _'(0.6670777 T -25 +Vj_7 -25 + /1762 36.97 min. VTO. 00 59) Qo Vs (282O)T 40QoT (2820)(36.97) - 40(o.459)(36-97) 1003.6 ft.3/ACfut T+25, (61-97) Vtotal Vs(A)Cfut = (1003�)(O-177)(0.667) = 119 ft.3 KIL)NICIPAL ENGINEERI NG 0 WAIER SUPPLY e WASTE TRrATKIENT SIJPVI:�'� r- (At)A'�'TPAI i t,, t i j r t' P, i ri c. A I k P6 R I' V1 A N N I N C. 1, 1 1 ", I c, N 0 N I A 1, 1 N A ", o 1'(_) R I �', I H 1) 11', 1 K I A 1 1) 1 \/I I () I'N I I H 1 0 1 1 A 1� I I; I I I I I I 1 1, 1 1 December 19, 1978 File No. 7159 Revised January 26, 1979 Page 21 STORM DRAIN RETENTION CALCULATIONS FOR TRI-PLEX OF JOHN ECKER (cont) I Size the retention system: ___jl � Vol. provided by surface ponding I _9 ft.3 d _�8 x-0.5'deep at one end only (see diagram belbw) 0, Use at least a 20-fi�t wide pon x H Vo 1., 3 ( AA + [�AAB + AB) f t, . 3 68 ( 5+ 5(1.8)+1 . 8 2 2 2 f t . 3 '> re a u i r e, d ' 'o' . kk do r i f = ��) head = max water surface less invert 3�.054 c.f.s. ft, ;� h Qex = 0 elevation F_4_F.0_54_)______' x 12 = 1.38 in. = 452-59 - 451-53 = i.o6 1( 0 - 6 3 ) � Use, 1-3/8 in. orifice (restrict the 4" P.V.C. to 1-3/8" diameter using a metal'plate) See cross-section on drawing. Assumptions: I.'. The south three stalls will be ponded 0.5 ft. deep(only over the catch basin), as shown on drawing for approximately 60 min. It will average 3" deep for 3P min. covering only half of these stalls. 2., '- Any flow over a 10 year storm will overflow out the driveway and south to the existing catch baslin. /6) 30'=' 7 37 Z;_1 Ce, (OT6 -6), - - Al 11,14y, 0- L) W-e— K a n -ZS- --7 3 VT-� 44 A Ae- -Tr V-S ivN Ma 9: IN I IL Li w> Lj-- CDj �Dl, L �--�]X, - L,t,�4�4 ! ..-- j LI D LI 1� 2 0 8 T H PL. SW, E' a. 0 gX45 7 OD C j CID[ (L 0 OD E; 11-�, ( -.- -7 b-It F-� r-� 0 0 0 0 Ct Ct m 0 04 w Y/fq ar w RJ 428 431 212TH ST. S 6770 MJ STREET HLE A I havV.-, ;Zea, ?ffZdd**M & 4dJ0a4&4, '796, ENGINEERS SURVEYORS PLANNERS 324 Main Street * Edmonds, Washington 98020 a Telephone (206) 775-3434 RECIEWE0 December 27, 1978 0 K I File No. 7159 0- 2 " 1978' Dir. -Of Public.Works Mr. Bob Franklin City of Edmonds Engineering Dept. Civic Center Edmonds, Washington 98020 Re: Storm Water Ret/Det System for John Ecker Property, Lot 7, Lumar Addition Dear Mr. Frankl in: The following are the soils logs and percolation data for the proposed tri-plex on the above mentioned property: Soils Log taken December 26, 1978 011- 4" Very gravelly sandy loam 4"-2411 Dark brown gravelly sandy loam 2411-4011 Gravelly loam mixed with silt & clay, moist and mottled No. -water table encountered Percolation Data 0"-24" depth 10 min/in 24"-40" 35 min/in+ The attached plan gives the approximate location of test hole. Tf you have any questions please contact our offi'ce. Very truly yours, REID.- MIDDLETON & ASSOCIATES, INC. A Enclosure ARM/ejj MUNICIPAL ENGINEERING o WATER SUPPLY o WASTE TREATMENT o SURVEYS & CADASTRAL ENGINEERING AIRPORT PLANNING & DESIGN o MARINAS 9 PORT & INDUSTRIAL DEVELOPMENT 0 FEASIBILITY STUDIES I j u I LAIVE V/ 11-25- ZOAC. P4,11EMENT 5CREW CAP 131gThIM. OR)FICE— ,6TRUDED, ORB' RE5T)?1C;r0R.DETA1L NOT TO SCALE '15TING CURB 9 GUTTER 1.7_1.�o '�` 71_F-4PYC-Sr1140 W1 ..Cdl7 AL. SCREEN WSW. te 452,09 a BOTH EA05 te. 461. 63 - BENCHIORK 5, E. C08NE R - -152. 0 46A56D ON CaRB INXERT ON �5-9=7- 9910. 1387) DATUA M.L.L.W. GENEM L 'NOTES 1. ELE44TIONS SOWN IqRE ELEYA TIONS IN P198,CNr1W5,C5 ARE 101W054C.D C PXYING. .2. �]/ R001-- DRAINS To &C CONAIEC TED TOAC 104RM6 ZOT o INDICXTES IPON PIN FOUND CITY OF EDMO ENGINEERING DEP Examined by D te CITIV OF ZDXWD5 STORM RETENTION PLAN V, FOR V 6 4� I L 'JOHN ECK r kk TRIPI EX ()F LR -ADDITION LOT 7, LUMAR CITY OF ED MOA10S, WA. S -7 R aEET FILE Rea, W4U&ao ENGINEERS SURVEYORS PLANNERS 324 MAIN STREET, EDMONDS, WASHINGTON D . RAWN CHECKED DATE FIELD BOOK SCALE FILE NO-7159 9ED 5,URFACE' S;r0R,9Gf A Dhlg R R 5 12-11-78 — /I/ = . 8 SHEE . T ) OF / , , I � kc) 80 PL iv z (9/w t 11yr #2 12-14- V1 11-25- Qb c Z"Ac. A4 11EM E N T) 6f15T1VYG C1JR0 9 GUTM? F 5CREW CAP "TICE 131g"DIM. OR) sy 7 L F- 4'PY&Sa. 40 W1 17 At. SCAEEN MESN - te 452, ago7H END,5 ie. 46,1. RESTRICORDETAIL- NOT TO SCALE BENCHMARK 5. E. CORIVER - �152. 0 rgAS,67D ON CLIRB INXER T ON 0 -gUIL 7- 09167. Z 38 7) OATUA M.L.L.W. GEINIML NOTES' I. ELEY,477OAfs :5kloWN ARE 14pppoglg�T ELEYAT108,5 IN P118,ENrA1f-S,6s' 1JRE PgoPo5zc-D ' C PA)IING. .2. All R001- DRAINS To 5C CONAIECTED TO A-CIPARfflNG Zor '-5 IMN PIN FOUND 3 o 111D1cX7Z 01 STORM RETENTION PLAN FOR TRIPLEX OF JOHN ECKER LOT 7, LUMAR-ADDITION 8, T Mi-Etf f- I L 9F. D MOADS WA Reaf Wea"oe .4ddadarej., lac.. ENGINEERS - - SURVEYORS 0 PLANNERS 324 MAIN s�rREET, EDMONDS, WASHINGTON DRAWN CHECKED DATE FIELD BOOK SCALE FILE NO. 44. 14 V 12 -1Y -78 OF I � 80 Ed Pt. w pp LINE C11) Qb 'CLI ,EXTRUDED, RR e"AC. PW VEM E NTj 5fl5TING CURB 9 GU rTEl? 5CREW Chp 131g"D1,1M. OR) 7 L F- 4';PYC-SC11 40 W1 17 —Al. SCflEEN WS# te 452,09 La BoThf, EAtDs z e. 46-1-63 RESTRICTOR -DETAIL NOT. TO SCALE 5. E. CORIAN91 R - �52 o OxsgD oN C41R13 INPERT ON 1�5-9=7' 09/6. 1387) DATum'. A LL W. GENERAL NoTEs. CELEV1471015­5--kJOWN lqRE114PRpollIvATC.� ELEYATIONS 1NP198fNrA&'S,65' 141?,E 101W05,CD h, C RAYING. 2. A I / RO OF DRAINS 7-0 BC CONNEC TED TO A -C IP4RKING Z 0 T J cr MIDICMfS I&N P11V FOUND. STORM RETENTION PL"AM FOR AER ECvr LEX t)F JOHN TRIP LOT 7, LUMAR -ADDITION CI TY OF ED.ffh99T'HLE I ) A I I- P� f- 1� A A I- 80 Ed PL. W p ,6TRUDED, C R'S 5X15T11YG C11R.8 Z"A. C. R4 MEM E N Ll GUTTER 5CI?EW CAP 1-410 TIM. ORIFICE- - 7 L F- 4PYC-sc#- 40 W1 C817 AL. SCAMN WSW te 45z.09 a BOTH ENDS i e. 467. 63 RESTRICTORDETAIL NOT TO SCALE O'BENCH14ARK 5. E. CORIVER - -152. 0 OX59D ON CURB �NXERT ON �5-9UJLT 0910- 1387) ,PATUA M.L.L.W. GENE&qL -NOTES. EL-EY,471-W SOWN IqRE IMPRoggATE. ELEYATIONS IN P191?fNrX_rs,6s- 11RE 101?,oP054c_D h. C PAYING. 2. All ROOF DRAINS TO BCC01VAIECTO TO &FMING ZOT 3 MIDICA72fS JAM P11V FOUND, APPRDffD DA TE C17 OF fDN01YD5 STORM RETENTION PLAN FOR 1p L TRIPLEX OF JOHN EC"R LOT L UIVA R A DDI TION OF EDMOA105, WA. ClIXMEET FILE SY 4- NA &Z S 4 IE�XvrsrlN�r : 80 H" F-7, STREET. FILE 01 0 4 &A 1z P�ktllr% C-4-111 to WMF­ , JZ(J5RZP_- im�W.AMOM �T*�327' I- -M, J�A VT 7 10 6,,t� YT LL T� TW& :4ENIERAL C NOSITRUCtION 'ITOT11112 did gionso&n d' ng. with the.-� "lion work. .2. Cooply with al! applicAble'60'deli and orilinan es Secure and pay f or all necessary potmi t a 3. are!�to cetle'rlines'of col a d i ter. ior walls 'and Dimensions shown on the drawings um n an n to outside f I ace of concrete and ntudsi1U-nl6s,s.�oth0r`s-1iOe, noted.. �4. r n loads: Floors..; ... f Roof ...... #..25 psf Wind..'. 5. Concrete: Ir Allack mix, 7/811 hard, dutable ag,&rq9AteP,* � C,,� . 1 6. I - .1 Reinforcing steelt fe.201000'psi; 4ap bars 30 difimoters-. 7. 11 (P�41500 Psi); hewas Framing lumber;-- Beams,- rOulas Fir 110 Joists and rs: D6ugla�, -Fir, kNo. 2 or better (I"ba 1250' ps, i) s plates' and bra6ihg,:, S, t u d rade touglas Fir. 8. Iic,,nse rues Scissors trusses for,ihe roof are' to be pro-falbrib&ted by a. c d, -t turer who is approved'by -the. local bu i Id ing 4uthority. 9. I ports and:, -under Walla runnibt'o. - Install solid blocking at, a I joists over.sul, opposite direction to joist span; 1-ouble Joists under partit iond running_par;� a k PLA4r-, Z N vf b J 0 (