21008 76TH AVE W)IOOB 'Up4h /4jg cA j R &THood and Duct Services, Inc. 6100 12th Ave. S. Phone (206) 726-0940 Seattle,WA 98108 Fax (206) 767-2607 Occupancy Name: . I U- - i U 4-'— L Occupancy Address: -7 1 po V -XJ Responsible Person: S (,�D Building Owner: COMPLETE Certification Given: REDE] YELLOWD WHITEZI FIRE PROTECTION CONFIDENCE TESTING RANGEHOOD High Pressure Hood Cleaning SYSTEM TEST REPORT Fire Suppression Installation & Service CONFIDENCE TEST21 REPAIRSE] Fire Extinguisher Sales & Service Range Hood and Fan Service & Repair Filter Sales & Service DATE: V12- 614 L7) Ct M C>r\ C1 1A) City, State, Zip: Phone Numb Phone Number: Building Owner Address: — City, State, Zip: Testers Name (Please Print):— V\D-T�\-e Lk 2 SFD Certification Number: SCP- m-o-2 67C, System Alarm? Yes No El Central Zation monitoring? Yes [Z No E] Monitoring company name: Control Pan, fedurer: - - Model Numberf Location of Alarm Panel: rf-t Plu"A Extinguishing System Manufacturer Location / Height of Range hood: 300 System? Yes 21 No F 0 U.L. 3 0 Compliant? Yes Z No C] Chemical Type: Wet [Z Dry Is pressure gauge indicator in operable rang�—? Y64804No 0 Is there chemical inside of the cylinder? Yes No Ej or Weigh CO2 or nitrogen cartridge. NA - No visible signs of a system fire or system tampering (if signs check no). Yes No Ej Check all piping and conduit. Are all piping and conduit immobilized with Yes No F-1 proper hangers and brackets? Are all protective covers present on nozzles? Yes [Z No El Are all nozzles checked in the proper position? Yes [Z No E] Does system have adequate volume and/or nozzle coverage? Yes Vj No [] Are all appliances inside of the hood protection area? Yes [7/j No E] Have fuse links been replaced? Yes [/-I No E] Was system operational from terminal link? Yes G6 No E] Was system operational from manual remote? Yes FZ No F-1 Was system and micro switch operational? NA F--1 Yes [7j No E] Is system visible and free from obstruction? Yes [j-6 No E] Is the inspection and service tag on the cylinder? Yesz Non 12 year hydro date of cylinder. Were hand portable extinguishers properly serviced? NAn Yes V) No Were all cooking surfaces protected? If not, give owner full Yes V No El information. Was operating procedure verbally given to restaurant personnel? Yes No Was UL 300 compliance explained to owner or manager? Yes No Gas shuts down upon system activation? NA Yes No Electric power shuts down upon system activation? NAEJ Yes Z No El Range hood tied to building alarm panel? NAE1 Yes Z No F] Range hood activation signal received at building alarm panel? NAEJ YesZ No Ej Class K extinguisher present? Yes [Z No E] Grease build i group: Lig —7—M Medium— Heavy, recommend cleaning Date of last cleaning Are cleaning intervals within NFPA standards? Yes F0 Previous Confidence Test Company & Technician —S-04--eu-so - — — 7 Ulf - - I-T- 1 —7 11 1 —Cld C) ZL L T + L I 21 re "Z'3 - '5 PQ K E- W I I-F; 0 0 li-�, r- ov -1 c-k I-:, n "T Y C 0 A4, r"-V Customer*r��IIC Corrections Made: Date Corrected: Corrected By: SFD Certification Number: This certifies that this fire and life safety system has been pro�erly inspected for reliability to cover the items listed in this report and is consistent with Seattle Fire Department Fire Code standards. Discreparic ave Jaw r i� the building Owner/Responsible Person for corrective action. Signature of Tester: ==A A , 0 1 -A )e4l� Phone # (206) 726-0940 Testing Agency: ___R&T Hood and DQct Services. Inc. MailingAddress: 610012thAve.S..Seaftle,WA98108 The owner is to perform and keep a written record of the following "quick check" fire system inspection to verify the following: 1. The extinguishing system is in its proper location. The extinguishing cylinder is in 6. The nozzle disc caps and their seals are intact, undamaged and tight. place and has not been removed or tampered with. 7. The inspection tag or certificate is in place and current. 2. The manual pull stations are unobstructed and in clear view and are labeled for 8. If any deficiencies are found, appropriate corrective action shall be taken immediately. intended use. 9. A record of the monthly inspections is to be kept reflecting the date inspected, inititals of 3. Insure that all tamper seals are intact and that system is in a ready condition. person performing the inspection and any corrections required. 4. Observe system, checking that no obvious physical damage or condition exists that might prevent operation. AUTHORIZED %,A, 5. The pressure gauge reading on the cylinder shall be in the green operable range. SIGNATURE FIRE DEPARTMENT COPY Kevin Zweber From: Martin Solorio [MartinS@exxelpacific.com] Sent: Tuesday, January 26, 2016 9:44 AM To: patdck.lawler@edmondswa.gov; Bjorback, Leif (Leif. Bjorback@edmondswa.gov); Kevin Zweber; John J. Westfall Subject: FW: Prestige Care Edmonds Med Gas Room Exhaust See below. NUN I A CENERAL CONTRACTORS Martin Solorio Superintendent Presfige Care Edmonds 21008 76�h Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com This email is to close the circle on the medical gas room ventilation requirements. The Washington State Department of Health requires the medical gas room to be designed and ventilated per the 1999 NFPA 99. In this version of NFPA 99, the medical gas room shall be vented either naturally or mechanically. Since we are not on an outside wall, the requirement is mechanical ventilation at I CFM/sq-iare foot. It is understood that newer Ix,ersions of NFPA 99 have different requirements but not per the code DOH uses. Thank you, Randy Hinton, P.E. R I C E Group, Inc. Mechanical Consulting Engineers p. 425.774.3829 x-213 f. 425-672.2084 20201 Cedar Valley Road, Suite 120 Lynnwood, WA 98036 www.rice-group.com 10/23/2015 8:00 am Event History Report Page I of 1 CS# U687020907 Dates 10/20/2015 00:00 to 10/2012015 23:59 Corp Account# All On Test? Y Site# All Event Class All Reporting Group All Open/Close? N Affiliation All In Service? Y Date Zone Operator Event Description ornment Additional Info User Com ent CS# U687020907 Site Name PRESTIGE CARE Add(ess 2:1008:76TH AVE W EDMONDS, WA 98026-7 Alt# 10/20/2015 10:47:46 AHW ONTEST OA-Place on Test �at: 1 jeremy King, gg cs# Expires: 10/20/2015 15:30:00 All C ��2 Zones 10/2012015 10:52:53 1 E320 CIE320 TR-SNDR/RELAY TRBL 10/20/2015 10:55:10 1 E320 CIR320 RE-SNDR/RELAY TRBL 10120/2015 11:00:08 1 E320 CIE320 TR-SNDRIRELAY TRBL 10/20/2015 11:02:21 1 E320 CIR320 RE-SNDR/RELAY TRBL 10/20/2015 12:02:31 1 E320 CIE320 TR-SNDR/RELAY TRBL 10/20/2015 12:04:28 1 E320 CIR320 RE-SNDR/RELAY TRBL 10/20/2015 12:13:00 14 54 FA -FIRE -SMOKE DET EAST HALL DINNING R, 10/20/2015 12:14:43 14 54 FA -FIRE -SMOKE DET EAST HALL DINNING R 10/20/2015 12:17:33 14 2000 RE -RESTORE EAST HALL DINNING R� 10/20/2015 12:17:37 14 2000 RE -RESTORE EAST HALL DINNING R- 10/20/2015 12:17:42 O/C CIE401 OP -OPEN (LOG-LSL) CONTROL 10/20/2015 13:10:48 11 3709 TR-TRBL ON ZONE DUCT DETECTORS SU 10/20/2015 13:14:58 11 3709 TR-TRBL ON ZONE DUCT DETECTORS SU 10/20/2015 13:16:10 11 2000 RE -RESTORE DUCT DETECTORS SU 10/20/2015 15:09:57 E603 CIE603 IN-RF TRANSMIT TEST zone: 0 CS# U687020907 I'll NO (S zoo" wkx Page 1 of 1 1113/2015 11:13 am 7(6A-J-- 1�7Z:?p Event History Report Page I of 2 CS# First to Last Dates 10/2912015 00:00 to 10/29/2015 23:59 Corp Account# All On Test? Y Site# 46717324 Event Class All Reporting Group All Open/Close? N Affiliation All In Service? Y Date Zone Operator Event Description Zone Comment Additional Info User Comment CS# U687020907 Site Name PRESTIGE CARE Address 21008 76TH AVE W EDMONDS, WA 98026-7105 A1lt# 10/29/2015 12:37:21 pm IWA ONTEST OA-Place on Test Cat: 1 sean olson with fire prot inc had cs # Expires: 10/29/2015 18:00:00 All Zones 10/29/2015 12:40:23 pm 0 ­01 US -UNDEFINED SIGNAL 10/29/2015 12:41:08 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 12:41:10 pm 0 2000 RE -RESTORE 10129/2015 12:41:14 pm O/C 96 OP -OPEN (LOG-LSL) RESET USER1 10129/2015 12:44:47 pm 9 3123 SU-FIRE SUPERVISORY KITCHEN HOOD 10/29/2015 12:49:43 pm 9 2000 RE -RESTORE KITCHEN HOOD 10/29/2015 12:49:46 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 12:51:09 pm 9 3123 SU-FIRE SUPERVISORY KITCHEN HOOD 10/29/2015 12:57:05 pm 9 2000 RE -RESTORE KITCHEN HOOD 10/29/2015 12:57:09 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 12:57:45 pm 2E320 CIE320 TR-SNDR/RELAY TRIBIL 10/29/2015 1:03:56 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 1:03:58 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 105:45 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 109:13 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 109:17 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10129/2015 109:19 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 1.10:14 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 1-10:18 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/2912015 1 10:20 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 1 10:50 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 1.10:52 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 1:12:49 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 1:13:25 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 1:13:56 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 1:13:58 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 1:39:09 pm 10 45 FA-FIRE-MANUAIL PULL RCU PULL STATION 10/29/2015 1:43:37 pm 10 2000 RE -RESTORE RCU PULL STATION 10/29/2015 1:43:41 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 1:44:05 pm 2 45 FA-FIRE-MANUAIL PULL FACP PULL STATION 10/29/2015 1:52:42 prn 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 1:52:46 prn O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 1:53:22 prn E412 CIE412 IN -PANEL DILL SUCCESEE 10/29/2015 1:53:24 prn E305 CIE305 RE -SYSTEM RESET 10/29/2015 1:54:00 prn OQ250 CIE320 TR-SNDR/RELAY TRBL 10/29/2015 1:54:36 pm OQ250 CIR320 RE-SNDR/RELAY TRBL 10/29/2015 1:55:02 prn 2E320 CIE320 TR-SNDR/RELAY TRBL 10/29/2015 2:30:27 pm 10 45 FA -FIRE -MANUAL PULL RCU PULL STATION CS# U687020907 Page I of 2 11/312015 11:13 am Event History Report CS# First to Last Dates 10/29/2015 00:00 to 10/29/2015 23:59 Corp Account# All Site# 46717324 Event Class All Reporting Group All Open/Close? N Affiliation All Date Zone Operator Event Description Zone Comment Additional Info User Comment CS# U687020907 Site Name PRESTIGE CARE Address 2100876THAVEW EDMONDS,WA 98026-7105 10/29/2015 2:35:56 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 2:36:53 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 2:36:55 pm 10 2000 RE -RESTORE RCU PULL STATION 10/29/2015 2:36:57 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 2:40:21 pm 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 2:40:23 pm 10 2000 RE -RESTORE RCU PULL STATION 10/29/2015 2:40:27 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/29/2015 2:40:56 pm 2 45 FA -FIRE -MANUAL PULL FACP PULL STATION 10/29/2015 2:42:32 prn 2 2000 RE -RESTORE FACP PULL STATION 10/29/2015 2:42:36 pm O/C 96 OP -OPEN (LOG-LSL) RESET CONTROL 10/1 9/2015 3:08:51 pm E603 CIE603 IN-RF TRANSMIT TEST zone: 0 10/29/2015 3:24:52 pm 2E320 CIR320 RE-SNDR/RELAY TRBL 10/29/2015,3:33:10 pm 11 3709 TR-TRBL ON ZONE DUCT DETECTORS SU 10/29/2015 133:12 pm 11 2000 RE -RESTORE DUCT DETECTORS SU CS# U6870204'07 On Test? Y In Service? Y Alt# Page 2 of 2 Page 2 of 2 — John J. Wesffall From: John J. Westfall Sent: Friday, October 16, 2015 3:15 PM To: 'Martin Solorio' Cc: Karl Fitterer; Kevin Zweber; 'Lawler, Patrick' Subject: Prestige TCO for FIRE Martin: Temporary Certificate of Occupancy (TCO PENDING) items require Tuesday 10/20 a.m. inspection. DFIVI Karl Fitterer 425.754.4262 Some systems NOT APPROVED have been agreed you will not use during temporary and pushed for final building approval (CO) When will the glazing that makes up smoke barriers be installed for CORRIDOR office areas? BLD20071154 Fire Connection/sprinkler supply FINALED -DDCA not alarm supervised; secured at lid. BLD20151303 FA Communicator TCO PENDING BLD20141295 FA System TCO PENDING -Verify operation of automatic hold opens for fire doors (CORRIDOR doors, any others?) -install additional horn/strobe CORRIDOR near #405 because of ceiling reduced visibility. -Install notification Ws) in EAST STAIRWELL. -Install smoke/CO combos and notifications and TEST in DINING space. -Rernove all dust covers left on initiators. -FACP verified connected to generator. BLD20141320 Auto Sprinkler System TCO PENDING -Install heads in DINING space. -Trim head s/remove tape in CLEAN UTILITY (across 217), SNOHOMISH DEN (across 302), Bathroom #308. -Hydraulic placards for risers. -Sign "FDC" sign/graphic on east exterior column near FDC. -Sign "AUX DRAINS" (UTILITY rooms BASEMENT & KITCHEN) BLD20140659 Mech (Fire portions) -Medical gas NOT APPROVED FOR STORAGE/USE -Post zone signage for controls in hallways -TCO compressed oxidizer gas storage/use limited to non -permitted quantity of 502 ft3 (2x5' cylinders) -Typelhood NOT APPROVED FOR OPERATION -Verify fan during cooking operations. -Damper tests (for FD1, BLDG approval separate) APPROVED -Generator TCO PENDING -Post "GENSET DISCONNECT" on switch panel near main entry. BLD20140465 Kitchen Suppression System NOT APPROVED FOR OPERATION -Acceptance test: -Verify shunt trip operation of gas and electrical under hood. -Verify automatic operation from fusible link -Verify manual operation from pull -Verify location of Class K extinguisher. -Verify operation of hood system activates the building fire alarm. BLD20140457 Skilled Nursing Building -Elevator NOT APPROVED FOR USE -Verify operation of elevator recall and fire protection. -Delayed egress doors: NOT APPROVED FOR USE -Illumination & keypad control. -Alarm/power/manual switch control deactivation. -EXIT signs/emergency pathway TCO PENDING -final item: repair or replace EXIT sign from PT room. -Knox Boxes: TCO PENDING -Provide permanent keys and key cards if necessary. -Fire Rated Assemblies: TCO PENDING -Verify FR labeling/closures where required. -CORRIDOR Doors with gaskets, automatic closing, magnetic hold operation (FA). -Extinguishers: TCO APPROVED -Fire Lane markings TCO APPROVED John 3. Wesffall Deputy Chief/Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile KHOHOM"Vol co F I R E t" *aw_ DIST-ICT From: Karl Fitterer Sent: Friday, October 16, 2015 11:47 AM To: John J. Westfall Subject: FW: TCO Sent from my Windows Phone TE- TiNG AID C. SERVICES PROJECT NO: 15-197 DATE: 10/14/2015 TECHNICIAN: CARLOS LUNA PRESTIGE.CARE, INC. � 21008.76TH AVENUE WEST EDMONDS, WA 98026 FIRE SMOKE DAMPER VERIFICATION REPORT ARCHITECT: CARLETTI ARCHITECTS P.S. 116 EAST FIR STREET, SUITE A - MOUNT VERNON, WA 98273 MECHANICAL ENGINEER: RICE GROUPr INC. 20201 CEDAR VALLEY ROAD, SUITE 120 - LYNNWOOD, WA 98036 MECHANICAL CONTRACTOR: SMITH MECHANICAL, INC. 6146 PORTAL WAY - FERNDALE, WA 98248 *--' )ep AIMIRL AADC TAC SERVICES, LLC 4811 DESMOND STREET BELLINGHAM, WA 98229 PH: (360) 224-8555 FAX: (360) 464-9973 ADMIN@TES-rANDC(.COM 10/14/2015 Page 1 of 7 Aidal, FIRE SMOKE DAMPER VERIFICATION TEST FORM AANC TE HO A a Cm SERVICES PRESTIGE CARE NURSING HOME EDMONDS, WA IS-197 CARLOS LUNA ACCESS FSD I.D. FSD-1 LOCATION HALLWAY AREA SEPERATED HALLWAY DOOR (Y/N) NO TECH INITIALS C.L. WITNESS INITIALS C.E. DATE 10/14/2015 COMMENTS FSD-2 HALLWAY HALLWAY NO C.L: C.E. 10/14/2015 FSD-3 HALLWAY HALLWAY NO C.L. C.E. 10/14/2015 FSD-4 HALLWAY HALLWAY NO C.L. C.E. 10/14/2015 FSD-5 HALLWAY 102 NO C.L. C.E. 10/14/2015 FSD-6 NURSE STATION 134 NO C.L. C.E. 10/14/2015 FSD-7 HALLWAY 141 NO C.L. C.E. 10/14/2015 FSD-8 210 209 NO C.L. C.E. 10/14/2015 FSD-9 HALLWAY 219 NO C.L. C.E. 10/14/2015 FSD-10 HALLWAY 220 NO C.L. C.E. 10/14/2015 FSD-11 HALLWAY 220 RR NO C.L. C.E. 10/14/2015 FSD-12 HALLWAY ROOF NO C.L. C.E. 10/14/2015 FSD-13 HALLWAY HALLWAY NO C.L. C.E. 10/14/2015 FSD-14 HALLWAY MEDS NO C.L. C.E. 10/14/2015 FSD-15 HALLWAY 309 NO C.L. C.E. 10/14/2015 FSD-16 HALLWAY 313 NO C.L. C.E. 10/14/2015 FSD-17 HALLWAY 317 NO C.L. C.E. 10/14/2015 FSD-18 CLEAN UTILITY 311 YES C.L. C.E. 10/14/2015 FSD-19 CLEAN UTILITY 312 NO C.L. C.E. 10/14/2015 FSD-20 SOILED UTILITY 310 NO C.L. C.E. 10/14/2015 FSD-21 HALLWAY 405 NO C.L. C.E. 10/14/2015 FSD-22 HALLWAY 501 NO C.L. C.E. 10/14/2015 FSD-23 HALLWAY 502 NO C.L. C.E. 10/14/2015 FSD-24 HALLWAY 409 NO C.L. C.E. 10/14/2015 FSD-25 CAFt CAFt NO C.L. C.E. 10/14/2015 FSD-26 CAFt ACTIVITY OFFICE NO C.L. C.E. 10/14/2015 FSD-27 CAFt MULTI PURPOSE NO C.L. C.E. 10/14/2015 FSD-28 ACTIVITY DESK PHYSICAL THERAPY NO C.L. C.E. 10/14/2015 FSD-29 RECEPTION RESTROOM NO C.L. C.E. 10/14/2015 FSD-30 MARKETING ROOF NO C.L. C.E. 10/14/2015 FSD-31 MARKETING ROOF NO C.L. C.E. 10/14/2015 FSD-32 HALLWAY MANAGER NO C.L. C.E. 10/14/2015 FSD-33 MANAGER HALLWAY NO C.L. C.E. 10/14/2015 FSD-34 STORAGE VACUUM NO C.L. C.E. 10/14/2015 FSD-35 HALLWAY CIRCULATION HALL NO C.L. C.E. 10/14/2015 FORM ID: FSD VERIFICATION FORM , m- OS LUNA (SIGNATURE ON FILE) / 10/14/2015 i CA-SE-Y EWALD (SIGNATURE ON FILE) / 10/14/2016 10/14/2015 Page 2 of 7 C) (D 0 I�j —I C) (-n I n Qs 'Z� K.3 MENEM] WE Imms am go, BOOM hug r1W_W*-417%Wn_1- Ows vwr, .. .4 I 101 COMMA BASEMENT - HVAC a I V IV 0 Ark 420UM 116 EAST FEE STREET SATE A MOUNT VERNON. WA. 98M P� 0 42�� F_ 42�5725 -ow. A NEW DILLOW FM PRESICE CARE Wt 21005 76TH ME W EDMONDS. WA 9M CONTACT. PALL RASMUSSEN (5m) 53%-MB3 1--. A 05-09-2014 PERM[T SET -17-14 REV. I DOM COFaWCTJONS o&-o�m aTY NEv/w SET SHEET DTLL. alrLolma"EM No . WhOw", MAY 9. 2014 m 3. 0 CD 0 rj CD Un (D-J 600-06---11 rk clllll� ;16 EASST -�- 3FREET Sul rE A MOOT 'ARWO. A, 98M Ph �!, 4 24 U� 24 6 :5 A NEW EFULA, FOR: - IC TIGE CW, 21001 16� I" EDWONDS, WI SaO26 "m""'T 'AM RA911.)�-4 (wq) 5z9-01. 5 ill�EE GROU; :�154 I'FM.T.LT% C5-09-2011 -;L[I T SE )T��REVMJ SET, ',Ht-FT 7-U Fill FLOOR KM A - HYAC RAND�U 901F *fir.-D;5� 11Y PAUL GOM acmyF.-- — "If 9. 201, M1.3 (D Ln 0 Pj -.1 �- t.n C3 ,4) 11) �3i) o r 'r '3P ��.7 — w � (w) Ark cwm 116 EAST lP. UREET WITE A PADIAT VM404, WA. 9B273 424- 94 '2,M5 11 3QLL 1� FO� "�SIKT C�E Ic 7IM3 76TH M.OlUl �-1126 C011ACT F.L R�� STITT 5!q , 1�; �EW;mi� ---- --- 115— 110. Pf W SET //I \W-17-11 rO 4 1 XH CLVKCn(k4E !I �� REV= TT INEET VRE FIM FLOCR KM B - NVAC RANDQ� K-rm ILI maw rr— PQJL OTO lAY 91V pw— M 3.2 CD Cl 0 � C:l 14 � Ul (D ------ --- - G)--- . FIRST FLOOR PLAN SW HVAC - Mp6m GONE mommlomi 166 CID FA Ark ch� m RL 116 DSI FIR MEEI 9117 ' M%Nr �MC�, .1 98213 Ph A W BULD -0, FOR. N�STIU. C� lc� 210O.'61H "A N EDUNCS. � I UNTACI: PAUL RASIAUz, i (") 5.n-o'E, RlcE,3Roljp I 3-1� —T DOH COPRECTT�r _4 D� NEL/81[ISET �,ET MW R-A 60*10 M. �AY 9. 2014 m 3.3 14 + k' FS I F — - — - — - — - — - — - - — - — -- FS�27 I Aw m R& U6 US, M STREET %)'TE A WWT ATOM, 'A. 982M r �h— 47 -W94 L-17-1 tilt A NE. O',RLIXNG P'�ESTIGE WE 21008 16M �,:'Q w s =55 ENMUS. NA 'N12' Efoo CCWA(T PAUL �, USSIN Itm) b�q-wu v RlcE'aRo'jp.l—. ------ L ---------- L--J ------------ x J L 262 (2 -50 C3�) C3X9,DO @ F_1R7ST FL�OOR PIA,,N SE HVAC iEmsiNs. ��09-M14 KBUT SET Z47�1z--11-1 7 RANDA11 HINTON 14jiliA PAUL TfO 9AY q. MA M 3.4 %-11 pr7- SERVIMS PROJECT NO: 15-197 DATE: 10/14/2015 TECHNICIAN: CARLOS LUNA PRESTIGE CAREJNC. 1,2*lM-gk7i6lT—iH.rrA7V-Erq�tlE,aW,E&T EDMONDS, WA 98026 FIRE SMOKE DAMPER VERIFICATION REPORT ARCHITECT: CARLETTI ARCHITECTS P.S. 116 EAST FIR STREET, SUITE A - MOUNT VERNON, WA 98273 MECHANICAL ENGINEER: RICE GROUP, INC. 20201 CEDAR VALLEY ROAD, SUITE 120 - LYNNWOOD, WA 98036 MECHANICAL CONTRACTOR: SMITH MECHANICAL, INC. 6146 PORTAL WAY - FERNDALE, WA 98248 10/14/2015 Page I of 7 AANC TAC SERVICES, LLC 4811 DESMOND STREET BELLINGHAM, WA 98229 PH: (360) 224-8555 FAX: (360) 464-9973 ADMIN@TESTANDC(.COM 4A FC.wp-- Tt seav FIRE SMOKE DAMPER VERIFICATION TEST FORM AAfirC ACCESS FSD I.D. FSD-1 LOCATION AY AREA SEPERATED HALLWAY WAY4 DOOR (Y/N) NO No TECH INITIALS C.L. WITNESS INITIALS C.E. DATE 10/14/2015 COMMENTS FSD-2 HALLWAY WAY HALLWAY NO No C.L. C.E. 10/14/201S FSD-3 HALLWAY LWAY HALLWAY No NO C.L. C.E. 10/14/2015 FSD-4 HALLWAY HALLWAY LW Y AtLA NO NO C.L. C.E. 10/14/2015 FSD-5 HALLWAY 102 NOE C.L. C.E. 10/14/2015 FSD-6 NURSE STATION 134 NO C.L. C.E. 10/14/2015 FSD-7 HALLWAY 141 NO C.L. C.E. 10/14/2015 FSD-8 210 209 NO C.L._ C.E. 10/14/201S FSD-9 HALLWAY 219 NO C.L. C.E.. 10/14/2015 FSD-10 HALLWAY 220 NO C.L. C.E. 10/14/2015 FSD-11 HALLWAY 220 RR NO C.L. C.E. 10/14/2015 FSD-12 HALLWAY ROOF NO C.L. C.E. 10/14/2015 FSD-13 HALLWAY HALLWAY NO C.L._ C.E, 10/14/2015 FSD-14 HALLWAY MEDS NO C.L. C.E. 10/14/2015 FSD-15 HALLWAY 309 NO C.L. C.E. 10/14/2015 FSD-16 HALLWAY 313 NO C.L C.E. 10/14/2015 FSD-17 HALLWAY 317 NO C.L. C.E. 10/14/2015 FSD-18 CLEAN UTILITY 311 YES C.L. C.E. 10/14/2015 FSD-19 CLEAN UTILITY 312 NO C.L. C.E. 10/14/2015 FSD-20 SOILED UTILITY 310 NO ---C.L. C.E. 10/14/2015 FSD-21 HALLWAY 405 NO C.L. C.E. 10/14/2015 FSD-22 HALLWAY 501 NO C.L. C.E. 10/14/201S FSD-23 HALLWAY 502 NO C.L. C.E. 10/14/2015 FSD-24 HALLWAY 409 —�Ft NO C. L C.E. 10/14/2015 FSD-25 CAFt NO C.L. C.E. 10/14/2015 FSD-26 CAFt ACTIVITY OFFICE NO C.L. C.E. 10/14/2015 FSD-27 CAFt MULTIPURPOSE NO C.L. C -. E-. 10/14/2015 FSD-28 ACTIVITY DESK PHYSICAL THERAPY NO C.L. C.E.. 10/14/201S FSD-29 RECEPTION RESTROOM NO C.L. C.E. 10/14/2015 FSD-30 MARKETING ROOF NO C.L. C.E. 10/14/2015 FSD-31 MARKETING ROOF NO C.L. C.E. 10/'14/2015 FSD-32 HALLWAY MANAGER NO C.L. C.E. 10/14/2015 FSD-33 MANAGER HALLWAY NO C.L. C.E. 10/14/2015 FSD-34 STORAGE VACUUM NO C.L. C.E. 10/14/2015 T FSD-35 HALLWAY CIRCULATION HALL NO C.L. C.E. 10/14/2015 1 FORM ID: FSD VERIFICATION FORM EWCARLOS LUNA (SIGNATURE ON FILE) / 10/14/201S CASEY EWALD (SIGNATURE ON FILE) / 10/14/2016 10/14/2015 Page 2 of 7 O'M .N .6 9 Un LIM LT. OPP/A3V AW 01-M-ID �14 90IMM HOO I VV Wil-W , \l/ Is Lotod we-" nw-MW4 x1mrms" Iowa 4XIM '26 3W* MaMW wl mom " v Mir, tal fj cm a VNM MOM v lum L3W 8, twoll 0 � A A-3 - Aft � MMM%M" A. .8 . .0 DYM — IM3"3SVO Ln ,Q C) � C-4 0 Mt *. ". avWN". 3VM - 6 WU WDU Tnu IR-6 iz� CW,,m L& I-S)d IICZ-M� -WdrlOUD I'lld flw-a� fv') Mr�b NWd :0".." III VIAL matt V% �m lxsbd �01 --4C" 0�3. V -*a_ MKI "44 V9146 1. 'WI.& I'mm , I'M i33ws w IS,) 9.� In 0 - it . � m � . �.' - At, - Ln .4 r� 0 Ln Q) En (0 0- M cu U3 CD M ��a% 0 r-j � CD 141-- Un 14—Im (D-- FUM R PLAN 0 e Ir r 14 Q� m RL 115 CAW m slilm WIT A "NI vvrm .4 IaM P- tw Q 12- Fw- PmPar cw or MCA 76 �*. . ED-DNM -I WIS C0414cl, pgk FkVium (WP) W-0155 MC.E GROUP. i�z FEW a, RE, , W, Q., qDAQ sn sill rItLL FOP FLOM PLM C - MAC cow PAUL M ri. M 3j IC., �1(1,,,b 7M - 0 WId MM LSW -'ita Um 81 c 135 OU;A;b LE AJIMBd lWI-CO-W V-rA%3j — — - — - — - — - — - — -- — --- COW TS Iw;) KFSM�h Vr'd -I_ �Ilw 9=6, loom . �ky.dv MOL: Im r.�2 MILOW OMMM -I. cim '"OkElft vvh ' II I MLS Oil ISY3 oil Td asumwuwwo i 444IF-i IT (D ------ -------- r ------------- G -------------- -+4- r Kevin ZweLe From: John J. Westfall Sent: Tuesday, October 13, 2015 10:43 AM To: Karl Fitterer Cc: Kevin Zweber Subject: FW: TCO for prestige Background on Prestige TCO... From: Martin Solorio [mailto:MartinS@exxelpacific.com] Sent: Tuesday, October 13, 2015 10:18 AM To: John 3. Westfall Cc: Kevin Zweber; '13jorback, Leif Subject: RE: TCO for prestige That's correct, delayed egress will not be working but doors will be fully operational. Yes we will have a 3 rd party inspector looking at those tomorrow. Thanks. EM PACERIC C. EN ER -AL WNTILACM RS Martin Solorio Superintendent Presfige Care Edmonds 21008 7e Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: John 1. Westfall [mailto:iwestfallftfiredistrictl.o[g1 Sent: Monday, October 12, 2015 6:55 PM To: Martin Solorio Cc: Kevin Zweber; '13jorback, Leif Subject: RE: TCO for prestige Alright. 1) 1 understand that for now, the medical gas or Dewar's storage will not be present. Is that correct? 2) Delayed egress features are not installed 3) Damper testing needs be completed for TCO. May I suggest 3 rd party testing given the urgency? John From: Martin Solorio [ma ilto: Marti nSCcbexxel pacific. com Sent: Monday, October 12, 2015 3:50 PM To: John J. Westfall Subject: FW: TCO for prestige Hi John, were you able to look into this? Thanks. EM PACIRC CEQU. CONTRY.-MRS Martin Solorio Superintendent Prestige Care Edmonds 21008 76"' Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: Martin Solorio Sent: Friday, October 09, 2015 8:24 AM To: 'John 1. Westfall'; Kevin Zweber Cc: Bjorback, Leif; TJ Mellema (Um@)exxelpacific.com) Subject: RE: TCO for prestige John, thank you for your response. That is correct, TCO is for furniture installation purposes only, there will be no staff, no cooking and it will be just about a week before we go for Co. All of the emergency exits will be working properly with all the signage installed but there will be no delayed egress engaged with the doors, they simply will open when pushing on the crash bars. The basement is finished but will not have elevator access, the 2 stairwells will be open, no staff will be operating the laundry room or using the staff lounge, the vertical separations are in place. At this point and for TCO purposes the Med gas room will be empty with no gas of any type stored or used in the building, this issue should be resolved one way or another by the time we obtain CO. Our intention is to have the fire alarm and fire sprinkler systems tested and inspected by your department on Thursday th th October 15 , followed by Building's department inspection for TCO on the 16 , with a re -test on Wednesday October 21't once the elevator gets final inspection and the delayed egress system installed and working; finalizing with the nd building department's final inspection for CO on October 22 Please let us know as soon as you can if this is acceptable and I will call the inspection request line to schedule the inspection. EM PACIRC CENRAL CONIILAC"MRS Martir-Solorio Sii peri*nte n d e nt Prestige r�,are Ed4onds 21008 76" Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: John 3. Westfall rma i Ito: jwestfa I I 0fired istrict 1. orql Sent: Thursday, October 08, 2015 5:45 PM To: Martin Solorio; Kevin Zweber Cc: Bjorback, Leif Subject: RE: TCO for prestige Martin: Is your TCO for purpose of installing FFE, or for staff/resident integration? You're only asking for a week under temporary? Typically, fire protection, detection), separations, exit/emergency lighting, hazard mitigations, fire access features (fire lane & Knoxbox) must be accepted for fire side of TCO sign off. If you're taking staff and residents we will ask for all of the patient care features such as FA voice evacuation notification and delayed egress when patients are present. When only staff, as long as the normal exiting is provided and horn/strobe notification. Are we cooking during this time? Need hood suppression connected to building and alarm. Leif shared that you may be working unfinished basement. How are the services (laundry, staff lounge, etc ... ) anticipated to be accommodated during TCO? How will the separations be maintained vertically? Lastly, please check the email from Kevin Scarlett @ DOH. The medical gas storage questions and solution must be in place with the hazard present, Cryogenic oxidizer storage vs. compressed gas storage appears to be the medical gas question to be answered in the immediate. The proposed Dewar's system appears to require additional protections in place. John J. Westfaill Deputy Chief/Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile A5111 &VOl'townsff I E 1, li&crl jultult T From: Martin Solorio [mai Ito: Marti nSOexxelpacific.com] Sent: Thursday, October 08, 2015 7:49 AM To: John 1. Westfall; Kevin Zweber Subject: TCO for prestige We are looking to get TCO on October 16 Ih for the Prestige Project and I have some questions regarding your rd inspections. We will go for final CO on October -23 Do we need to have final fire sprinkler and fire alarm inspections done for TCO? What are the other requirements for TCO? Our state elevator inspection will be done on October 21", does the elevator need to be operational for TCO? Ih The delayed egress system may not be operating before October 16 , is it required to be for TCO? Let me know when you get a chance. Thank you. C ENEIL-U. CONTU."WLS Martin Solorio Superintendent Presbge Care Edmonds 21008 76"' Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com Prestige Care Fire Final Checklist: 10/15/15 2 Fir larm rlif:y notification devices including external bell orstr Ze�?, ces door releases Elevator recal \Yrify sequence of operation for different alarm states — mode??? Vify address descriptors to be understandable Ivure FACP circuit has lock -on device on AC panel VU re FACP is connected to emergency power system Y (Vice Evacuation System lFC 907 :Delayed Egress i tem - mpers and Duct Detectors —special inspection Oxygen supply system Ref DOH emails etc. u tic Spr r a prinkler necessity for FDC ignage 'Is�� Lamper switches at FACP �j �Fau ic Fcalcs label on 9]' ..syste fy signage on system---%7 test system (notification seconds) Comrr(ercial Cooking Type I Hood $fi-'unt trip shuts off all electrical and gas under hood Activation from manual pull (located within 10-20 feet of Activation from fusible link Class K extinguisher within 30' of hood All activations of hood activate fire =S'Vsf�em t Lighting A qg6 ,Zfo c a 'n, distances, directional arrows \Jdttery backup or emergency power? � LIA s �_fZ41A_y W_ck- ko" 07 0 Emergenc ��ess Lights Adeq,Lpte lighting for egress oryor emergency power generator Knox Box Master keys FACP and pull station keys One complete set, two operational sets e La marking "fi<a �essr ss% th visibility on the 76 AveSide X/ I ZA W, 6, wal 11 Raw-, d 4"", In A '�'4 M .5VA S"'Okz'p , 5'pe� VU—Y Reply Reply All Forward FW: Delayed egress sign Bjorback, Leif [Leif.Bjorback@edmondswa.gov] To: Kevin Zweber Cc: Westfall, John Uohn.westfall@edmondswa.gov] Thursday, October 22, 201S 1:15 PM fyi From: Lawler, Patrick Sent: Thursday, October 22, 2015 1:12 PM To: 'Martin Solorio' Cc: Bjorback, Leif Subject: RE: Delayed egress sign I discussed the proposed sign location with Leif, building official. As far as the building code is concerned, we have no issues with locating the signs adjacent to the -affected doors. The Fire Marshall will have the last say on the matter though, so I would recommend waiting until Kevin has a chance to see the mock-up on Monday prior to permanent installation. I would also suggest that "Emergency Egress Only" signs be considered for those locations. From: Martin Solorio rmailto:MartinS(�)exxeli)acific.com Sent: Thursday, October 22, 2015 9:40 AM To: Zweber, Kevin (Fire District Address); Westfall, John (Fire District Address); Fitterer, Karl (Fire District Address); Lawler, Patrick; Bjorback, Leif Subject: CO We are going to go for CO on October 27th rather than tomorrow. Thank you. (i F-\'FXM. CONTRACrORS Martin Solorio Superintendent Prestige Care Edmonds 21008 761h Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com Kevin Zweber From: John J. Westfall Sent: Tuesday, October 13, 2015 10:39 AM To: 'Martin Solorio' Cc: Kevin Zweber;'Biorback, Leif Subject: RE: TCO for prestige Great. Bear with us, there is a lot of demand on our time at this juncture. John From: Martin Solorio [mailto:MartinS@exxelpacific.com] Sent: Tuesday, October 13, 2015 10:18 AM To: John 1. Westfall Cc: Kevin Zweber; 'Bjorback, Leif Subject: RE: TCO for prestige That's correct, delayed egress will not be working but doors will be fully operational. Yes we will have a 3 rd party inspector looking at those tomorrow. Thanks. EM PACIRC CFNERM. CONTRACTORS Martin Solorio Superintendent Presfige Care Edmonds 21008 76�h Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: John 3. Westfall [mailto:iwestfall@firedistrictl.orQ] Sent: Monday, October 12, 2015 6:55 PM To: Martin Solorio Cc: Kevin Zweber; '13jorback, Leif Subject: RE: TCO for prestige Alright. 1) 1 understand that for now, the medical gas or Dewar's storage will not be present. Is that correct? 2) Delayed egress features are not installed 3) Damper testing needs be completed for TCO. May I suggest 3 Id party testing given the urgency? John From: Martin Solorio [mailto:MartinSOexxelpacific.com] Sent: Monday, October 12, 2015 3:50 PIVI To: John 1. Westfall Subject: FW: TCO for prestige Hi John, were you able to look into this? Thanks. r7-7 #0 CENEU. CONTIMC17ORS Mailin Solorio Superintendent PresUge Care Edmonds 21008 76�' Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: Martin Solorio Sent: Friday, October 09, 2015 8:24 AM To: 'John 1. Westfall'; Kevin Zweber Cc: Bjorback, Leif; TJ Mellema (UmC@exxeloacific.com) Subject: RE: TCO for prestige John, thank you for your response. That is correct, TCO is for furniture installation purposes only, there will be no staff, no cooking and it will be just about a week before we go for Co. All of the emergency exits will be working properly with all the signage installed but there will be no delayed egress engaged with the doors, they simply will open when pushing on the crash bars. The basement is finished but will not have elevator access, the 2 stairwells will be open, no staff will be operating the laundry room or using the staff lounge, the vertical separations are in place. At this point and for TCO purposes the Med gas room will be empty with no gas of any type stored or used in the building, this issue should be resolved one way or another by the time we obtain CO. Our intention is to have the fire alarm and fire sprinkler systems tested and inspected by your department on Thursday th th October 15 , followed by Building's department inspection for TCO on the 16 , with a re -test on Wednesday October 21't once the elevator gets final inspection and the delayed egress system installed and working; finalizing with the d building department's final inspection for CO on October 22" Please let us know as soon as you can if this is acceptable and I will call the inspection request line to schedule the inspection. 77 �7-- 1 P, CE.-NMU. CONMACTORS Martin Solorio Superintendent Presfige Care Edmonds 2100876 1h Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com From: John 1. Westfall [mailto:jwestfall0firedistrictl.org] Sent: Thursday, October 08, 2015 5:45 PM To: Martin Solorio; Kevin Zweber Cc: Bjorback, Leif Subject: RE: TCO for prestige Martin: Is your TCO for purpose of installing FFE, or for staff/resident integration? You're only asking for a week under temporary? Typically, fire protection, detection), separations, exit/emergency lighting, hazard mitigations, fire access features (fire lane & Knoxbox) must be accepted for fire side of TCO sign off. If you're taking staff and residents we will ask for all of the patient care features such as FA voice evacuation notification and delayed egress when patients are present. When only staff, as long as the normal exiting is provided and horn/strobe notification. Are we cooking during this time? Need hood suppression connected to building and alarm. Leif shared that you may be working unfinished basement. How are the services (laundry, staff lounge, etc ... ) anticipated to be accommodated during TCO? How will the separations be maintained vertically? Lastly, please check the email from Kevin Scarlett @ DOH. The medical gas storage questions and solution must be in place with the hazard present, Cryogenic oxidizer storage vs. compressed gas storage appears to be the medical gas question to be answered in the immediate. The proposed Dewar's system appears to require additional protections in place. John J. Wesffall Deputy Chief/Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile . ANQ�l FINOROMIS11 Co. wit From: Martin Solorio [mai Ito: Marti nS@exxel pacific.com] Sent: Thursday, October 08, 2015 7:49 AM To: John 1. Westfall; Kevin Zweber Subject: TCO for prestige We are looking to get TCO on October 16 th for the Prestige Project and I have some questions regarding your rd inspections. We will go for final CO on October 23 Do we need to have final fire sprinkler and fire alarm inspections done for TCO? What are the other requirements for TCO? Our state elevator inspection will be done on October 21", does the elevator need to be operational for TCO? th The delayed egress system may not be operating before October 16 , is it required to be for TCO? Let me know when you get a chance. Thank you. EM PACK (;F-\'FJbkL CONTRACrURS Martin Solorio Superintendent Presfige Care Edmonds 21008 7e' Ave W Edmonds WA 98026 360 734 2872 Ext. 363 Cell: 360 815 0328 www.exxelpacific.com -4 John J. Wesffall I From: John J. Westfall Sent: Thursday, October 08, 2015 5:33 PM To: 'Scarleft, Kevin A (DOH)'; Randy Hinton; David Wilson Cc: Tj Mellema; Martin Solorio; Paul Rasmussen; Pete; Bjorback, Leif; Kevin Zweber Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 Kevin thanks for the conference with Leif today. A discussion I had last year with Paul Goto was regarding the "indirect" heated medical gas enclosure. IMC and NFPA 99 seemed at odds for heating medical gas space. The mechanical plans may have been approved allowing building supply for indirect heating. According to Kevin and NFPA 99, the fuel -fired building system would not work for the oxidizing gas storage area, that supply must be routed directly from exterior and the typical heating are radiant fixtures local to medical gas to create a separate space, esp. if we're tripping the H3 using Dewar's. At that time city opted for the more specific (medical) NFPA 99 requirements, but it may be that mechanical configuration may not work due to this indirect heating requirement Kevin lists below. Please re -check the configuration for medical gas heating at this location. lohn I Westfaill Deputy Chief/Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile lw� / BNOWMIZI co Affia DWF I &W V .tV T I T From: Scarlett, Kevin A (DOH) [mailto:Kevin.Scariett@DOH.WA.GOV] Sent: Thursday, October 08, 2015 2:11 PM To: Randy Hinton; David Wilson Cc: Tj Mellema; Martin Solorio; Paul Rasmussen; Pete; Bjorback, Leif; John 3. Westfall Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 Randy, The category of Cryogenic Oxidizing does not apply here. Actually we consider the product from Dewars the Hazard, not the contents of the compressed tank, therefore a Dewar in a Health Care Application/Use will always be in it's expansive form. Oxygen Dewars (depending on mfr) will range from 4500cf to 5500cf of this oxygen expanded gas volume. The 1 hr room separation requirement in N FPA 99 is overridden by N FPA 1 (1 FC) exempt Table 5003. 1.1 (1) under Oxidizing Gas takes you to an H-3 when you exceed 3000cf. This occupancy Sep is 2hr from H-3 to 1-2. Ps - Re: heat sources for this space ... from NFPA 99 ......... other indirect means" includes, electric/oil fin tube*, radiant panels*, light bulbs* * no exposed elements (electric resistant elements) and fixture carries a UL listing. Example: fixture with all electrical elements sealed within the unit as part of the UL listing. Thank you, Kevin A. Scarlett, RA, HFDP Senior Plans Reviewer - Construction Review Services - Hours: M-Th 6:00am - 4:30pm RA - Registered Architect - Washington State License HFDP - ASHRAE Certified Healthcare Facility Design Professional Washington State Department of Health 360-236.2949 Desk/Direct 253.355.6237 Personal Cell 360.236.2944 Main Office -General Public Health - "Always working for a safer and healthier Washington http://www.doh.wa.gov/crs Check project status by going to our website via 'ctrl+click' (you only need to enter the pro*ect number and click 'search'). hftps://fortress.wa.gov/doh/constructionreviewsearch/ 77his mc,%vsa1(,4, 11111Y h('0)11fldL'111i0I. If'YOU /I - V MiS111k.". J)ILWSC;101�f�' thCAL71(krand delele thc nies.sage. All me�ysages to and ftom the Depat-ilnent offlealth mu), he disclosed to the public. Notice on Interpretations: This correspondence is not a formal interpretation issued pursuant to the applicable licensing regulations, and does not necessarily represent the official position of the Department of Health. In addition, this correspondence is neither intended, nor should be relied upon, to provide professional consultation or services. From: Randy Hinton [mailto:rhintonCdricegroup.coml Sent: Thursday, October 08, 2015 1:11 PM To: Scarlett, Kevin A (DOH); David Wilson Cc: Tj Mellema; Martin Solorio; Paul Rasmussen; Pete; Bjorback, Leif; jwestfallMedistrictI.org Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 Kevin, Per our conversation (and for my understanding), the IFC states that we can have 90 lbs of cryogenic oxidizer liquid in a 1-hour room if sprinklered. And no applicable maximum for cryogenic oxidizing gas per Table 5003. This is not to disregard your stance on NFPA 99 but to clarify that the IFC takes a different look at the "state" of the oxygen and in our case we would be liquid with the Dewars. Furthermore, the 1999 NFPA 99 for over 3,000 cubic feet says the room must be 1-hour rated (see attached). I want to make sure that all of the information is on the table. I know you are busy but a quick response will be helpful in moving forward. Thank you, Randy Hinton 425-774-3829 From: Scarlett, Kevin A (DOH) [mailto:Kevin.Scarlett@DOH.WA.GOV Sent: Thursday, October 08, 2015 12:06 PM To: David Wilson <david@carlettiarchitects.com> Cc: Tj Mellema <tim@exxelpacific.com>; Martin Solorio <MartinS@exxelpacific.com>; Paul Rasmussen <Prasmussen@prestigecare.com>; Pete <peter@carlettiarchitects.com>; Bjorback, Leif <Leif. Bffiorback@ed mondswa.gov>; Randy Hinton <rhinton@ricegroup.com>; *westfall@firedistrictl.org Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 David, Yes, If you use (or intend to use) Dewars, the room must be 2hr (this room becomes an H-3 occupancy). You will need to submit to me (DOH) and Leif (City) for approval. Please note a few particulars (items you must provide) regardless of what direction you take; 1) all room electrical outlets and switches must be above 5ft. 2) ventilation - the SA & EA for this room must be dedicated and protected to the exterior (1 hr for 1-2 & 2hr for H-3). Therefore you will need to wrap the supply and exhaust duct continuous to the exterior. Dampers are not permitted. 3) verify room is heated to above freezing. This is generally done with a small oil/fin tube or radiant panel, but, it must be dedicated to this room. The section I was talking with Randy Hinton (Rice Group) about follows here, and doesn't really help this application much. It is a Code Commentary from NFPA 55 relative to the 20,000cf limit for'room within the building'. 4 35, uompressea uases ana uryogenic t-tuicis L;oae Uy, requires mar DuiK sysiems De iocarea eirner ouraoors or in a Duliving usea c )se. Because S. 1.3.3.1.9 requires that locations storing more than 566,335 L (ZO.00�0)_,qf oxygen comp ith NFPA 5 the maximE jy!W_ on that can be stored inside a health care facility is 566,335 L (20,000 W)i R is a tendency to use this number as the sole test of a bulk gas installation, which is not really the intent. To protect the operator, any ded with a stationary tank of liquefied gases should be installed following these rules insofar as Dossible. The hazards are common to mary liquid installation and are not unique to those aboveT in this edition are limitations on the sizes of gases other than oxygen and nitrous oxide. Any installation with more than 5L6,335 L (LO, Your design team is always welcome to contact NFPA for a formal interpretation and direction. Anyway, as you know, I sit on four NFPA Code Committees and my interaction with these NFPA folks is somewhat continuous. That said, specifically re: Dewars, I've already done that .... years ago and updates a couple times each year (when the issue is encountered) and as recent as this morning talking with the past NFPA 99 Chair (for over a decade) on Med Gas. Dave Mohile said, nope, nothing's changed, a Dewar is figured at 4500cf to 5500cf depending on mfr. He went on to say the reason NFPA has always used the expanded volume is the code is the purpose of limiting/guarding against the ability/capacity to fuel/feed/accelerate a fire. A somewhat separate issue, but, should be remembered, the tanks tend to 'off gas' a lot, so you will have more accelerant in the room than with standard H cylinders. Also, since there is no requirement for piped Med Gas in this Facility, you may de -couple this room/issue from the main project (Leif agrees). HOWEVER, you will need to contact us both relative to the particulars of required separate submittals and the current Med Gas system. In short, it can be done, but we both have requirements for this type of thing and you need to contact us directly to ascertain the particulars. I believe you have our contact information, please inform us of your intended direction. Thank you, Kevin A. Scarlett, RA, HFDP Senior Plans Reviewer - Construction Review Services - Hours: M-Th 6:00am - 4:30pm RA - Registered Architect - Washington State License HFDP - ASHRAE Certified Healthcare Facility Design Professional Washington State Department of Health 360.236.2949 Desk/Direct 253.355.6237 Personal Cell 360.236.2944 Main Office -General Public Health - "Always working for a safer and healthier Washington hftp://www.doh.wa.gov/crs Check project status by going to our website via 'ctrl+click' (you only need to enter the proiect number and click I search'). hftps://fortress.wa.gov/doh/constructionreviewsearch/ Thi-V Mil I'll(! (..W?fld011iU1. 16'011 t-CCeived it h), mistake, please nnlyj- the sender and delcte the MCSSM'C. -111 messages to and firom the Depurtment qflleallh maj; bedisclosed to the PlthliC. Notice on Interpretations: This correspondence is not aformal interpretation issued pursuant to the applicable licensing regulations, and does not necessarily represent the official position of the Department of Health. In addition, this correspondence is neither intended, nor should be relied upon, to provide professional consultation or services. From: David Wilson [mailto:david(&cariettiarchitects.com] Sent: Wednesday, October 07, 2015 4:49 PM To: Scarlett, Kevin A (DOH) Cc: Tj Mellema; Martin Solorio; Paul Rasmussen; Pete Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 Kevin, Just to clarify this is if we have to provide the 2 hour wall. It is our understanding that the Rice Group still feels that the 1 hour wall meets the requirement of the code for this med gas room with the Dewars Tanks. Again it is our understanding that you were going to forward on some code sections of why you feel that the med gas room needs to be a 2 hour enclosure. We want to be absolutely sure before we have Prestige go to the expense of providing a 2 hour room enclosure if the 1 hour enclosure is acceptable. Thanks for time, David Wilson Project Manager CARLMI ARcHrTECTS P.S. ARCHMMRE, INTERIOR DESIGN, & PMNING www.carleftiarchitects.com Ph: 360-424-0394 ext. 104 From: Scarlett, Kevin A (DOH) [mailto:Kevin.ScarlettC@DOH.WA.GO Sent: Wednesday, October 07, 2015 3:49 PM To: David Wilson Cc: Tj Mellema; Martin Solorio; Paul Rasmussen Subject: RE: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 David, Yes this will work. You will need to pay close attention to the wall to ceiling detail and arrange penetration protection (dampers). Alsd, this needs to go to Leif at the City ... but, I think he will be pretty quick on this .... we discussed it this morning. Thank you, Kevin A. Scarlett, RA, HFDP Senior Plans Reviewer - Construction Review Services - Hours: M-Th 6:00am - 4:30pm RA - Registered Architect - Washington State License HFDP - ASHRAE Certified Healthcare Facility Design Professional Washington State Department of Health 360.236.2949 Desk/Direct 253.355.6237 Personal Cell 360.236.2944 Main Office -General Public Health - "Always working for a safer and healthier Washington" hftp://www.doh.wa.-gov/crs Check project status by going to our website via 'ctrl+click' (you only need to enter the project number and click Isearch'). hftps://fortress.wa.gov/doh/constructionreviewsearch/ This message tmi.i. hL' C0t1fl11011i1J1. I(YOU I-CLVi1Vd it hV 111iStake, /dCUSC 120fili. thL' Sell(ILT Lohl LICIL'It! the HICSS(Il"t.' AII tnesso�gvs it) and fi,om the Deparitnent qf flealth mti.v , be disclused to the public. Notice on Interpretations: This correspondence is not oformal interpretation issued pursuant to the applicable licensing regulations, and does not necessarily represent the official position of the Department of Health. In addition, this correspondence is neither intended, nor should be relied upon, to provide professional consultation or services. From: David Wilson [mailto:david@carlettiarchitects.com Sent: Wednesday, October 07, 2015 2:59 PM To: Scarlett, Kevin A (DOH) Cc: Tj Mellema; Martin Solorio; Paul Rasmussen Subject: 13-625 Prestige Edmonds Med Gas question on 2 hour enclosure 10-7-15 Kevin, Concerning Prestige Care Edmonds Med Gas: If we changed the walls to 2 hour per the attached GA file #, and the ceiling of the med gas room to 2 hour per attached GA File #, and the doors to 2 hour could we keep the "FUTURE" Dewars system and avoid running the 2 hour walls all the way to the bottom of the roof deck above. Seems like this would meet the code. See attached GA File # options and sketch of the location of the 2 hour enclosure. Let us know ASAP if this is an option. Thanks, David Wilson Project Manager CARLErn ARCHrrECTS P.S. AROIMOURF, INTERIOR DESIGN, & MNNING www.carleffiarchitects.com Ph: 360-424-0394 ext. 104 John J. Westfall From: John J. Wesffall Sent: Friday, September 26, 2014 10:27 AM To: 'Paul Goto' Cc: '13jorback, Leif Subject: RE: Prestige Care Med Gas Paul: I want to let you know Leif and I have had discussion with DOH on prescriptive requirements for medgas system, specifically, the space heating requirements and supply/exhaust allowances. The city will deferring conflicting requirements to NFPA 99/101 from IMC/IFC, as they are more specific with your care facility design. Alldepartments approve of the Mechanical submittal and you should be able to pickup permit from Linda or Kristin. Thank you, John From: Paul Goto [mailto:paulg@ricegroup.com] Sent: Thursday, September 18, 2014 2: 11 PM To: John 1. Westfall Cc: '13jorback, Leif Subject: RE: Prestige Care Med Gas No problem. It is good that you are busy. Let me know if you have any questions. It is a little difficult when different sectors ask for different things. Thank you, Paul Goto, E.I.T. R I C E Group, Inc. Mechanical Consulting Engineers p. 425.774.3829 x-203 f. 425.672.2084 20201 Cedar Valley Road, Suite 120 Lynnwood, WA 98036 www.ricegroup.com From: John J. Westfall [mailto:�westfall@firedistrictl.org] Sent: Thursday, September 18, 2014 10:39 AM To: 'paulg@ricegroup.com' Cc: 'Bjorback, Leif' Subject: RE: Prestige Care Med Gas Hi Paul: We're sorry for delays on this, we have a lot of projects coming due. We'll be back soon on the items. John 1 From: Westfall, John [ma i Ito: joh n.westfa 11 ccbed mondswa. go Sent: Wednesday, September 10, 2014 7:37 AM To: John J. Westfall Subject: FW: Prestige Care Med Gas From: Paul Goto [mailto:r)aulq@ricegroul).com] Sent: Tuesday, September 09, 2014 5:58 PM To: Westfall, John; Bjorback, Leif Subject: RE: Prestige Care Med Gas Hi John, I was out of the office this morning, so I apologize for not getting back to you right away. The "indirect heating" requirement comes from NFPA99 1999 edition which is what the DOH uses for regulations. Section 4-3.1.1.2 Storage Requirements #10 g. Heating shall be by steam, hot water, or other indirect means. Cylinder temperatures shall not exceed 130 degrees F. If we bring in 100% OSA into the room. We would then need to heat the air during the winter because we would potentially be bringing in 18 degree air. We do not have steam, and the only hot water is for domestic use. You are correct with the code stating that the supply duct should come from the outside. We have done this in the past and it has not had an issue. This is our way of getting outside air into the space while still providing the indirect means of heat. This may be something that we will need to have a phone conversation about. I want to comply with what you are looking for, and also with what DOH will be requiring as well. Thank you, Paul Goto, E.I.T. R I C E Group, Inc. Mechanical Consulting Engineers p. 425.774.3829 x-203 f. 425.672.2084 20201 Cedar Valley Road, Suite 120 Lynnwood, WA 98036 www.ricegroup.com From: Westfall, John [mailto:"ohn.westfall@edmondswa.gov] Sent: Tuesday, September 09, 2014 9:48 AM To: Bjorback, Leif; 'paulg@ricegroup.com' Subject: RE: Prestige Care Med Gas Here's the complete thought, thanks. From: Westfall, John Sent: Tuesday, September 09, 2014 9:42 AM To: Bjorback, Leif Cc'-' 'paulg@ricegroup.com' Subject: RE: Prestige Care Med Gas Paul: Although oxygen is non-flammable, the presence of oxygen will increase the combustion hazard directly related to increased concentrations. This is a reason why IFC regulates medical gases, oxygen and oxidizing gases as hazardous materials that must be treated more carefully than indoor air. I have two questions: 1) Where does the "indirect heating" requirement come from? This is an interior space is why we can't use exterior room prescription, but all spaces are heated below and at sides. Oxygen or medical gases will not freeze in this application and the interior room is not living space. 2) As I read your excerpt from 5306.2.2 below, I've highlighted in yellow below a prescription that is not being met: that with the supply air coming from the "exterior". Lastly, Leif and I had been through the justification you make in closing. I trust there will be conditions where the gas could backfill the interior spaces, I have seen many "never happens" occur. Our take from fire and building codes is that both supply and vent goes to/comes from the exterior, then is the challenge where to site the exhaust away from intake and any other intakes above. Please respond. John J. Westfall Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile SN10HOMI$11 co, F I 'RD E DI.S."AFRI'VT From: Bjorback, Leif Sent: Monday, September 08, 2014 2:12 PM To: Westfall, John Subject: FW: Prestige Care Med Gas John, you good with this? From: Paul Goto [mailto:paulqftricegrour).coml Sent: Monday, September 08, 2014 2: 11 PM To: Bjorback, Leif Subject: Prestige Care Med Gas Leif, It has been common for us to take a supply duct from the main heating and cooling unit to the medical gas storage room. This way, we are not adding more equipment to maintain the indirect heating of the room. This is the section from the 2012 international fire code. 5306.2.2 One -hour interior room. When an exterior wall cannot be provided for the room, automatic sprinklers shall be installed within the room. The room shall be exhausted through a duct to the exterior. Supply and exhaust ducts shall be enclosed in a 1-hour-rated shaft enclosure from the room to the exterior. Approved mechanical ventilation shall comply with the International Mechanical Code and be provided at a minimum rate of I cubic foot per minute per square foot [0.00508 M3/(S. M2)] Of the area of the room. Only oxygen is being stored in this room, and it is not flammable, or toxic. If a 250 Cubic foot tank has a leak and back pressures the supply duct, the oxygen will have no adverse effects on the people in the hallway or other surrounding areas. The room is 4.5' by 9' and the ceiling is 8 feet tall. This is 324 cubic feet, so if a tank leaks all of its contents, it will not fill the room. Please let me know if you have any other questions. Thank you, Paul Goto, E.I.T. R I C E Group, Inc. Mechanical Consulting Engineers p. 425.774.3829 x-203 f. 425.672.2084 20201 Cedar Valley Road, Suite 120 Lynnwood, WA 98036 www.ricep,roup.com CE9� -0- (�� EPIr-WEERING August4,2014 John Westfall, Fire Marshal City of Edmonds 1215 th Ave N Edmonds, WA 98020 RE: BLD2014-04S7CIVILS21008 Project Name: Prestige Care Project Address: 21008 76 th Ave W DearJohn, AUG 0 6 2014 BVILDING DEPARTMENT CITY OF EDMONDS Itemized below is our response to the plan review memo dated July 24,2014 for the above referenced project. Our responses appear In bold. 1. 1 understand that Engineering Division has requested plan specifically for fire supply line and appurtenances. Fire Prevention Services will like to review the proposal for location and configuration of FDC, PIV, and DCDA vault. Refer to C4.1 Sheet. 2. Provide make& model for WA State DOH -approved DCDA. Provided with OCIDA detail on Sheet C4.2 3. Add COE Engineering details E.7.8 and E.7.8.1: Details added. 4. Show designated fire lanes on civils &/or site plan. Designated FIRE LANE should continue along the east side access road continuing only to the main entry doors at the south side of building. Provide yellow paint on curb face, or 4" bars on asphalt with black FIRE LANE — NO PARKING message alternating every 50'. Fire lane will not continue over storm water vault. Fire lane depicted on architectural site plan. Note regarding painted curb and fire lane message added to C4.1 plan In dvil drawings. 5. No detention lid "point" loading requirements in fire lanes due to single story design, use HS-20 "live" loading for regular traffic loads. Noted. If you have any questions or comments regarding the responses, please do not hesitate to call. Sincerely, tCG gineering GreG len, PE SE Principal 'C Westfall, John From: Westfall, John Sent: Tuesday, October 14, 2014 5:08 PM To: Startzman, Jeanne Cc: Zweber, Kevin Subject: RE: Fawcett Records Request Rcv'd 10-13-14 Attachments: 20141014163319.pdf Request Received: Oct 13, 2014 Request (Summary): Hazmat incidents 21008 76 th Ave W Jeanne: The Edmonds Department of Fire Prevention office has address file for 21008 76 th Ave W, an assisted living facility. 2100876 th Ave W: No hazardous material incidents were found in address file information. I have found two emergency response incident reports in FD1 incident database since 1/1/2007, attached, consisting of 1) natural gas leak and 2) paint overspray event. This satisfies all available information requested by attached request. John I Westfall Fire Marshal Fire Prevention Services 425-771-0213 Desk 425-775-7721 Fax 425-231-3644 Mobile I SNOHOMISH CO F I RE DISTRET From: Startzman, Jeanne Sent: Monday, October 13, 2014 11:54 AM To: Westfall, John Cc: Zweber, Kevin Subject: Fawcett Records Request Rcv'd 10-13-14 Hi FDI, Attached is a records request for hazardous materials incidents at 21008 — 76 th Ave W. Our response is due October 20th; please let me know if you will need a date extension. Thanks, Jeanne S. Public Disclosure & Records Maintenance Specialist City of Edmonds 0 425-775-2525 ext. 1244 From: Della Fawcett [mailto:DFawcett(�)landauinc.com] Sent: Monday, October 13, 2014 9:54 AM To: Records Requests Subject: Public Records Request Hello, Please find attached my Public Records Request. Thank you, Delia Fawcett * Senior Project Geologist Landau Associates, Inc. 333 SW 5"' Avenue, Suite 700, Portland, OR 97204 (503) 542-1080 * fax (503) 542-1081 dfawcettalandauinc.com * www.landauinc.com Landau Associates is proudly carbon -neutral through our sustainable practices and financial support of U.S.-based carbon -reduction projects. NOTICE: This communication may contain privileged or other confidential information. If you have received it in error, please advise the sender by reply email and immediately delete the message and any attachments without copying or disclosing the contents. Thank you. I Your Name I Time Spent ,bohn Westfall 160 minutes 7 F_ TOTAL[60 minutes CITY OF EDMONDS Tracking No. 121 5th Avenue North Edmonds, WA 98020 425.775.2525 (phone) 425.771.0266 (fax) Email: prr@edmondswa.gov (Save completed form to your computer before attaching to email) REQUEST FOR PUBLIC RECORDS Date of Request October 13, 2014 Requester Name: Della Fawcett Requester Address: 333 SW 5th Avenue Street SuitelApt 700 City State zip Email Address: Portland, OR 97204 Phone Number: 503-542-1097 Request Made: [] In Person E] In Writing E] Telephone E] Fax R] Email How would you prefer to be notified when the records are available? E] In Writing E] Telephone E] Fax F;� Email DESCRIPTION OF REQUEST: Be Spec and provide as much detail as possible; include address and owner of property; file name or number; time period, incident location and date; case number; any other names associated with your request; etc.): I am looking for any records regarding fire or hazardous materials incidents at 21008 76th Avenue West, Edmonds, WA. I agree to pay for any requested copies per the City's adopted fee schedule. Yes R1 Is the information requested a list of individuals to be used for a mailing list for commercial purposes? Yes [:1 No [Z] If yes, please complete the additional form found on page 3. "Responses to requests for public records shall be made promptly by agencies, the office of the secretary of the senate, and the office of the chief clerk of the house of representatives. Within five business days of receiving a public record request, an agency, the office of the secretary of the senate, or the office of the chief clerk of the house of representatives must respond by either (1) providing the record; (2) providing an intemet address and link on the agency's web site to the specific records requested, except that if the requester notifies the agency that he or she cannot access the records through the intemet, then the agency must provide copies of the record or allow the requester to view copies using an agency computer; (3) acknowledging that the agency, the office of the secretary of the senate, or the office of the chief clerk of the house of representatives has received the request and providing a reasonable estimate of the time the agency, the office of the secretary of the senate, or the office of the chief clerk of the house of representatives will require to respond to the request; or (4) denying the public record request. In acknowledging receipt of a public record request that is unclear, an agency may ask the requestor to clarify what information the requestor is seeking. ff the requestor fails to clarify the request, the agency need not respond to it." RCW 42.56.520 (in part) Page -1- Incident Report Snohomish County Fire District I 2010-0016631 -000 Basic Alarm Date and Time 19:44:00 Monday, December 20, 2010 Arrival Time 19:50:00 Controlled Date and Time Last Unit Cleared Date and Time 19:54:00 Monday, December 20,2010 Response Time 0:06:00 Priority Response Yes Completed Yes Reviewed Yes Fire Department Station 16 Shift B Incident Type 745 - Alarm system sounded, no fire - unintentional Aid Given or Received N - None Alarms I Action Taken 1 86 - Investigate Casualties No Apparatus - Suppression I Personnel - Suppression Personnel 3 Property Use 311 - 24-hour care Nursing homes, 4 or more persons Location Type Address Address 21008 76 AVE W City, State Zip Edmonds, WA 98026 District I Apparatus - E16 Apparatus ID E16 Response Time 0:06:00 Apparatus Dispatch Date and Time 19:44:00 Monday, December 20, 2010 En route to scene date and time 19:44:00 Monday, December 20, 20 10 Apparatus Arrival Date and Time 19:50:00 Monday, December 20, 20 10 Apparatus Clear Date and Time 19:54:00 Monday, December 20, 2010 Apparatus priority response Yes Number of People 3 Apparatus Use I Apparatus Action Taken 1 86 - Investigate Apparatus Type I I - Engine Personnel 1 7909 - Oftedahl, Dennis Position: CAPT Personnel 2 8606 - Martin, James Position: FF/EMT Personnel 3 0920 - Robinson, Antonio Position: FF/EMT Authority Reported By 7909 - Oftedahl, Dennis 21:44:50 Monday, December 20, 2010 Officer In Charge 7909 - Oftedahl, Dennis 21:45:55 Monday, December 20, 2010 Reviewer 7909 - Oftedahl, Dennis Page: I Printed: 10/14/2014 16:31:06 Incident Report Snohomish County Fire District 1 2010-0016631 -000 Authority 21:44:56 Monday, December 20, 2010 Narrative Name New Narrative Narrative Type Incident Narrative Date 21:42:52 Monday, December 20, 20 10 Author 7909 - Oftedahl, Dennis Author Rank CAPT Author Assignment I Narrative Text E 16 arrived on scene and was met by nursing home staff. A painting company was painting the physical rehab area. The mist from the paint sprayer set off the alarm. There was no fire. The system was reset and confirmed by the alarm company. E 16 then returned. End of Report Page: 2 Printed: 10/14/2014 16:31:06 Incident Report 2012-0016728 -000 Snohomish County Fire District I Basic Alarm Date and Time 20:51:05 Friday, November 9, 2012 Arrival Time 20:56:48 Controlled Date and Time Last Unit Cleared Date and Time 21:44:00 Friday, November 9, 2012 Response Time 0:05:43 Priority Response Yes Completed Yes Reviewed Yes Fire Department Station 16 Shift D Incident Type 412 - Gas leak (natural gas or LPG) Initial Dispatch Code GLI Aid Given or Received N - None Alarms I Action Taken 1 86 - Investigate Action Taken 2 84 - Refer to proper authority Casualties No Apparatus - Suppression 3 Personnel - Suppression Personnel 7 Property Use 311 - 24-hour care Nursing homes, 4 or more persons Location Type Address Address 21008 76 AVE W City, State Zip Edmonds, WA 98020 District I Map Page EF206 Apparatus - E16 Apparatus ID E16 Response Time 0:02:44 Apparatus Dispatch Date and Time 20:51:35 Friday, November 9, 2012 En route to scene date and time 20:54:04 Friday, November 9, 2012 Apparatus Arrival Date and Time 20:56:48 Friday, November 9, 2012 Apparatus Clear Date and Time 21:44:00 Friday, November 9, 2012 Apparatus priority response Yes Number of People 3 Apparatus Use I Apparatus Action Taken 1 86 - Investigate Apparatus Action Taken 2 84 - Refer to proper authority Apparatus Type I I - Engine Personnel 1 0808 - Bien, Keith Position: FF/EMT/I Personnel 2 0920 - Robinson, Antonio Position: FF/EMT Personnel 3 0202 - Dowling, John Position: CAPTIRR Apparatus - BC -I 6 Apparatus ID BC16 Page: I Printed: 10/14/2014 16:34:52 Incident Report 2012-0016728 -000 Snohomish County Fire District I Response Time Apparatus Dispatch Date and Time En route to scene date and time Apparatus Arrival Date and Time Apparatus Clear Date and Time Apparatus priority response Number of People Apparatus Use Apparatus Action Taken I Apparatus Action Taken 2 Apparatus Type Personnel I Apparatus - BC16 0:02:44 20:51:35 Friday, November 9, 2012 20:54:04 Friday, November 9, 2012 20:56:48 Friday, November 9, 2012 21:09:00 Friday, November 9, 2012 Yes 93 - Cancelled en route 84 - Refer to proper authority 9 10 - Battalion Chief unit 8005 - Allison, Steve Position: BC Apparatus - E 17 Apparatus ID E17 Response Time 0:02:56 Apparatus Dispatch Date and Time 20:51:35 Friday, November 9, 2012 En route to scene date and time 20:54:04 Friday, November 9, 2012 Apparatus Arrival Date and Time 20:57:00 Friday, November 9, 2012 Apparatus Clear Date and Time 21:07:00 Friday, November 9, 2012 Apparatus priority response Yes Number of People 3 Apparatus Use I Apparatus Action Taken 1 93 - Cancelled en route Apparatus Action Taken 2 84 - Refer to proper authority Apparatus Type I I - Engine Personnel 1 8606 - Martin, James Position: FF/EMT Personnel 2 9816 - Hunter, David Position: CAPT Personnel 3 9118 - Soucy, Joseph Position: FF/EMT Authority Reported By 0202 - Dowling, John 05:59:11 Saturday, November 10, 2012 Officer In Charge 0202 - Dowling, John 05:59:13 Saturday, November 10, 2012 Reviewer 0202 - Dowling, John 05:59:14 Saturday, November 10, 2012 Narrative Name Narrative Type Narrative Date Author Author Rank Narratives E16 Incident 05:51:45 Saturday, November 10, 2012 0202 - Dowling, John CAPTIRR Page: 2 Printed: 10/14/2014 16:34:52 Incident Report 2012-0016728 -000 Snohomish County Fire District I Narratives Author Assignment I Narrative Text (205 1) E 16, along with BC 16 and E 17, responded to the report of a gas leak inside of a structure. E 16 arrived on scene and made contact with staff who directed our crew back to the kitchen area. The kitchen area had a light odor of natural gas. E 16 requested a priority response from PSE. E 16 located a gas stove that had six burners with pilot lights. Four pilot lights were on and two where out. E 16 secured the gas to this stove and began natural ventilation. PSE arrived on scene and investigated the the kitchen and found negligible reading for natural gas. The tech who responded made contact with staff and advised them that he would "re -light" their stove for them. End of Report Page: 3 Printed: 10/14/2014 16:34:52 FACILITY MAINS: SWITCHES, CONTROLS & SHUTOFFS F %1% 1 6 00 0- IM 9.1)"P, 6 \6 \I- \0 0 0 Z t;) 0�e\ '�L\ F 0 (411 LLIJ A 1. Main Water Valve ADA 2. Main Power Panel & 10 Fire Alarm System 3. Main Telephone Panels 4. Automatic Timer - outside 6,0 S Lights I a 5. Air Compressor for Laundry 6. Laundry Power Panel - Includes Dishwasher 7. Automatic Timer - Front Sign 17 8. Section Power Panel 9. Kitchen Power Panel 10. Power Panel for Baili_�r & Water Heater Pumps 15 11. Main Gas Inlet & Met r 12. Section Power Panel I low. 13. Telephone Section Pane 14. Automatic Timer - Door. Warning System 1 15. Automatic Timer - Papio Lights (in bushes) F_DfVV'0NDs 16. Facility Thermostat 21COO 76TH tV. 17. Telephone Section Pa�el RRE DOOR 413N. 00O20 18. Section Power Panel 19. Gas Shut-off - Fireplace FIRE ALARM SO X 11171 lr"2� 1: 1 RE EXIT DOORS A P% Ra MWT) A-�Gu ISHZP, Eagle Eye Consulting Engineers, PS West Coast Code Consultants Company PO Box 523 01alla, WA 98359 hoytjeter@centurytel.net 206-356-7790 To: Leif Bjorback, Building Official City of Edmicinds Woodinville WA 98072 Re: Prestige Care Fire Sprinkler Package 2100876 1h Aveniue West Edmonds, WA 98026 Edmonds Permfit-V-i EECE#: EDM 14-06 4-1320 ?��9LE EYE NG ENGINEERS A VV�l Co.st C.d. C.—ftnts C—p—i Friday, January 2, 2015 The above referenced project is in the process of plan review for compliance with City of Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plan review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. A response to correction must be provided to the citv within 90 days of the date of this letter or the permit application mav be cancelled without notice. SCOPE OF REVIEW The scope of this. review is for the Fire Prevention requirements of this proj ect. The project was reviewedfor compliance ivith the State of Washington Building Codes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. FIRE COMMENTS 1. General Note #5 on sheet FP6 makes reference to NFPA 13R. In looking up the use of this building on the web it appears that it will be used for more than simply custodial care and will service persons that are "incapable of self-preservation". As such it should be considered an 1-2 occupancy in accordance with IBC 308.4. This EECE Project EDM 14-06 Edmonds Permit BLD2014-1320 Page 2 of 3 would require that the sprinkler system design meet the requirements of a full NFPA 13 system per IFC 903.2.6. Please address. 2. In accordance with Section'22.1.3 of NFPA 13 the plans should clearly note all fire separation walls and rated floors as well as the method and means of providing appropriate fire stopping at piping penetrations of these rated assemblies per IBC 713. Please address. 3. Please note the "clearance" requirements for piping passing through walls and floors as required by Section 9.3.4 of NFPA 13. 4. Please clarify how hanger rods are to be attached to and supported by the structure in accordance with Section 9.1 of NFPA 13. 5. No information regarding sway bracing has been provided on the plans. Section 9.3.5.3 requires sway bracing of all feed and cross mains as well as all branch lines 2.5" or larger. Please clarify sway bracing requirements on the plans and provide supporting calculations in accordance with Section 22.1.3 of NFPA 13, Item 39. 6. Please clarify on the plans how restraint of branch lines less than 2" will be provided as required by Section 9.3.6 of NFPA 13. 7. The plans specify a volume of 551 gallons for the attic dry pipe system and 120 gallons for the canopy dry pipe system yet a calculation complying with Section 7.2.3 of NFPA 13 has not been provided. Please address. 8. While material data was provided for the air compressors that can be used for the dry pipe system, the particular compressor that will be used has not been noted. Please confirm that the air supply source will be available at all times and that it can meet the 30-minute fill requirement for the dry pipe system as required by Section 7.2.6.2 of NFPA 13. 9. The plans must clearly note the following water flow test information in accordance with Section 22.11 of NFPA 13: a. Static pressure b. Residual pressure c. Flow d. Date of test e. Name of person/company who perforined the test 10. While the riser diagram on sheet FP6 calls for a spare sprinkler box, please clarify that a minimum of two spare sprinklers of each type and the appropriate wrenches shall be provided as noted in Section 6.2.9 of NFPA 13. 11. While sidewall sprinklers are shown at the bottom of the elevator shafts, sprinklers are not specified at the top of the shaft as required by Section 8.15.5.4 of NFPA 13. Please confirm that the shaft consists of noncombustible construction and that the elevator car enclosure meets the requirements of ASME A 17. 1. 0 EECE Project EDM 14-06 Edmonds Permit BLD2014-1320 Page 3 of 3 12. The following Tyco material submittals for sprinkler heads were provided, yet these types of sprinklers have not been specified on the plans. Please clarify. a. TFP172: TY313 and TY323, quick response, standard coverage sprinklers b. TFP500: TY3255, TY3155 and TY3355, dry -type sprinklers 13. Please address the following discrepancies in the material data provided for the sprinklers called out on the plans. Please coordinate. a. TY3235: The plans specify a 1/2" NTP while TFP5 10 lists V'. b. TY3335: The plans specify a 1/2" NTP while TFP51 0 lists I". c. TY318: The plans specify a K-factor of 8.0 and 3/4" NTP while TFP610 lists a K-factor of 5.6 and 1/2" NTP. 14. While the riser diagram on sheet FP6 notes an alarm bell is required, it does not specify the type of bell as required by Section 22.1.3 of NFPA 13, Item 26, nor has material data for the alarm been provided. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans may also be reviewed concurrently by other departments within the City of Edmonds. Changes, clarifications or additional corrections may be required subsequent to the reviews performed by these other departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (206) 356- 7790 or by email at chrisk@wc-3.com or Hoyt Jeter. By: 0-0 Chris Kimball, P.E., S.E. ICC Fire Plans Examiner ICC Fire Inspector 1/11