Loading...
21822 76TH AVE W82- Z -7 to A 0 Or, W FIRE PREVENTION DIVISION Fire Alarm Checklist Name of Building or complex FGA0,qIc/41 Date Address Ak,?AV, 26-y"A ve Permit number je L-1- ;Z 0 1 Fire alarm system complete and[] Fire alarm system pre -testing complete Building occupants (if applicable) notified of fire alarm testing System is in test mode [ I SnoCom has been notified [ ] Knox box has been provided Remote annunciator is properly located, accessible, not obstructed and conforms to approved plans [ ] Fire alarm control panel is properly located, accessible, and not obstructed and conform to approved plans. [ ] Approved signage has been provided. This includes signage to specific locations and specific features. ( ie. Dry Standpipe and FDQ [ ] Provide the alarm monitoring compan I name and 24 hr number on the control panel. Monitoring company's name NIZ2 her-7-0-Aw rJ I-e- Provide a manual pull station reset key(s) as needed for the Knox box. System loss of ac power, verify operation standby power AES check list completed (on reverse side) Fire alarm control panel circuit breaker shall be labeled FACP, painted red, and locked in the ON position. [ ] Fire alarm panel shall indicate what circuit breaker supplies power and the location of the panel where that circuit is located. Check a random selection of initiating devices (minimum of 25%) Activation of audible, visual and audible / visual devices. Verify visual synchronization Outside horn / strobe activation and location Verify alarm, supervisory, and trouble retransmission signals to monitoring station Require Certificate of completion from insta"r Signature of Fire Official -C� Wireless Mesh Network (AES) Installation Inspection Checklist All AES radio transmitters shall be installed and inspected according to NFPA 70, NFPA 72, WAC, manufacturer requirements/recommendations. /'The AES Radio is mounted near the FACP in a temperature controlled environment. If it is mounted on the interior side of an exterior metal, concrete, or block wall it is mounted on an insulating board to prevent direct contact with moisture or temperature extremes. Alternate locations, if approved by the fire marshal may require the AES Radio to be located inside a lockable NEMA 4X enclosure with smoke detector and thermostatically controlled heater. 9/_AES routing table shows a minimum of two (2) "good" paths with a net -con of 0-5 prior to connecting to FACP. p--'AES is protected by a smoke detector. V"AIC transformer to AES is protected inside a secured transformer enclosure. t/The A/C transformer is one of the following 3 models; AMSECO model XF1640, Elk Products model TRG1640, or MG Electronics model MGT1640. 6,-,'Wires from A/C transformer enclosure to AES enclosure are in conduit. tAAES is powered via dedicated A/C circuit or shared with a dedicated circuit to FACP. V'AIC breaker to AES circuit is labeled and provided with a lock -on device. ,"'All exposed wiring below seven feet (7� AFF is protected in conduit. Coaxial cable outside the AES enclosure is installed in conduit. 00 A//WExterior antennas are protected by a lightening arrester. Arrester is located a minimum 6'from AES radio and grounded to earth with a minimum 6 AWG copper wire. All bends in the coaxial cable outside of the AES enclosure (if applicable) have a minimum six inch (6'1 radius. Mljvl�AES AND IntelliPro Fire or FireTap (if installed) is locally supervised at the protected premises (both audibly and visibly) in an approved manner for antenna cut, low battery, communication troubles, and charger fault as a separate zone or address on the FACP. (14 outputs) General alarm (zone 1), general trouble (zone 2), and supervisory (zone 3) outputs from the FACP are connected to supervised input zones on the AES. �/AES programming: Trouble Pkt is set to "Y", zone inputs in use are set to "F" w/ EOLs. VIAll zones, signals, or addresses capable of being transmitted by the FACP are transmitted to the /c c ntral station. This may require an IntelliPro Fire or FireTap. A current Routing Table showing the NetCon, Link Layer, and Signal Strength (minimum 2 "Good" paths with a minimum NetCon of 5 or less) is to be provided to the Fire Inspector at time of final inspection. Event History S stem # 200652942 y Seq # 2498987602 CS # Emp # Event Date: 2/24/2017 10:52 AM Event ID: PF1656 User ID: Area: 0 Zone ID: 1 Event Description: Fire (DISP Match: l.CID.El. 1 l.Task*.738.,--- 2 FD-1, k - � .1 Karl Fifterer From: KARL FITTERER [kjfitt@msn.com] Sent: Friday, February 24, 2017 11:17 AM To: Karl Fitterer Subject: BLD20170175 tuca Integrated Security Fire Alarm System Discontinuance Letter 9931UEOO Tyco Integrated Security Edmonds Fire Department 14200 E Exposition Ave Aftn: 121 5th Ave N Aurora, CO 80012 Edmonds, WA 98020 Tel: Fax: Check Type of Letter Toll Free: 888-989-2647 One www.tycols.com X This letter will serve as formal notification that the fire alarm system at the business location listed below will no longer be monitored by Tyco Integrated Security effective. This letter will serve as a formal request that the fire alarm system at 13 the business location listed below shall be removed from the local alarm board following your approval. 425-775-7166 Business Name: Sound Urology 1822 76th Ave W Business Address: (�� City, State, ZIP Code: Edmonds, WA 98026-7900 Reason for Discontinuance Customer Changein [3 Reason Not 0 Moved/ X Service 0 Non-payment Closed Provider Provided Type of Discontinuance Full Maintenance X (Monitoring/ 0 Monitoring Only 0 Only Maintenance) Date Effective : 2 16 / 17 Please do not hesitate to contact me at 888-989-2647 with any questions you may have. Thank you, Brent Duncan 303-306-5585 Tyco Integrated Security OIL FIRE PREVENTION INSPECTION REPORT .$erving Bri�r, Edmonds, and ",12425 Meridian Ave S SNOHONIISII Co. If A 98208 *DMONDS Etg. Mollntlak�" Terrace Everett, W 0 BRIER F11 0 MOUNTLAKE TERRACE Phone (425) 551-1200 0 UNINCORPORATED DES., r Lln R www..FireDistrict].org Fax (425) 551-1272 FREQUENCY I STATION& SHIFT*� LOCATION: 21822 76 th Avenue W 98026 2016 20-D BUSINESS NAME: Sound U rologica (Associates PHONE: 4257757166 SCHEDULED Nov 2016 DATE DUE MAILING LIFIR � 593 156 ADDRESS: 21822 76th Avenue W, Edmonds, WA 98026 BUSINESS OWNER: Roddy, Timothy HOME PHONE: EMERGENCY-1: Sound Urological Assoc. L::A HOME PHONE: 4257757166 KEY ACCESS-2: HOME PHONE: EMAIL: —6:AA1TAl#4W 6.�amjD "iwc,96Y, t�oni PERSON CONTACTED INAME OF INSPECTOR: Vjltj�100 FIRE SYSTEMS: 13-Jul FE 91 IT. AS -*lp I Fh 2V/-; -- SF�CK rto6v 1 Date Last Serviced: S,45;r A�&a,"S CURRENT CITY -,, YES NO BUSINESS LICENSE El R INITIAL INSPECTION'DATE. 11-23 �A -2 ,MT ). 2013 10:52AM .tqqo Integrated Security Fire Alarm Inspection and Testing Report Date:�2 9— o 1,::k Tirnw. SERVICE ORGANIZATION Name: Two Intearated Securi & Representative: License No* Telephone: No. 6582 P. I 8833UEOO Inspection Job N: _1�t�ba PROPERMAME (U ER) Wn, e Li JG0 i L) onA AddraEs: ZIP-2-0 Owner Contact; Telephone: —7 MONITORING ENTITY contacE -IYW :I; C��) Telephone; 1500 9_99 2_(,A-�— I - Monitoring Account Ref No (CS#): APPROVING AGgkcy Contact: Telephone: TYPE TRANSMISSION SERVICE El McCulloh AlarmNat [J Weekly Multiplex Telular E] monthly Digital AAG&rd Bimonthly ri Retarve.1'riority Ounneriy n RF Semiannually Other (Specify): *Annually E] Other (Specify):. Control Unit Manufacturer: ht>-r- Circuit Styles: Model No: Number of6ircuits., 5 Software Rev.: "62— Last Date System HadAny Service Pedormed: Last Date that Any Software or Configuration Was Revised; ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Devices cIrcultatyla Quantity of Devices Installed B Tested 3 Manual Fire Alarm Boxes Ion Detectors Photo Detectors Duct Detectors —C He at Detectors :L7-- Waterflow Switches Supervisory Switches Olher(Specifv), Alarm verification feature is:. Disabled F-1 Enabled Reprintedwiih permission from NFPA 72 0 2001. National Fire Alarm Cod4, CopyrIghtO 2007, National Pro Prolection Aeaociation, Ouincy, MA 02169, This reprinted material Is 1p. 10141 ,1011hc complete and Official position oftheNFPAon the referenced subject which Is represented only by thestandard In litemiretv. M t - �__ 51 — rteicoii�GTM# ADS i =ea vMWIM- Jul.25. 2013 10:52AM tq00 .' Integrated Security ALARM NOTIFICATION APPLIANCES and CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Appliances Installed Appliances Tested Bells Horns Chimes Strobes No. of alarm notification appliance circuits: Are circuits monitored for integrity? Wry" E] No Speakers Olher(Spaelfy): No. 6582 - P. 2 8833UEOD SUP&Q,VISORY SIGNAL -INITIATING DEVICES and CIRCUIT INFORMATION QtyofDevIcQ_9'-"CircuIt'9W8 Qtyofnovicos QtyofDevices Circultstyle QtyofDevicas Installed Tested Installed Totted Build[AgTornp. Fire Pump/Pump Controller TrbI Site Water Tomp. Fire Pump Low Fuel Sho 'h evel Generator In Auto Position ave' Fire Pump Power Generator or Controller Trouble Fire Pump Running Switch Transfer mp Fire Pump Auto Position Generator Engine Running Other (specify): SIGNALING LINE CIRCUITS Sao NFPA 72 section for Protected Premises Fire Alarm Systems, Performance of Signaling Line Quantity and style of signaling line circuits connected to system.,. Circuits (SLC), table for Performance of Signaling Line Circuits for Class and Style Quantitr, Style(s): SYSTEM POWER SUPPLIES (a) Primary (Main): NaminalVoltage:_170 VAt _ - Amps: OvercurrentProtectiom Type: _Znea� — Amps; Location (of Primary Supply Panelboard): &�r_ rUA� P. Disconnecting Means Locations: Jb) Secondary (Standby); StoraaeBatterV:Amj'.-Hr.Ftafing: Calculated capacity in Arnp+frs to operate system for hours Engine -driven generator dedicated to fire alarm system; Location of fuel storage: BATTERYTYPE DryCall [] Nickel -Cadmium Ea SealedLead-Acid E] Lead -Acid E] Other(Specify): (c) Emergency or standby system used as a backup to primary power supply. instead of using a secondary power supply: Emergency system described in NFPA 70, Anicle 700; 4 Legally required standby described in NrPA 70, Article 701: Optional standby system described in NFPA 70, Article 702. which also meeia the performance requirements of Article 700 or 701: fl,�Printad %ith permission from NFPA 72 0 2007, National Fire Alarm CodeT. CopyyightO 20ol, National Fire Protection AssociaUon, QuineV, MA 02 188. This reptinted material Is 1p, 2 014) oot the complete and dfflCiAl DDOitiOrk Of 1haNFPAnnVh.,.fAranPAdaijh1-,t -4,i,k Jul 25 2013 10:52AM Integrated Security PRIOR TO ANY TESTING NOTIFICATIONS ARE MADE Monitoring Entity Building Occupants Building Management Olher(Spec4) AHJ Notified of Any Impairments yar; El No El El D R E) No. 6582P. 3- 8833UEOO Who Time SYSTEM TESTS and INSPECTIONS TVp0 Visual Functional Comments Control Unit X Ay, J* Interface Equipment Ar 94 —OL Lamps/LEDs El 0 Fuses 0 0 Primary Power Supply UQ Trouble signals wr Disconnect SwAtches Ground-Faul I Monitoring SECONDARY POWER Type Visual Functional Comments Battery Condition 49 (+-- LeadVoliage D( DischargaTest Cl Charger Test El Specific Gravity TRANSIENT SUPPRESSORS REMOTE ANNUNCIATORS NOTIFICATION APPLIANCES Type Visual Functional Comments Audible Cl 1116 r-Y) Visible El Speakers Voice clarity INITIATING and SUPERVISORY DEVICE TESTS and INSPECTIONS Loc. & S/N DaviceType, Visual functional Factory Setting Measured 811fting Pass Fall 240b �Smk cid C1 �4 PA '6 11 El El 11 0 11 13 El 0 El El El El Cornment(;:-- --- I ry�— t , — M) � Relprinted with permlssion from NFPA 12 0 2007, National Fife Alarm Codat), CopyrightC 2007,Nabonal Fire ProlactionAssodalion. Quincy, MA 02 160. This repyinted material is (P. a of 41 ,101 the complete and official position of the NFPA on the referenced subject, which is represented only by1he standard in its entiyary. IIIIIII -80-WOM k 0 1 Fq R.4 IIIIII'MME Jul 25 2013 10:52AM No,6582 P. 4 Integrated Security Fire Alarm In--mpt-tinn anel Tactinri Pnnnp+ 8833UEOO EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments Phone set PhoneJacks Ofl-Hook Indicator Amplifier(a) El El Tone Generator(s) Call -in Signal i System Performance AL COMBINATION SYSTEMS Firelixiln =uisherMonitorIngDavica/Systern Carbc Monox 81� /system (Specify) INTERFACE FOUIPMENT --1 Visual (Specify) 0 (Specify) 11 (specify) 0 Special Procedure; Commenw SUPERVISING STATION MONITORING AlarmSignal Alarm Restoration Trouble Signal Supervisory Signal Supervisory Restoration Device Simulated Visual Operation Operation Cl El 11 El Cl 11 11 Cl 0 Device 91mulated SPECIAL HAZARD SYSTEMS pF4,afion operation I NOTIFICATIONS THAT TESTING IS COMPLETE Building Management Monitoring Agency Building Occupants Other (Specify) The follovAng did not operate correctly (See ServiceJob)., ServicaJob#:— (specify) Yes No El El El r-1 L-i Lj yes No El 0 R-MV IV4 Device Simulated Visual Operation Operation El 1:1 El 11 El El El 1:1 1:1 Time I Co mens Time Ali. Who System restored to normal operation* Data: Time; On monitored alarm systems, I tested, 4nd it necessary. connected the telephone line sellufa feature lo ensure ilia working correctly. THISTESTINGWAS, ERF(�PMEDINAC FID ITH APPLICABLE NFPA STANDARDS. Name of Inspector: Date XV2613Time:— Signature. NamaofOwner Re esentative:a�*1�0014-';`--, jk&D Date:-L' a5l( 5- Tim.;- (L "06 Signature! [-] YesE]No R-iPrInted with permission [rum NFPA 72 V 2007, National Fire Alarm Codalk Copyright 0 2007, National Fire, Projection Association, Quincy, MA 02 190. ThIls reprinted matorialis 1p.4041) --it the complete and offiejal position of the NFPA on the referenced subject, which is represented only by the standard in ite entirety. -1 Adlh SNOHOMISH CO. i, Serving #riet; Edinonds FIRE1D Mountlake Terraceand Tthe Town of Woodway wwwFireDistrictl.org LOCATION: 21822 76th Ave W BUSINESS NAME: Sound Urological Associates MAILING 21822 76th Ave W ADDRESS: Edmonds BUSINESS OWNER: Sound Urological Assoc. EMERGENCY-1: __99d*;fTq_Rw"_ KEY ACCESS-2: Grier, Douglas FIRE PREVENTION 12425 Meridian Ave S. INSPECTION REPORT Everett, WA 98208 0 EDMONDS 0 BRIER Phone (425) 551-1200 E]WOODWAY 0 MOUNTLAKE TERRACE Fax (425) 551-1272 0 UNINCORPORATED FREQUENCY STATION & SHIFF**) 730 16 D PHONE: 42577557166 SCHEDULED DATE DUE � 11/01/12 UFIR � 593 1156 98026 HOMEPHONE: 4257757166 4257418858 HOMEPHONE: CURRENT OMEPHONE: 4257422774 YES NO CITY BUSINESS LICENSE INITIAL INSPECTION DATE PERSON CONTACTED: NAME OF INSPECTOR: FIRE FA 10/11 AS in gas room/ FE LQJL�7 SYSTEMS: " -E I �_ 014, ANNUAL HAZARDS FOUND AND LOCATIONS COMMUNICATIONS 2 2 J L-)IA 3 3 (2� cT P_ LI) 4 4 5 5 Ce 6 6 j 7 7 I AGREE TO CORRECT THE ABOVE VIOLATION(S) IN THE NEXT 30 DAYS X 1st RE -INSPECTION 2nd RE -INSPECTION EXTENSION FINAL RE -INSPECTION VIOLATIONS DATE DUE: DATE DUE. GRANTED TO: DATE DUE: CITED: PERSON PERSON� PERSON 1 CONTACTED: CONTACTED: CONTACTED: INSPECTOR: INSPECTOR: INSPECTOR: 2 DATE: DATE: DATE: 3 VIOLATIONS VIOLATIONS PRE -CITATION CITATION ISSUED 4 5 1 LETTER SENT NUMBER: CODE 5 2 6 2 6 DATE: SECTION: RETURN RECEIPT 6 3 7 7 RECEIVED DISPOSITION: 14 18 4 18 DATE: 7 I \. LETTER NEEDED [] YES NO LETTER NEEDED [] YES NO 8 FIRE DEPARTMENT COPY m7MMMM 4115 In. We �IMWGTAV if 6=1 IMNM- ,NfAN o v . 5. 2012 2: 2 1 PM -No 2377—P ow 111111161 U.0 I&" Integrated Security Fire Alarm Inspection and Testing Report 8833UEOO Date: Time: Inspection Job 0: A SERVICE ORGANIZATION ��WOPERTY NAME (USER) -�M3 1 Name:_._.. Tycq Inj��qrated Securi -ty­ Address: HrAVLAJ Address—tkw. Representative: ownerContact: License No: #t-lnk- 15XIe-w­ Telephone: Telephone: MONITORING E14TITY APPROVING AGENCY Contact; Contact: Telephone: mj —bim— Telephone: Monitoring Account Ref No (CS#): .. TYPE TRANSMISSION SERVICE F� IvIcCulloh AlatmNei Weekly F� Multiplex Telular Monthly Digital AAGad Bimonthly Reserve Priority F1 Quarterly RF E] Semiannually Other (Specify)� Annually Other lSpecify):- Control Unit Manufacturer: Circuit Styles: Model No: NumberofCirCuil$: SoftwareRev.: Last Date System Had Any Serv;cg Performed: Last Date that Any Software or Configuration Was Revised: ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Devices Circuit Style Quantity of Devices Tested Manual Fire Alarm Boxes Ion Detectors Photo Detectors Duct Detectors Heat Detectors Waterflow Switches Supervisory Switches Other (Spachfy): Alarm verification feature is: El Di9abled Enabled Reprinted with DOrMissiontrorn NFPA 72 T 2007, National Fire Alarm CodcT, Copyright 0 2007, National Fire Pr9terctionAsaociation, Quincy. NIA 021139. Thi5renrintedrnaterielis 4) -10% the complete and offiriel position of the NFPA on the referenced subject, which is represented only by the standard In its entirety. TYCID TLNov- 5. 2012 2:21PM N - 2377 P 2 Integrated Security Fire-Marm Innnentinn and Tp-qtinn Rannrt 8833UEOO ALARM NOTIFICATION APPLIANCES and CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Appliances Installed Appliances Tested Bells Horns Chimes Strobes Sneakara Other (Specify): No. of alarm notification appliance circuits: Are circuits monitored for integrity? 9 Yes F] No SUPERVISORY SIGNAL -INITIATING DEVICES and CIRCUIT INFORMATION QtV of Devices Circuit Style Qtv of Devices Oty of Devices Circuit Style QtV of Devices Installed Tested Installed Tested D JX V U ng emp. Fire PUMP/Pump Controller Trbl NalarTemp. Fire Pump Low Fuel Generator in Auto Position Fire Pump Power Generator or Controller Trouble Fire Pump Running Switch Transfer Fire Pump Auto Position Ge Generator Engine Running Other (Speclfy)� SIGNALING LINE CIRCUITS See NFPA 72 section for Protected Premises Fire Alarm Systems. Performance of Signaling Line Quantity and style of signaling line circuits connected to system.* Circuits (SLC), table for Performance of Signaling Line Circuits for Class and Style Quantity: ., Silyle($):­ SYSTEM POWER SUPPLIES (a) Primary (Main): Nominal Voltage:... WVA;r,, Amps: Overcurrem Protection: Type: _-LxU*W-- Amps: Location (of Primary Supply Panelboard): _,. At- &L R��- Disconnecting Means Locations:. 1�1 -z -iJ111-A ­. ­.. (b) Secondary (Standby): Storage Elattery:Amp-l-Ir. Rating:_ Calculated capacity in Arnp-Hrs to operate system for hours. Engine -driven generator dedicated to fire alarm system: Location of fuel storage: BATIFERY TYPE n Dry Cell [:] Nickel -Cadmium Sealed Lead -Acid [:] Lead -Acid E] Olher(Specify): (�t) Emergency or standby system used as a backup to primary Power supply, inswad of using a secondary power su pply: Emergency systern described in NFPA 70, Article 700: A Legally required standby described in NFPA 70, Article 70 1: Optional standby system described in NFPA 70, Article 702, which also monts the performance requirements of Article 700 or 70 1: Reprirtedwiih prumis5ionfrorn NFPA 72 9 2007. National Firs Alarm CodeT, Copyright 0 20()7, Notional Fire ProttrctionAssoclation, Qvincy. MA 02 1189. Thi3rVprint@drn;nCrj9Ii3 lo. Z or 41 not 'he complete and 0*41 pochion of the NPPA an the referenced svbject. which 13 represented only by the standard in Its entirety. TYCO 71. r-zk"-3=- Is Ro-worl, 1=1 IN!!= In- N LANov, 5. 2012 2 : 22PM No 2377 P 3 Integrated Security Fire Alarm Inspectean and Testina Rpnnrt 8833UEOO PRIOR TO ANY TESTING NOTIFICATIONS ARE MADE yes No Who Time Monitoring Entity Building Occupants Building Management E] 0 Other (Specify) E] R AHJ Notified of Any Impairments 1:1 R SYSTEM TESTS and INSPIECTIONS Type Visual Functional Comments ContFol Unit CA Interface Equipment % 9 Lamps/LEDs Fuses Primary Power Supply T'rouble Signals Disconnect Switches Ground -Fault Monitoring SECONDARY POWER Type Bartery Condition Visual Functional I* Comments Lead Voltage Discharge Test Charger Test Specific Gravity F7 TRANSIENT SUPPRESSORS REMOTE ANNUNCIATORS NOTIFICATION APPLIANCES Type Audible Visual Functional 1:1 Comments Visible El Speakers n VoiceClarity El INITIATING and SUPERVISORY DEVICE TESTS and INSPECTIONS Loc. & S/N X, 1i J`-- Device Typo Visual Functional Factory Sorting Measured setting Pass Fail -- -N El C1 El El El Comments: 77' Rep,;ntedwilh par-imionfrorn NFPA 72 & 2007, Notional Fire Alarm CodeQo, CopVrigh 10 2007, Notional Fire Projection Association. 01.11ncv. MAO 2 169, This reprinted material is (P. 3 of 4) not the c ornplate and official Position of the NFPA am the referenced subject. which is ropre sented only by'the standard in it., ontitely, TYCO WIM �_Mqn r1=1101 WN VA 91 Kyj 1; F. MIT. I We I�Gywvy S 5 11 9=1 IM I=- I M a] LgNov. 5. 2012 2 : 22PM N0112377— 4 Integiated SecuritV 11111 Eire Alarm luspecteon all stona Rerwrt 8833UEOO EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments Phone Set PhoneJacka Off -Hook Indicator Amplffiqr(a) 0 0 Tone Generator(s) Call -in Signal System Performance COMBINATION SYSTEMS Device Simulated Vi3u8l Operation Operation Fire E;ilngyjsher Monitoring Device/SVstem D El '�;'*Qe Carbon Mono plector/Syslem El F1 (Specify) INTERFACE EQUIPMENT Device Simulated SPECIAL HAZARD SVSTEMS Device Simularted Visual oration Operation Visual Operation Operation (specify) El (Specify) El 13 11 (Specify) (specify) El (Specify) El El (Specify) El El Cl Special Procedure: Commentv SUPERVISING STATION MONITORING Yes No Time rnments Alarm Signal rg El 14'3011� Alarm Restoration El Trouble Signal k Supervisory Signal Supervisory Re3toration 7] NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Who Building Management E] El Monitoring Agency 11 n — — — Building Occupants Other (Specify) El The following did not operate correctly (See Service Job): Service J o b#: System reSloredto normal ClPevsti0h: Dato:_ Time: - On monitored alarrin systems, I tested, and if necessary, connected the telephone line seiture feature to onaure it is working correctly. E]Yes (]No THISTESTING WAS P "UMIDINACCPDA. E ITH APPLICAI LEN FFA STAN DARDS. Date'oq_40 D12 Time: 4 Name of Inspector: ____1 Signature: 4KC Name of Owner epraseintative. C-el ate: Time: Signa Reprinted .0 Parm;33ion from NFPA 72 S) 2007, National Fire Alarm COdeT, Copyright C 2007, National Fire Protection Association, Quincy. MA02 169. This reprinted-aterial 13 4- 4 or 4) noi the complete kind official position of the NFPA on the referencrd subject. which is represented only by the standard in its, entirety. TYCO FIRE PREVENTION Servink Brier, Edmonds SNOHOMISH CO. 12425 Meridian Ave S INSPECTION REPORT J." / " d" '0 j Moun�lake Terraceand FIRE . Ev��r�tt, WA 98208 EDMONDS EI BRIER the Town of Woodway DIST T www.FireDistrictl.org Phone (425) 551-1200 Fax (425) 551-1272 OWOODWAY [I MOUNTLAKE TERRACE 0 UNINCORPORATED STATION & SHIFT-') e FREQUENCY LOCATION: 21822 76th Ave W 730 16 C BUSINESS NAME: Sound Urological'Associates PHONE: 4257757166 SCHEDULED 11/01/11 DATE DUE MAILING 21822 76th Ave W UFIR 1, 593 1'156 ADDRESS: Edmonds 98026 BUSINESS OWNER: Sound Urological Assoc. HOME PHONE: 4257757166 EMERGENCY-1: Roddy, Timothy HOME PHONE: 4257418858 CURRENT KEY ACCESS-2: Grier, Douglas HOME PHONE. 4257422774 CITY YES NO BUSINESS 1:1 E] LICENSE PERSON CONTACTED: INITIAL INSPECTION DATE NAME OF INSPECTOR: 'Vj N f- g- f _7 ^_j cl FIRE FA 10/06 AS in gas room/ FE 12-01 SYSTEMS: ANNUAL HAZARDS FOUND AND LOCATIONS COMMUNICATIONS cA r kovi e C 3 V- x ip 4. 2 2 3 3 4 4 5 5 6 6 7 7 !I AGREE TO CORRECT THE ABOVE VIOLATION(S) IN THE NEXT 30 DAYS X I st RE -INSPECTION I 2nd RE -INSPECTION EXTENSION FINAL RE -INSPECTION VIOLATIONS t ATE DUE: DATE DUE: GRANTED TO: DATE DUE: CITED: PERSON PERSON PERSON CONTACTED: CONTACTED: CONTACTED: 1 2 INSPECTO INSPECTOR: INSPECTOR: 3 DATE: DATE: DATE: V I N VIOLATIONS PRE -CITATION CITATION ISSUED 15 1 5 LETTER SENT NUMBER: 4 CODE 5 2 6 2 6 DATE: SECTION: RETURN RECEIPT 3 7 3 7 RECEIVED 6 DISPOSITION: 8 4 8 DATE: 7 D , [] YES C3 Nod LETTER NEEDED [] YES NO . 8 FIRE DEPARTMENT COPY Fie Alarm Inspection and Testing Report C?2-20 Date: 20 t I Tinio: Inspection Job#:.5n - -t SERVICE ORGANIZATION ,.PROPERTY NAME (USER) SECURITY SERVICES Name: 49 Add few Adareys5� _2ef� —A j �j Wle Rr;presentative� O�fner Contact; License No: Telephone: Telephone: =A-).- b� 149, MONITORING ENTITY Ali3OROVING AGENCY Contact: AD= Contact: r,.d ?,. Telephone: ':ZO=42a�: Telephone: .1 3M I � 1 9 MonItorIng Account Ref No (C$#): !Spu 00 Logm- TYPE TRANSMISSION E] McCulloh AlermNef multiplex Talular 018ital AAGard L] Reserve Priority 0 RF L] Other ($P(jclfy): Control Unit Manufacturer: Circuit Styles*. Number of Circuits: Software Rev.: Last Date System Had Any Scirvice Performed: Last Date that Any $ol'lware or Configuration WS5 Revised: SERVICE C] Weekly Monthly l3imonthly Quarterly Semiannually z' Annually 6ther ($pocify)� Model No: ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Oevices Installed Uevi Tested Manuel Fire Alarm Boxe6 M. Alarm verification feature is: F-1 Disabled ____L(e — Ion Detectors Photo Detectors Duct Detectors Heat Detectors Waterflow Switches Supervisory SwItchas Other(Specify): 71 Enabled Keprinted wim parmicnifin (funj NFPA 72 0 2007, N&nionfij Fled Alurryi CodoQ, CoPYAMV 2UO7. Nellonal I'll'6171018001-AfidoC10110A. 0uhley. MA 02169. Tfti�; al Ii nol IIi#,:,)p1PI6I6 411d 01001;J1 potiitlon of Illo NFPA of, the rofamnced eubjec;, wnich Is represented only by 11to standard lil Its undruty. roprintud matark (p. 11 of 4) Efts W =111di 1111IFUN—TWE?XXIIIIIIIIII 111111117.0, V re 0 r 111 F501 1-04 Fire Alarm Inspection and Testinq Report Date; Time� — (Y InapectionJobM SERVICE ORGANIZATION Name; ADT SECURITY',SERVICES Address: Representative:. S-4& License No: Telephone, PROPERTY NAME (USER) Name: Address: 2-032-2- Owner Contact Telephone: MONITORING ENTITY APPROVING AGENCY Contact: Conloct: Telephone! Telephone! Monitoring Account Ref No (CSN): TYPE TRANSMISSION McCulloh [7 AlarmNet MUKIPIOX E] Telular Digital E] AAGard C3 Reserve Priority M RIF E] Other (Specify):_ Control Unit Manufacturer. "D Circuit Styles., .. . ....... .. Number of Circuits: Software Rev,: Last Dmte System Had Any Service Performed: Last Date that Any Software Of COnfigUration Was Revised: SERVICE Weekly Monthly Bimonthly Quarterly Ej Sernlannually Z,,Annually [] Other (Specjfy):_­­,. Model No: ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Devices Installed Devices Tested . ... ....... Manuel Fire Alarm Boxes Ion Detectors Photo Detectors Duct Detectlors Heat Detectors Walcrflow Switches Supervisory Switches Other(Specify); Alarm varification feature is; F1 Disabled F-Mabled Nprintorl wIlli pornileMn fto in NFPA 72 0 2007, Nallowil rfrn Al-.%rm rnd,.4, C,;oyr1ghj 0> 2007, Nallon.dil Firn Protection A890clation. Quincy. MA 02 159. rhi, I of 4) roprimtrid rnwortni In not ll rorriplutq ano oMcIn) position ot (lie NFPA an thri rfvfr.rnncnd mittl9ri, "ICII 13 Mprn�Antqd only by thq standard In Ila enfirdly. 0 Ff re Alarm Inspection and Testing Report Date: ax 20 Time: inspection Job* SERVICE ORGANIZATION .P.ROPERT-Y NAME (USER) Name. ADT SECURITY SERVICES Name: Address: AdUrebb; -A Rc;prewtative; Owner Contact; 14 4(_�' License NO: 2*�Q"v C. Telephone: Telephone: MONITORING ENTITY A�OROVING AGENCY Contact: Contact: 'relephone: Telephone: Monitorinq Account Raf No (C$#): TYPE TRANSMISSION SERVICE n McCulloh Fj AlerrnNet C] Weekly 0 MUI(iplax CD Talular 0 Monthly Digital E] AAGard 0 Bimonthly 0 Reserve Priority El Quarterly 0 RIF Semiannually E) Other (Speolty): Annually Other (Specify). Control Unit Manufacturer: . . ......... Circuit Styles, Model No: Number of Circuits: Software Rev.: Last Date System Had Any Scirvicc, Performed: Last Date that Any Sollware or Configuration Was Revised: ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Devices Installed Devil� sted '�P' — — - --- Manuel Fire Alarm Boxes Alarm verification feature is: E] Disabled —Le — Ion Detectors Photo Detectors Duct Detectors Heat Detectors Watorflow Switches Supervisory SwItches Other(Specify): 71 Friabieci Keprinted wim pannicuifin huffl NFPA 72 0 20V, Nallonal Rea Alarm C000, Copydahl 0 2U07, Wonal Fbi, Rolealoi. Amodallon. Quhwy, MA 02169. Thi� I la n0l 1110 0111PIOW alld Uffl�ljl potiillon 011110 NFPA or, thu tofor4nced oubjeci, vvnich Is reprojentA only by th(i Slail&rd ii) III Unt1ruly. ip. I of.') roprintad rnater�j F501 1-04 Rre Alarm Inspection and TestnReport, cont. ALARM NOTIFICATION APPLIANCES and CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Appliances Installed Appliances Tested Bells Horns Chimes Strobes Sproakers Other($pKify)* No. of alarm notification appliance circuits: Are circuits monitort;d for Integrity? 15� Yes No v"__1 SUPERVISORY SIGNAL -INITIATING DEVICES and CIRCUIT INFORMATION Oty of Devicut; Circuit Style Oty of Devices Qty of Devices Circuit Style Qty of DeVIC06 Installed Tested Installed Tested Fire Pump/Pump Controller Trbl Building Temp. Site Water Temp, Fire Pump Low Fuel Water Level Generator In Auto Position S_ "a r T emp' Water Level Fire Pump r Generator or Controller Trouble .. .... Fire Pump Running Switch Transfer Fire Pump Auto Posillion Generator Engine Running Othar (Specify); See NFPA 72 section for Protectod Premises arm Systems, Performance of Signaling SIGNALING LINE CIRCUITS �s - �_l Line Circuits (SLC). table for Performance of SignaliMI-ine Circuits for Class and Style Quantity and 6tyle ol'5ignaling line circuits connected to system,. Quantity; Style(s): SYSTEM POWER SUPPLIES (a) Primary (Main): Nominal Voltage- Amps: Overcurreilt Protoctlon: Type; Amps., Location (of Primary Supply Panalboard): T, -)Vl DisconnectIng Means Locations! (b) Siiiconclary (Standby): 12t/Ac, Storage Oa(tery; Amp-Hr, Rating: _IX-111 Calculated capacity In __ Amp-Hirs to operate system for hours Engine-drivon generator dedicalod to fire alarm systern: Location of fuel storage: BATTERY TYPE 0 Dry Coll [:] Nickal-Cadmium Scaled Lead -Add Lead -Acid Other (Specify): (c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply: Emergency systGm described in NFPA 70, Article 700: Legally required standby described in NFPA 70, Article 7U I.* 2: Optional standby system described in NFPA 70. Artich; 702. which also meets the performance raqulrornent6 of Article 700 or 701: R4printudwito pormlasloii (turf, NFPA 7202U07, lll.flan4l FlroAiulm CockW. Copyjl9I1lltQ2G07.l%1luiia1 Fira NotoctIon A�zncizflon. QuIncy, MA02100. Thi� wpdul-d aijuirial is ool the cumpl-ituand official p0811101% of the NFPA 01) 1110 iulorcricold gubject, whl�lj 14 l'ot)nz:jutdtjd only by the olandard in Its eilftly. (ij. 2 of 41 ell ­ .— �.0 F6011-04 Fire Alarm Inspection and Testinq Report Date; Time: Inspoction Job#: SERVICE ORGANIZATION PROPERTY NAME (USER) Name: ADT SECURITY SERVICES Name: 74n�� MA� �ek- QLA-A Addtass: jR L Address: AA 0 —� —t. X,? --- - i Representative: �jj Owner Contact: L Telephone: _­.. 71— 5 lltai(4 .425 1-,- Telephone, Lam -05�� MONITORING ENTITY APPROVING AGENCY Contact! Contact: FAMA!5nd-C, - t , b. Telephone; Telephone;_...,- 911 Monitoring Account Ref No (CS#); TYPE TRANSMISSION SERVICE C] McCulloh AlarmNat Weekly multiplex Telular monthly Digital E] AAGard Bimonthly n Reserve Priority C3 Quarterly 0 RF C] Semiannually E] Other (Specify): Annually Other (Specify); Centrol Unit Manufacturer! . .... . T� . ...... circuit Styles: _—. k1b Model No: Number of Circuits; Software Rev.: Last Date System Had Any Service Performed' Last Date that Any Software or Configuration Was Ravlood: ALARM -INITIATING DEVICES AND CIRCUIT INFORMATION Quantity of Circuit Style Quantity of Devicer, Installed Devices Tested Manual Fire Alarm Boxes Ion Detectors Photo Detectors Duct Detectoriii Heat Detectors Waterflow Switches Supervisory Switches Other(Specify): Alarm verification feature Is: 0 Disabled Enabled Koprintud with parmiobion from NFPA 72 0 20011, Naliabbl Fire Alorm Cfid,11U. copyright 0 2007. NjIloribi Flia ProtorAiutl Assocl ition, ou5icy, MA 02169 . Thh� (p. I of 4) rupriuWa material is not thu Coff-Plate and official peidillon of IN N17PA on Ing Forural red Ubiciv, whiel:4 is roorvzoplud only by thu dtaildwd in Ili wthety. CUSTOMER FILE 01-- 000001HI. M-1 - III - - . ��=K=ar-ym- 31-10 F601-04 Fire Alarm Inspection and Testinq Report, cont. ALARM NOTIFICATION APPLIANCES and CIRCUIT INFORMATION Quantity of Circuit ftle Quantity of Appliances Installed Appliances Tested 13011S Homs Chimes Strobes Speakers Other(Specily): No, of alarm notification appliance circuits: �11- Ara circuits monitored for integrity? KYes No SUPERVISORY SIGNAL -INITIATING DEVICES and CIRCUIT INFORMATION Qty of Devices Circuit Style Qty of Devices Oty of Devices Circuit Style Oty of Devices Installed Tested Intitalled Tested Building Temp. Fire Pump/PUMP Controller Trbl Site Water Temp. Fire Pump Low Fuel Site Water Level Generator In Auto Position Fire Power Generator or Controller Trouble Fire Pump Running Switch Transfer Fire Pump Auto Position Generator Engine Running Other (Specify); See NFPA 72 section to( Protected Premises Fire Alarm Systems. Performance of Signaling SIGNALING LINE CIRCUITS Lino Circuits (SLC), table for Performance of Signaling Line Circuits for Class and Style Cluantity and style of signaling line circuits connected to system. - Quantity; Slyle(s): SYSTEM POWER SUPPLIES (a) Primary (Main): Nominel Voltage: 12nukc, Amps; Overcurrent Protection, Type: by-eAmUAe, Amps, Location (of Primary Supply Painelboard): 423 Disconnecting Means Locations: .. cia * !R (b) Secondary (Standby); Q Me, x ��. Storage Battery: Amp-Hr. Rating: Calculated capacity In _ Amp-Hrs to operate system for 24 hours Engine-drIven generator dedicated to f1ria alarm system: Location of fuel storage' ...... BATTERY TYPE C] Dry Cell Ej Nickel-Cadmluin Sealed Lead -Acid C] Lead-ACid [3 Other (Specify): (c) Emergency or standby sy5tern used as a backup to primary power supply, instead ofuuing a soconclary power supply: 9 Emergency system described in NFPA 70. Article TOO: 9 Legally required standby described in NFPA VO, Article 701: 15( Optional standby system described In NFPA 70, Article 702. which also meets the Performance requirements of Article 700 or 701: r<oprintod wiji, pajjj)jsWC�A 11orn N�!PA 72 0 2007. NetlonvJ Fim Mimi codow. Copyriglit 0 207. Nationai Fit%, Protection k�wLij0011, Quincy, MA D216�. Thit; NIqlAl.womprial in nnl Ihm crvttirlPla and official uositlon of the NFPA on the refufurtwd g0ject, which ib; iulimsorlied only by 010 stancland In 116 entliety. (p. 2 of 4) in o4'rr-mr-P Fit I - Wall IN= 0.11111111 F6D1 1-04 .Fire Alarm Inspection and Testing Report, cont. PRIOR TO ANY TESTING NOTIFICATIONS ARE MADE Yes No Who Time Monitoring Entity 4 0 Avr—,.- Building Occupants El Building Management El 1:1 Other (Specify) AHJ Notified of Any Impairments SYSTEM TESTS and INSPECTIONS Type Visual Functional Comments Control Unit IX interface Equipment ZL Lamps/LEDs 13 El Fuses 11 Primary Power Supply Trouble Signals Disconnect Switches 0 Ground -Fault Monitoring SECONDARY POWER Type Visual Functional Comments Battery Condition Lead Voltage Discharge Test Charger Test Specific Gravity M TRANSIENT SUPPRESSORS C3 REMOTE ANNUNCIATORS NOTIFICATION APPLIANCES Type Visual Functional Comments Audible visible speakers Voice Clarity INITIATING and SUPERVISORY DEVICE TESTS and INSPECTIONS Loc. & SIN Device Type Vllsual Functional Factory Setting Measured Setting Pass Fail Iowa —<,Ml/ &t— q Ig El bid'i IN06t &t— '0 Cl 1 0 CK 0 El CommeAM ""7 Reprhitallwith parml—la.i I(OMNFPA 72020DI. Nation;1I Rra Alarm CGOL4W, Copyright 0 2007, NadonsiFiroPrt)tecOonAutweiation, Quincy, MA02189. TM6 (P. 3 ot 4) talviniwri maietlai is not tho complete end olficial position of Pis NFPA a n Ole roferoncod �wbjbct, which i;; 1,iprallenjod cxiiy oy tho tit; d&O In it* brd1,btY- rm r FSDII-04 isFire Alarm Inspection and Testing Report. cont. EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments Phone Set 0 El Phone Jacks P( Off -Hook Indicator C1 Amplifier(s) 0 Tone Gonerator(3) 0 Call -In Signal 19 system Performance K Device Simulated COMBINATION SYSTEMS visual operation Operation I Fire Extinguisher Mon�kori vice/Systern El Carbon Monoxide DatectorlSyste 0 (specify) 0 D 0 INTERFACE EQUIPMENT vice Simulated SPECIAL HAZARD SYSTEMS Device Simulated Visual Oper n Operation Visual Operation Operation (Specify) 11 0 (Specify) ID 11 (specify) 0 11 (specify) 11 C1 (specify) 0 Specify) Special Procedure; Comments: SUPERVISING STATION MONITORING yes No, Time Comments E] 0 �_' Alarm Signal Alarm Restoration Trouble Signal 0 Supervisory Signal Supervisory R06toration F1 NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Who 0 Cl Building Management Monitoring AgOnCy Ix C1 Building Occupant$ El Other(Spacity) E] 0 The following did not operate correctly (SeS Service Job); System restored to normal operatiow Daw Time:.. Service Job#: on monitar0d alarm systoms. I tested. and If nOcOssarY. connectod the telephone line %uUuro featuru to ensuro it is working correctly, []Yes [:]No THIS TESTING WAS PERF0 ",M IN ACCORDVaITH APPLICA13LE NFPA STANDARDS. Time; Name of Insoector. Date: Signature! Date; Ti,,: e n tive: Name of Owner or Signature: 1b. Corjvflahl 0 2007, NatiOnal Flm P(oteation Aajoelg6on, ouIncy, MA 02169, Thlu =1� Al-.. r.ndAL (D. A W 4) —, , .. '- - - - - - _- - . 6 Wo a 11 1- ,prigod mgtoriji IS lot the compittI, end olikiiiI p0tbn ()f Iho NFPA on tho raf&rwcod wbjuct, whlch 6 fdw son r y uy tu rIAS'1 OMER FILE Wesffall, John From: Turner, Amy Sent: Wednesday, January 12, 2005 1:15 PM To: Westfall, John Subject: Medical facility would like in-service training John: We were prefiring the facility at Sound Urological Associates WERE =Bt QN. A couple of the staff members M-) including the administrator, Hope Dumais (425-670-8950), asked wketh-e—r sofnewn—e from the department would come to their facility to provide "emergency situation" training to the staff, "for instance, if a car drove off 76th and into the side of the building." I told her I would try to find out if we had anyone who did that type of thing. Could you follow up with Hope? Thanks. Amy VS I.-- A-l"I TV+, A-45 Te �C, U ,�-, Wesffall, John From: Westfall, John Sent: Tuesday, March 08, 2005 4:43 PM To: 'hdumais@soundurology.com' Subject: Emergency Guide by the Numbers Hope: 1) Sculpt away everything that doesn't belong or apply to the Life Safety Plan. You'll be left with a fire safety guide for your building. 2) When complete, give me a call and the 3 of us can cover some basic emergency procedures for you to write down. 3) When the Guide & procedures are complete, we can have inservice for your staff. 4) How's that? Don't be insulted -I've been reducing all my efforts to step-by-step procedures. John 425.771.0213 r _7N Jm lifesafetyplan.doc (259 KB) STA 0 188 STATE OF WASHINGTON DEPARTMENT OF HEALTH DIVISION OF RADIATION PROTECTION I APR 10 2003 OFFICE OF THE MAYOR 7171 Cleanwater Lane, Bldg. 5 o P.O. Box 47827 * Olympia, Washington 98504-7827 TDD Relay 1-800-833-6388 April 7, 2003 The Honorable Gary Haakenson Mayor of City of Edmonds 1215 th Avenue North, Third Floor Edmonds, Washington 98020 Dear Mayor Haakenson: The Department of Health, Division of Radiation Protection is required by law (RCW 70.98.080.(2)) to notify the'appropriate local government officials whenever a radioactive materials license application is received. Specifically, the Division must notify either: the Chief Executive Officer, if the applicant is located in a city; or the county legislative authority, if located in the county. This is your, official notification of the specific use and possession of radioactive material as described in paragraph four below. We urge that you forward a copy to the appropriate fire department for their review. The Division of Radiation Protection will delay the issuance of a license at least 20 days from the date of this notice. During this time period, if you deem appropriate, you may file written object -Ions against the applicant or the activity for which the license is sought. The law states that all written objections shall include a statement of facts upon which such objections are based. Upon filing written objections you may request, and the Division of Radiation Protection may at its discretion, hold a formal hearing concerning the applicant or activity. On April 4, 2003, Sound Urological Associates, P.S. submitted an-appiicat on requesting to be th licensed to receive and use radioactive materials A 21822 76 Avenue West', Edmonds, Washington. The applicant states that the radioactive materials will be used for interstitial treatment of cancer. 0 -Z.J� 18 a 0 Page Two The Honorable Gary Haakenson April 7, 2003 If you have comments, they should be submitted to this office by April 28, 2003. Please submit comments to: RADIOACTIVE MATERIALS SECTION DOH DIV OF RADIATION PROTECTION 7171 CLEANWATER LANE BLDG 5 PO BOX 47827 OLYMPIA, WA 98504-7827 If you have further questions regarding this notice or the application (cover page enclosed) described herein, please feel free to contact this office at 360-236-3220. Sincerely, Dorrie B. Dodson, 7Sfe-cretary Radioactive Materials Section Enclosure cc: Bob Pekich Snohomish Health District 0 RECEIVED APR 0 4 2003 61, APPLICATION FOR RADIOACTIVE MATERIALS SECTIOP Radiation Frotecton Division RADIOACTIVE MATERIAL LICENSE MEDICAL INSTRUCTIONS — complete ail items in this application to apply for a new license or the renewal of an e),Jsting lirense. Use supplemental sheets where necessary. Item 31 must be completed on all applicabons. Mail to: Washington State Deparb-nent of Health, Division of Radiation Protection, P 0 Box 47827. Olympia, Washington 98504-7827 Upon approval of this applic�ation. the applicant will r&.,,eiv& a State of Washington Radioactive Matenal License issued in accordan,-,e with the general requirements contained in Washrigton State Department of Health, Radiabon Protection Regulations, and the Washinglion Energy and Radiation Control Act. Chapter 70.�8 RCW Ia NAME AND MAILING ADDRESS OF APPLICANT Iffistilution. Firm, Clinic. Phvisician. etc.) INCLUDE ZIP CODE Sound Urological Associates, P.S. 2182276 111 Avenue W. Edmonds, WA 98026 Khai Lai Ib. STREET ADDRESS(ES) AT WHICH RADIOACTIVE MATERIAL WILL BE USED 6fdifferent than Ia.) INCLUDE ZIP CODE. Sound Urological Associates, P.S. 2182276 111 Avenue W. Edmonds, WA 98026 N1161mmilyX 3, THIS ISAN APPLICATION FOR: �Check appropriate iterro A 14 NEW LICENSE B. C3 AMENDMENT TO LICENSE NO- WN-M ...... C. 0 RENEWAL -OF LICENSE NO. ­32�m ....... 4. INDIVIDUAL USERS Of more than one individual will be named, corMlele 5. RADIATION SAFETY OFFICER (RSD) Authorized Use- Form.) I (Narrie of person designated as Radiji'*n Safety Officer.) See List 6a, RADIOACTIVE MATERIAL FOR MEDICAL USE Radioactme Materials as defined in, WAC 246-2' .5,120 Schedule A ITE PAS DESIRED MARK �111 K4A>IPAUPA POSSESSION LIMITS (in Curies Group I As Needed Group 11 As Needed Group III Group IV As Neede�d Group V As Needed Group Vi As W&Jed XENON — 133 asgasorgas in soine ror bt�.,d flow studies and pulmonary function studies TECHNETIUPA�9m—AEROSOL As Needed Khai Lai ITEMS MAXIMUM Particular procedure desired where DESIRED POSSESSION Groups IV andfor V are NOT checked, MAPK LIPATS X (in curies) IODINE — 131 AS IODIDE FORTREATMENT OF HYPERTHYROOISM PHOSPHORUS— 32AS SOLUBLE PHOSPHATE FORTPEATMENTOF POLY CY THE PAAVEPA, LEUKEMIAAND BONE METASTASES PHOSPHORUS —32AS COLLOIDAL CHROMIC PHOSPHATE FORINTRACAVITAW TREATMENT OFMALIGNANTEFRiSIONS. IODINE —131 ASIODINE FORTREATMENT OF THYRODCARCINOMA STF;tOP4TIUPA— �9AS'OHLMDEFORTREATMENT OFPAINFP.t-*AC,4N(;EP.METAS'TASES 6b. RADIOACTIVE MATERIAL FOR USES NOT LISTED IN ITEM 6a. (Sealed Sources up N; 3 Ind. used for caliotatic4, and feter&nce staroarcs are aultoraed under WAC 246-235- 080 (3) (C) and up to 22 mci for Colialt-57 used for calibration and reference standards NEED P40T BE LISTED.) ELEMENT AND MASS NUMBER CHEMICAL AND/OR PHYSICAL FORM MkXMUM?1AABER OFMLLICLF4ES0R Bfic�� DESCRIBE PURPOSE OF USE Palladium-103 Solid As Needed Interstitial treatment of (sealed) cancer DOH322-W6 (Rev 196) * LICENSE FEE F�EOLqF�ED(-�,)troetetten)*,9,) P02P 1 RHF - I ?A '10am-e— FL-4t--, -71 CITY OF EDMONDS 121 5TH AVENUE NORTH * EDMONDS, WA 98020 - (425) 771-0215 - FAX (425) 775-7721 FIRE DEPARTMENT www.edmondsfire.org .,I? '. 1 S 9 13 Ms. Hope Dumais Administrator Sound Urological Associates 2182276 th Ave W Edmonds, WA 98026 Re: Proposed Fire Alarm Modifications Dear Ms. Dumais: August 11, 2003 GARY HAAKENSON MAYOR The Fire Department approves the proposed changes (below) to the existing fire alarm th system at Sound Urological Associate=WWNWRE:�� 1. Relocate manual pull station at north end of hallway to new location below alarm keypad and light switch. Manual fire alarm shall be no higher than 54", nor lower than 36", in accordance with WAC 51-30-1106.15. 2. Relocate horn -strobe in recovery room at south wall to the recovery room west wall, left of the door. Horn -strobe shall be located not less than 80" above floor level, or 6" below the ceiling, whichever is lower, in accordance with WAC 51- 1106.15. No permit will be required for these modifications. Please contact my office at (425) 771-0213 for a verification inspection when your work is complete. No other fire alarm modifications are authorized. I recommend that you make contact with the State agency that holds authority over your Outpatient Surgical Room status to seek their approval for your proposal prior to making those changes. Sincerel John J. W Fi re Mars� Cc: Mr. Jantzen Ramento, ADT, 841 Powell Ave SW #101, Renton, WA 98055 Ce 1( 9 U� -7 30 - 2-66.5'_ 10 Incorporated August 11, 1890 * Westfall, John From: Westfall, John Sent: Wednesday, April 23, 2003 12:34 PM To: Battalion Chiefs Cc: Smith, Mike; Tomberg, Thomas; Martin, Jpmeg--,--- T Subject: Radiological Elements at Sound Urologick L21822 76th Av;e) The State Dept of Health has notified the City that they have made application to use and store lodine-1 25 and Palladium- 103, radiological elements used in the treatment of prostate cancer. Mr. Khai Lai (206) 713-2022 is the Shoreline consultant who helps to develop patient pre -operative plans when the radiological treatment is prescribed. The individual Rx remains no longer than 2 days. Each Rx is packed, delivered, and stored on -site in a lead -lined container. The radiation "seeds" are inserted into the prostate during an operative procedure. Any leftover elements are repackaged and sent back to manufacturer. Fire Prevention will be obtaining a permit from Sound Urological for the use/storage of the elements. The exempt amount for radioactive elements in lined storage is 1 millicurie. Each patient is estimated to require 100 seeds, approximately 100 millicurie. The frequency of procedure is estimated at two persons every other other Wednesday. Mr. Lai has offered to provide awareness, hazards, or procedural training regarding the elements in our jurisdiction. Please coordinate with each other and FF Martin if you are interested. FM MEMORANDUM DATE 10 It 6-/ qq REPORTED BY OF SUBJECT ADDRESS: CONCERNSI HAZARDS: FoLLow-up: SIGNED 4"OT 7- 06 36 (� - get? 0 F:7�' 7.6-& 37,5--0777 I.D. CLA--->,c CA-L i- FVIP,- A) &V A) cagz, 40,?-5; A at N—le,4� F,ee A4 C q-,,f-rf-tx- - F-J-1-t-37 41- E-x-'T-5 ' / 35;, C&�4.&M-0 Gits Srv"z,<- (94TE-c-.-- X454e V 15- 't-t- 0 AJ L, AM JIJ 5--Altr-F. --j sp-prc"Z;5� 4..v 17-H hL6..,+I--- C(,J� (IN C hZ&A--e, /,j co-k-A,40�p— 14(tA sl-t IN 5�-A&6x-,,f SIGNED -7) City of Edmonds * Office of Fire Prevention I /V leCA,^4 -AAC,� OCT-18-99 03:27 PM COMMUNIQUE 05;40P CARLETTI ARC:+jjTEC-r:S 2063250737 p .05 300 424 5726 P.02 Ion T�l 4L tl v Jr. m 'Jul-14-99 09:33A CARLETTI ARCHITECTS 360 424 5726 P.01 CARLETTI ARCHITECTS, PS. architecture & planning FACSIMILE TRANSMITTALSHEET TO: FROM: Mike Smith Peter Carletti COMPANY: DATE: City of Edmonds Fire Department 07/14/99 FAX NUMBER: PHONE NUMBER: RE: NUMBER OF PAGES INCLUDING COVER SHEET: Sound Urological Associates 98-162 76'h Ave West Fire Sprink[er at Medical Ga es Roorn Q UKGJ;N1 0 FOR RE-VIEM 0 PLEASE COMMENT 0 PLEASE REPLY C1 FOR YOUR USE NOTES/COMMENTS: Mike: The following is to Confirm our telephone discussion of the sprinkler head requirement for the medical gases room. In discussions you have lield with Public Works they have agreed to allow a side wall head within the medical gases room, The head must be fed by a minimum of a 1/4" copper line, The Y." line must be a loop directly off of the main supply that comes into the building. It cannot be reduced in size and must maintain -ys" size up to the head. In addition, you stated that you want to inspect the line to the head prior to final cover. Unless I hear from you otherwise I assume that all issues have been resolved and you and or Mr. Westfall can sign off on the permit. Thanks for all your efforts and help on this issue Peter Carletti Carletti Architects, P.S Cc: Bob Wilcox, Wilcox Construction Tom Cherpeski, Nardone Mechanical Tom Harrylock, HV Engineering C,arletti Arckicclv. P.S. 2204 RiverUde Drive, Sude 270 Mount Vernwi, WA 98273 (360) 424 - 0394 F,4X(360) 424 - S726 (�ARLETTI ARCHITECTS, P.-S. architecture & planning July,12,.1999 o6 John Westfall,Fire Marshall City of Edmonds Office of Fiie Marshall 121 Fifth Avenue North 'Edmonds, WA 98020 RE: Plan Check #98-162 Sound Urologic�l 2 21826 — 76"' Avenue West Dear. Mr. Westfall: The. following is in response to your Correction Checklist, dated July 9, 1999, for the above referenced �roj ect. Listed below are our itemized responses. Please refer to Sheet C-4 of the Civil Drawings, Which show a new fire hydrant installed on theeast side 1h df.76 AvenueWest -This., is per the, agreement reached in the Pre -Application meeting of February 12, 1999. I em,2 Please sheet S�eet C-4, which has been reviewed by engineering, that shows the installation and details th for anew firehydrant to be installed on the east side bf 16 Ave mie West, per Public Works and Engineering specifications. Item 3 There Is ric full fire s ri.--kler system for th6 project. We are installin,2 one head within the medical I .:.p gasses room, Room #148. Per discussions I have held with Mike Smith, of your department, and with Jim Wait of Public Works, we areagreeing to tap off the existing domestic system and have a Wet head Jocated within this room. The only requirement for public.works wili be for a reduced -pressure back - flow preventer off of the main in to the building. W,xj, e.will be providing a deferred submittal for the voluntary manual and automatic fire alarm'system, permit. We will include in that submittal three copies of plans, battery calculations, and specifications of all, 0 uipment for review. . t, q We. agree to provide heat detection in the one -hour interior room, in lieu of a watei full alarm to alert the building occupants, for the'sprinkler head that is being installed in Room # 148. S:\Arch\98\Documents\1'62\FireMarshalI 07-12-99.doc 2204 Riverside Drive, Suite�;270 Mount Vernon, WA 98273 (3 6 0) 4 2 4 - 0 3 9 4 FAX (360) 424-5726 John Westfall, Fire Marshall City §f Edmonds Office of the Fire Marshall Plan Check #98-162 Sound Urological 21826 — 76th Avenue West July, 12, 1999 m 6 e 4gree that the fire alai-m design and installation shall be per LTFC, 1007.2.12. 10, UFC 1007.3, and LJFC standards 10-2 and,1.0-3. 1jefn 7 /We agree that ihe medical gas installers shall be certified and/or licen�ed to perform medical gas installation. In addition, -as a requirement of the Building Department, the medical gas installation is going tdrequire special inspection by a WABO Certified, inspector tocertify that the medical gasses are installed per Code. rhave a total -of one.tank of nitious with -one back-up-and-tNNo-t-anl,�,s-of-oxygen w1th�tvo­back-up-tdn_ks to -be stored in Room #148. Ittpo I— Xeagree to provide mechanical exhaust at a rate of one cubi c foot per minute per square foot of the room. In addition, we will provide make-up air from -the exterior, per the Mechanical Code and UFC 7404.2.13' /We are going to be providing a deferred, sub�mittal for the specification.s on the emergency generator -equipment, including fuel type and tank capacity. Our sub -contractors, Nardohe Mechanical and Ewing,' Electric, are. putting together'this submittal and will be providing, it to your department for your review and approval prior to installation. Ijr.ust that these answers are, satisfactory in answering any of your comments or. questions. I appreciate your as sistance in reviewing this permit package. We will be submitting deferred submittals for the fire alarm and for the generator in the future. If you have any further questions, please don't hesitate to call: Carl6tti cc: Bob Wilcox, Wilcox Construction Tim Roddy, Owner Lara Knaack, City of Edmonds S:\Arch\98\Do6uments\162\Fire Marshall'07-12-99.doc MEMORANDUM Date: July 9, 1999 To: Building Department From: John Westfall, Fire M hal ,q_yjr� C,A,t,%_ CA44,6-rT-( C.�fc� 1T6:"-1_5 Subject: ' Plan Check #98-162: Sound Urological 21826 76 th Ave W The Fire Department has the following comments: 1 . Fire -flow calculations and distances indicate that an additional hydrant will be required for fire protection needs. 97 UFC Appendix 111-A & -13 2. Provide fire hydrant at frontage per Public Works and Engineering specifications. 19.75.140 ECDC 3. Provide submittal for fire sprinkler system installation permit. Provide three copies of plans, hydraulic calculations and specifications for pipe, sprinklers, hangers, and system appurtenances for review. Contact Mike Smith (425) 775-7720, for information regarding multi -purpose water supply and pipe* routing for sprinkler service. 97 UFC 1001.3 4. Provide submittal for (voluntary) manual and automatic fire alarm. system installation permit. Include three copies of plans, battery calculations and specifications of all equipment for review. 97 UFC 1001.3 5. Provide heat detection in one -hour interior room in lieu of waterflow alarm to alert building occupants if looped multipurpose system is approved by Water Dept. 6. Fire alarm design and installation shall be per UFC 1007.2.12.10 (WAC 51-44 UFC), UFC 1007.3 and UFC Standards 10-2 & 10-3. 7. Medical gas installer shall be certified and/or licensed to perform medical gas installation. Provide type and amount of medical gas to be stored in one -hour interior room. 9� UFC Table 105-A, Article 80 9. One -hour interior room shall be exhausted mechanically to the exterior at a min. rate of 1 cubic foot per minute per square foot of the room. Makeup air from the exterior shall be provided per Mechanical Code. 97 UFC 7404.2.1.3 lo. Provide specifications for emergency generator equipment including fuel type and tank and capacity. Cc: Carletti Architects 360.424.5726 City of Edmonds :5b Office of Fire Marshal _�l q7A 0 314 TV Jun-29-99 08:59A CARLETTI ARCHITECTS 360 424 5726 P.01 CARLETTI ARCHITECTS, PS. architecture & p�anning FA CSIMIL E TRA NSMITTA L SHEE T TO: FROM: Mike Smith Peter Carletti COMPANY; DATE: City of Edmonds Fire Department 06128/99 FAX NUMBER: PHONE NUMBER: RE: NUMBER OF PAGES INCLUDING COVER SHEET: Sound Urological Associates 1 98-162 76'h Ave West Fire Alarm oURGIN'l n FOR RINIEW oPLEASE(UMMENT 0 PLEASE REPLY 0 FOR YOUR USE NOTES/COMNIFINTS Mr. Smith: This is to confirm our phone conversation this morning regarding the above referenced project. Per the UBC and UFC for a B occupancy a fire alarm system is not required. However, per Medicare standards it is required to be installed in the surgery suite. You stated that if we begin an installation of a fire alarrn system you want the system installed throughout the building. You want pull stations at all the exits and horns and strobes. We also discussed the medical gases room. Per the UBC it is required to be sprinkled and mechanically ventilated. You stated you would allow us to tap off of the domestic system for the bead. This head would then have to be ties into the fire alarm system with a flow device. You also said you would accept a reduced pressure backflow device for the head. However, you cautioned rne to contact the water department and verify that they would not require a double check valve detector for the bead. We are proceeding with this information please call me if any of it is incorrect. C, Cc: Bob Wilcox, Wilcox Construction . Michael Case, Engineered Electrical Systems Peter Cartetti Carletti Architects, P.S. (.'adelriArcbilecls. fl.,5. 2204 Riverside Drive, Suke 270 Mount Vernon. WA 98273 (360) 424 — 0394 1-.4X (360) 424 - 5726 MEMORANDUM V Date: July 9, 1999 To: Building Department From: John Westfall, Fire Marshal Subject: Plan Check #98-162: Sound Urological 21826 76 1h Ave W The Fire Department has the following comments: 1 . Fire -flow calculations and distances indicate that an additional hydrant will be required for fire protection needs. 97 UFC Appendix 111-A & -13 2. Provide fire hydrant at frontage per Public Works and Engineering specifications. 19.75.140 ECDC 3. Provide submittal for fire sprinkler system installation permit. Provide three copies of plans, hydraulic calculations and specifications for pipe, sprinklers, hangers, and system appurtenances for review. Contact Mike Smith (425) 775-7720, for information regarding multi -purpose water supply and pipe routing for sprinkler service. 97 UFC 1001.3 4. Provide submittal for (voluntary) manual and automatic fire alarm system installation permit. Include three copies of plans, battery calculations and specifications of all equipment for review. 97 UFC 1001.3 5. Provide heat detection in one -hour interior room in lieu of waterflow alarm to alert building occupants if looped multipurpose system is approved by Water Dept. 6. Fire alarm design and installation shall be per UFC 1007.2.12.10 (WAC 51-44 UFC), UFC 1007.3 and UFC Standards 10-2 & 10-3. 7. Medical gas installer shall be certified and/or licensed to perform medical gas installation. 8. Provide type and amount of medical gas to be stored in one -hour interior room. 97 UFC Table 105-A, Article 80 9. One -hour interior room shall be exhausted mechanically to the exterior at a min. rate of 1 cubic foot per minute per square foot of the room. Makeup air from the exterior shall be provided per Mechanical Code. 97 UFC 7404.2.1.3 lo. Provide specifications for emergency generator equipment including fuel type and tank and capacity. Cc: Carletti Architects 360.424.5726 City of Edmonds Sb Office of Fire Marshal 2�087Z 7GTt,�_ I+V'C,,-) W6-�-�L Z10/91 Fire -Flow (UFC Appendix 111-A) Building type: V- a Fire a'rea: square feet 4-hour area separation wall? Type I or Type 11-FR Construction? Fire -flow is gpm for ',7 hours. Modifications: Increase or Decrease? R3 dwelling reduced %for auto sprinkler? (min. 1000 gpm) All other use reduced % for auto sprinkler? (min. 1500 gpm) Total fire -flow: —7 gpm for Z_ hours. Fire Hydrant Locations and Distribution (UFC Appendix III -a) 5bo (10 /1, Min. # of hydrants: Ave. spacing: Max distance to frontage: 7_5Z) Dead-end road? Highway dividerlobstructions? ec-o C_ 1900 Residentially zoned area?: Existing hydrant distance to frontage North 7--')0— feet. South 4-feet. East feet. West feet. # of hydrants required and text location(s) Mg*W OA/,!�_ - cc /41 F�6!5� ,14 Ldc Q-0,444 T 6,<, 'e,", 'T DA river !a 003 to 10 200 2001 026 J, 001 it FIL 4 21019 ZJ016 Joe 0 0 wo W PIS to Ise !1% I's a 210 1 to 21 10016 2J021 FA 2 21035 2/024 1 8 Ate OZ3 WISJOYMA'd I Irz 13 IOU I V026 21104 11103, 1114 nos 21110 of U10 IND 21 10 '2 is 2jit? all SEVEN 1 17 it/2 1 L21 If rifts 2 tot P. 107 21,21 4D MAD so jaw, C To ZMAMP g T ZI . . . . . . . . . . . �-v &W.5%, MOW OD now 21214 Z1219 0 WIRE 7630 z ?J221 2J214 21903 21 11313 % A ty ID I CD ).T 411S. 229 Z W T. W. tWU66411 WWO 13 21405 Sit = 0 . I I V G! MS7 AON 14 on kn Co. 2131 AOYAL 21117 &a.pww 49 cod vok" TZA"tj PL. 2J40* WIT VILLA 216ow two$ DvAwA Q i� 74 ZJ417 U 2)409 21429 ST S. 107B IDPOIS 10 "low 2.1501 WILO FO B] III so to 44 ao OD 40 Ah I ..� ST ST. W7 2j&07 Zj"G 1,0 rms,. 21603 D E] 604 0% srlvf�i' - -7:'- 2166 2j6)4 1 1 11642 1-111.14"m (PI& 6,15 412 ;. W 2= 32)12 2*16 N 21 21 &JAVAIS I rAs 2J701 CHASE 1,29 )(0.30 6129 2162 OL L.A E 21744 " % Z705 Sr 70S Z1701 trios uhn HOOL. 2.17071 e P 4 11711 21709 718 81101 721 Z�F720 2 rYZ7 21M pu Fi Ito ?27 It I M a 7M mer z 21008 21809 W13 SO za 21007 1�8 1-6 21817 It 11WI; 11617 13 09 21811 LIS13 veto 118JIF 803c IS'S — 4 1 % 215t4 21430jg 21831 t4 '4 2JO W11 I a I I 1 21111 828 21 1� 21905 ago ;90 2)9 TA ST. i A&I." I 21919 it 21911, 2"27 194 V927 IM 200MMMS W-220mmme" 0- V it 91) ft P. 2,v., 01, 018 % oD eds 202T tz 01 "f 02 AVRORA 009 31 22OU 2022 to 0 Z2023 #2 CID 28 020 ?103 0— ED Af tp COMMERCIAL & MULTI -FAMILY WORKSHEET PROJECT INFORMATION PROJECT ADDRESS. E9>2_(" 704- "LAN CHECK# -I OWNER/APPLICANT PROJECT ARCMTECt/DESIGNER, M, PROJECT STRUCTURAL ENGINEE PROJECT GEOTECHMCAL, ENGINEE U> RELATED PERAffTS/APPLICATIONS BUELDING LIMITATIONS TYPE OF CONSTRUCTION_Yfi CCUPANCY(IES) V�L_O Floor Occupancy Floor Occunant V.-vife TOTAL ALLOWABLE AREA (TABLE 5-B)-,,- 11F mr) ALLOWABLE HEIGHT/STO OCCUPANT LOAD CALCULATIONS OCCUPANCY SEPARATIONS 7D 011-5 P5 14055 7*4tV 31?, co f . -ev :7-00 on 94r IP ,jun - e!i - !:st:* xx-� ersiA - utAmL-r- i i -L -mmL-t-1 jL 1 r— 1 - -'� %J %J -* C- -P ;.a I C- W-j � � A^ r 'V t'(VjeQ RIeEC E IV ED CARLETTI ARCHITECTS, RS. JUN 2 9 "S.'" architecture & planning DEVELOPMENT SERVICES CTR CITY OF EDMONDS FACSIMILE TRANSMITTAL SHEET TO: FROM: Jeanine Graf Peter Carletti COMPANY: DATE: City of Edmonds June 29, 1999 FAX NUMBER: PHONE NUMBER: (425) 771-0221 RE: NUMBER OF PAGES INCLUDING COVER SHEET: Edmonds Sound Urological 5 1) I)R('i[:N*I' -IFORRINIEW 0 PLEASE. COMM Wl' 0 PI.EASE REPLY 0 FOR YOUR USE NOTES/COMMENTS- Jeanine: Please find attached our responses to the Correction Checklist. Please call to discuss. Thank you Peter Carletti CeirlettiArchilects. P.S. 2204Riverside Drive, Suite 270 Afount Vernon, WA 98273 (.360)424-0394 FIIX(3(jO)424- 5726 o u n - z!:# -!o �:s L iL U " I I r_ U I =/40 CARLETTi ARCHITECTS, P.S. ardiiicrime & June 28, 1999 Jeannine Graf, Building Official City of Edmonds 121 — 5"' Avenue North Edmonds, WA 98020 RE: Plan Review #99066 Edmonds Sound Urological Dear Ms. Graf - REC:FIVED JUN-2 9 1999 DEVELOPMENT SERVICES CJR- CITy OF EDMONDS I- . U4 The following is in response to your Correction Checklist, dated June 18, 1999, for the above referenced project. Listed below are our itemized responses. NON-STRUCTURAL Item I Please see notes on the upper comer of Sheet A-2.0 that state that the south and the west walls are to be of one -hour construction. Also, please see the note on Wall Section 1, Sheet A-5.0 that states that the south and west walls are to be of onc-hour construction. Item 2 Per a pre -application phone conference call with you, it was determined that the building is a B Occupancy, as there are less than five patients that are incapable of self-preservation. Item 3 Per a pre -application meeting with the City of Edmonds and discussions with you, the area above the reception area is not for storage, but is a mechanic al.pl atform, and therefore does not need to have a complying stairway. We are utilizing a com mercial disappearing stair with a onc-hour rated opening. Per all discussions I have held with City staff, this is an acceptable solution to accessing the mechanical platform. In addition, per 1003.3.3. 1, it states stairs or ladders used to attend equipment are exempt from requirements of this section; and, per 1103. 1. 1., it states non-occupiabic space accessed by ladders, such as mechanical and electrical equipment rooms, are exempt, Item 4 There is a complying landing. Please refer to the Site Plan, Sheet A- 1.0, which shows that there is a concrete landing on the e,xterior of Door 430 that leads directly to the sidewalk and there are no steps or barriers. S:\Arch\98',,DuL:LLMCn(5\162'�Williams 06-28-99.doc' 04 Kivt�rsidr Drivi-. Suilc _'?0 Mouni Vernon, WA 992":1 :360) 4214-0394 FAX �161)i 424-1726 AA_ ,jun — e- to — !:o to -.L xt etotAt_tAmL_ r- i i L �-%mt_n L i r-%— i _s Jeannine Graf., Building Official City of Edmonds Plan Review #99066 Edmonds Sound Urological C_ -+ L'A I C_ %a F_ . RECEIVED JUN! .2 9 1999 DEVELOPMENT SERVICES CTR. CITY OF EDIVIONDS Item 5 It is agreed that the maximum live load for the mechanical platform shall be posted. We will post this as 125 ounds per square foot. This is noted on Sheet S-3 of the Structural Plans. (,j:0Kj !11:11111d #0 A-2.5, fit m is 110 uir ge room to be placed on an exterior ion 4'10, there q Per Section 410, there is no requirement for the medical gas'stora wall. We will change Door #27 into the room to be a one -hour smoke and, draft assembly rather than 1/4 hour rated. (Please note this on the plans.) Item 7 We are agreeing to provide medical gasses Room #148 with automatic sprinklers and mechanical ventilation in accordance with the Exception of Section 410. (Please note this on the plans.) Item 8 We agree that all smoke and draft doors shall comply with the 1997 UBC, Standard 7-2. This revision requires that all smoke and draft assemblies be tested for a maximum allowable leakage of three CFM per square foot and be labeled with an S rating. Please indicate this on the Cover Sheet of the plans. Please mark this revision in rate on the Cover Sheet. Item 9 We agree that all other fire resistant door assemblies shall be tested to the new provisions of UBC Standard 7-2.1, for fire resistant assemblies. Item 10 There is no requirement, per the UBC, for protection of any through wall penetrations of any fire resistant wall assemblies. The only fire resistant walls required by the LJBC are the south and east walls. The only penetrations that will be occurring on the south and east walls are for one hose bib on each side. Each hose bib will be fire stopped with an assembly with an F Rating equivalent to the wall that it penetrates. Item 11 We do not have any insulation facing that is exposed to the interior. However, we agree that if there is any it shall have a flame spread rating of 25, per Section 707. Item 12 We -agree that the masonry veneer anchors should support no more than square feet of veneer area. (Please revise Detail .1 on Sheet A-5.0. with red markings for this comment.) Item 13 The size of the vertical strut for bracing the suspended ceiling sh all be 3 Y2" 20 gauge steel stud. (Please note in redami4c-pl-ahs-tt-aT-ir���apa���ing an actual compression load of 200 pounds.) �� Av�a RjAe4 -6 cWtIS 1:5/15 sIck A- S:\Arch\98',Documeiits'%162'.Williams 06-28-99.doc 'Juri—ew—t.1to JLX ; Z:_W1A_ 'k-1AML-r- I I X PAM%-rll.L I F-%- 1 -3. Jeannine Graf, Building Official City oJ* Edmonds Plan Review 499066 Edmonds Sound Urological MECHANICAL Item I We arc submitting mechanical as a deferred submittal. (Please note this on the Cover Sheet.) Item 2 We agree that if the water heaters have non -rigid water connections and are over four feet in height they should be anchored or strapped to resist earthquake motion, per Section 303.4 of the UBC. 1997 WASHINGTON STATE NON-RESIDENTIAL ENERGY CODE Item I Please add a note in red to Sheet A-2.4 that all glazing shall be certified and labeled with its U factor and solar heat gain coefficient by an independent agency licensed by the NREC. Item 2, We agree that the slab insulation shall comply to complete the then-nal break. It has been my experience that Plans Examiners for NREC, as well as Site Inspectors, have allowed the insulation to be cut down from the top o f the sl ab due to spauling of concrete and other Issues that arise with floor coverings. When the Code was written it did not take into account the constructability of such a detail. All inspectors we have worked with to date in the greater Seattle/Bellevue area have been allowing this exception. Please advise if not acceptable. We will revise and get a complete thermal break. Item 3 We agree to comply with outdoor air being required in the building, per the Washington State Vent 11 ati on/indoor Air Quality Control, WAC 51-13. As previously mentioned, we arc doing a deferred submittal for mechanical. Calculations will be submitted to Justify the quantities. Item 4 We agree that any full partition height space shall have individual lighting controls. Item 5 We agree that daylight zones in the room shall be shown to have switches, occupant sensors, or daylight sensors to control luminares near the window wall independent of the general lighting. Item 6 The attic access door does come with insulation and is weather stripped, as it is a one -hour smoke and fire draft assembly. 1995 WASHINGTON STATE REGULATIONS FOR BARRIER FREE DESIGN Item I Per prior discussions with Karissa Kawamota, due to conflicts with planning issues and availability in requirements for parking, she agreed to allow a five foot access aisle in lieu of the eight foot access aisle for a van accessible stall. S:"Archl,.98".Documents'%162\Williams 06-28-99.doc Jeannine Graf, Building Official City of Edmonds Plan Review ft99066 Edmonds Sound Urological Item 2 As previously mentioned in Item I above, this requiNment was waived by Karissa Kawamota. Item 3 Please refer to Detail 9 on Sheet A-L 1. The side slopes shown are 1:10, which are acceptable, as the top width of the sidewalk is 48 inches or greater. Item 4 Please see Detail 9 on Sheet A-1. 1. We have noted that the slope of the ramp is 1: 12 maximum. STRUCTURAL Item I — Item 6 Please refer to the attached letter, dated June 28, 1999, from DC1 Engineers, which addresses these items. I trust that these responses are acceptable to satisfy the corrections for the project. We appreciate you reviewing the project. If you have any questions, please don't hesitate to call. S1 it tects, P.S. cc: Bob Wilcox, Wilcox Construction Tim Roddy, Sound Urological Associates S:\Archl,98',,Documents'�.162\Williams 06-28-99.doc TO: Jeannine Graf =0 f e_ 0 P 01 CARLETTI ARCHITECTS, PS. architecture & planning FACSIMILE TRANSMITTAL SHEET FROM: Peter Carletti COMPANY: DATE: City of Edmonds 02111/99 FAX NUMBER: PHONE NUMBER: RE: NUMBER OF PAGES INCLUDING COVER SHEET: Sound Urological Clinic I 98-162 C URGENT 13 FOR REVIEW C3 PLEASE COMMEN7 r3 PLEASE REPLY 0 FOR YOUR USE NOTES/COMMENTS: Jeannine; The following memo is to confirm our phone conversation of February 10, 1999 regarding the above referenced project and our pre -application plans that were submitted for review. We discussed the following issues: I If we have an x-ray room the walls need to be lead firked 2. it was agreed that this is a B-occupancy type V-N construction 3. You stated that you need the quantity of gases that will be kept in the building 4. Our interior lighting is exempt and you will not require NREC. However, you will need an outside lighting plan and budget per NREC. S. Demolition permits will be required. 6. 1 need to speak to the planning depicitrient regarding the lot line adjustment or lot aggregation that needs to take place. 7. 1 -hour walls will be required at the south and the cast walls due to less than 20' from the property line. However, parapets won't be required, as we can have unprotected openings'. Overhang is 30" and is not rated due to unprotected opening. 71= 518" 'x' Swb can stop at the top of the wall plate, 8. We have no rated corridors. All pasuges are non -rated hallways. 9. You stated we should check the dimension of our egress exits for'half the distance of the diagonal. We are proceeding with this information for design purposes. If any of it is incorrect please notify us irnmediately. Tlianks, Petc Carletti Carletti Architects Carteld Architects, P.S. 2204 Riverside Drive, Suite 270 Mount Vernon, WA 98273 (360) 424 — 0394 FAX(360) 424 - 3726 M CWA CONSULTANTS STRUCTURAL ENGINEERING BUILDING CODE CONSULTANTS 22421 N.E. 20n' Stmet, Redmond, WA 98053 (425) 836-2833 FAX: (425) 836-3707 E-Mail. chuckw@gte.net June 18, 1999 Jeannine Graf Building Official City of Edmonds 121 5tAvenue North Edmonds, 98020 Dear Ms. Graf; CITY COPY Plan Review #99066: Edmonds Sound Urological 1997 Uniform Building Codes Type of Construction; V-N Occupancy — B Stories: 1 Seismic Zone: 3 Wind Speed: 80 R E C E I V F,- Wind Exposure: B -JUN 2 9 DEVELOPMENT SEW, - CITY OF EDMON., We have completed our review of the Edmonds Sound Urological. The plans have been reviewed for compliance to the 1997 Uniform Building Code, 1997 Uniform Mechanical Code and the Washington State Accessibility. NONSTRUCTURAL For your information the entire building is of Type V-N construction. However the south wall is required to be of one -hour construction since it is located less then 20' from the property line. The Sheet A-2.0 'zyou should verify to your satisfaction that the actual use of this building does not require an 1-1.2 occupancy classification. The architect has indicated that the building is a B occupancy since the building serves less then 5 patients. This is for your determination. There appears to be a storage area located above the reception area. This should be provided with a complying stairway. The details for the pull -down stairs shown on Sheet A-6.2 do not comply with Chapter 10. /4. A complying landing should be shown at the exterior of door 30. JUN_ei_1t$t$1j 11:.�b �'Kuill; I U � ItCZ) I I luccl r. UUC, UUlt Edmonds Sound Urological PC 99066 June 18, 1999 Page 2 of 4 ,/The maximum live load for the storage area should be posted Section 1607.3.5. The medical gas storage room should be placed on an exterior wall. The door (#27) X81"T into the room should be a 1whour smoke and draft assembly. The exterior wall should be vented with a high and low vent of 36 in 2 each. Section 410. /7/Alternately the room could be provided with automatic sprinklers and mechanical ventilation in accordance with the exception to Section 410. All smoke and draft doors should comply with the 1997 UBC Standard 7-2. This zz"") revision requires that all smoke and draft assemblies be tested for a maximum allowable leakage rating of 3 cfm per square foot and be labeled with an "S" rating. This should be indicated on the plans. Z,P�A I other fire resistive door assemblies should be tested to the new provisions of I U BC Standards 7-2, Part 1 for fire resistive assemblies. This revision to the Standards now requires that the doors be labeled with a temperature rating and that the doors pass a much more stringent fire test procedure. �"�etails should be provided for protection of all the theough-penetrations and membrane penetrations of all fire resistive wall assemblies. Section 710. These should be listed assemblies with an F rating equivalent to the wall penetra ' ted. Note that a T rating is no longer required in the 1997 UBC for wall penetrations. y"'I'nsulation facing that is exposed to the interior should be provided -with a maximum fl me spread rating of 25. Section 707. (X2. The masonry veneer ties should support no more than 2 square feet (not 2' oc) of v neer area. Detail 9, Sheet A-6.0 should be revised .The size of the vertical strut for bracing the suspended ceiling system should be /1�t specified. It should be capable of supporting an axial compression load of 200#. MECHANICAL No mechanical plans were submitted, These should be listed on the plans as a deferred submittal. I f the water heaters have nonrigid water connections and are over 4' in height, they should be shown anchored or strapped to resist earthquake motion. Section 303.4, UIVIC JUN-21-1999 11:36 FROM: I U: 14d�) ((I uddi t. UU4 Edmonds Sound Urological PC 99066 June 18, 1999 Page 3 of 4 1995 WASHINGTON STATE RESIDENTIAL ENERGY CODE (WAC 51) The designer should note on the plans that all glazing shall be certified and labeled with its U-factor and solar heat gain coefficient by an independent agency licensed by the NFRC. Section 1312.1 /2�_Fhe slab edge insulation shown in Detail 2/A-6.0 should provide a complete thermal break. Z_��Outdoor air is required for this building per the Washington State Ventilation and indoor Air Quality Code (WAC 51-13). The quantities of outdoor air supplied to each area should be listed on the plans per Table 3-4 of that code, Calculations should be submitted to justify the listed quantities. Each full -height partitioned space should have individual lighting controls. Section 1513.1 Cth5�_ "'�The daylight zones in rooms should be shown to have switches, occupant sensors, or daylight sensors to control the luminaries near the window wall, independent of the general area lighting. Section 1513.3, Section 1210. ,/"�Tlhe attic access doors should be shown with insulation and should be weather- s st ripped. Section 502.1.4.4 1995 WASHINGTON STATE REGULATIONS FOR BARRIER -FREE DESIGN /. one accessible parking space should be provided, which should be van -accessible. Sections 1107.1.1, 1107.1.5, Table 11 -F Van -accessible parking spaces should be 8'wide, with adjacent 8' wide access aisles (which may be shared with an adjoining space). Sec;tion 1107.2.2 The maximum side slope for curb cut ramps should be shown as 1:12, where the width of the sidewalk at the top of the ramp is less than 48". Section 1106.4.7.3 X,"The slope of all ramps should be shown on the plans (1:12 maximum). Section 1106.8.2 STRUCTURAL /�All deferred submittals should be listed on the plans. Section 106.3.4.2. JUN-tl-l*=�'Z) 11;-)tD rmUll; I U - : I I YJCC I r, . Y-)Y-)-t I YJU-t Edmonds Sound Urological PC 99066 June 18, 1999 Page 4 of 4 zzl_�T 'he non -bearing walls should be held down from the truss bottom chord with an approved fastener (such as Simpson STC) to insure that the truss bottom chord will not bear on the wall. A ",_�Ipproved hangers should be used at all connections of rafters, jack or hip trusses to t�, the main girder truss. The type should be specified on the plans. All shear walls with an allowable shear of more than 350 plf should be provided with ."�l 3x members at adjoining panel edges and at the foundation sill plate. Note 9 of the shear wall table should be revised. This would apply to both SW 3 and 4. /15�All anchor bolts should be provided with ZxZx3/16" plate washers. he use of PT Doug -Fir for the foundation sill should be justified. I don't believe that 'n DF species. pressure treated material is available i I am retaining all plans and data and anticipate that I will be rechecking any plans as necessary. I will gladly accept telephone inquiries from the designer. I will also send a copy of this plan check list directly to the designer. Please instruct the designer to indicate on a separate letter which sheet or detail the corrections may be found and to REVISE AND RESUBMIT THE PLANS. Please feel free to contact me if there are any questions, Sincerely; Chuck Williams SE CWA Consultants Eno -­'57 een.-O GeGI C) WIN 00'-� ap DOG 0 0 W, we (D SOD, . e —NO FIX TREES TO REMAIN 76TH AVENUE W. -p we _,� -to !! wc ­.T 0 ME TO L IF) LANDSCAPE PLANT MATERIALS LIST SYMBOLI NAME size DESCRIPTION OF' PLANT le— 1-1111EIA VCAL 1111- III= TIEC WIT. -I!. BRANCHING (D PAPER BIRCH HABIT AND LACY FOLIAGE CHAMAEC PARIS ObTUSA 6.&- PT SL NOES SMALL EVERGREEN T EE WITH HlNoKI CYPRESS OPEN BRANCHING. DROUGHT RESISTANT PRUMUS YEDOENS18 2 IN GReEAT MEDIUM-BIZE SHADE TRCE WITH YOSHING FLWQ. CHERRY CL AN HABIT AND GHOWT BLOOMS RHUS YTp.HINA 6-10 PT SHIPW TREELIKE SHRUB WITH BRILLIANT STAG RN BWAC FALL CMOR AND INTERESTING WINTER LOOK ENKI THUS CAMPANULATUS 50' HT. SMALL SHRUB WTTH GLOSSY EVERGReCN ReDVEIN ENKIANTHUS LCAVCS -- OPEN BRANCHING 0 eftICA CAANe"c�uN^ Vua.G. I GAL REVIEW LIST OF PROPOSED VARIETIES WITH MEATHS AND HEATHERS LANDSCAPE ARCH. BEFORE INSTALLATION 0 RHODODENDRON 50 IN. DARK GREEN LOW $HR.. WITH NO- ZEMBLA RH.... RCO BLOOMS AND CLEAN FOLIAGE 0 RHODOD MORON SP. ­5* I� GWAAF MAROON —NOD FOLIAG AND PJM RHODOOeNDRON EARLY LAVENDER -PINK BLOOMS 0 ARCOCOC A RUSCIFOLIA I — SM LL CVCRGKCCN SHRUB WITH FRAGRANT SW �T SARCOCOCCA CARLY BLOOMS -- LOVeS SHADE (D THUJA 0 ClOeNTALIS . P'. FULL AND BUSHY. WELL MATCHED EMS. DIC.. PYRAMIDALIS ,�6 JUNIPeRUS CONFER A 2 GAL LOW SPREADING GROUNDC.VtR WIT. SOFT —1. BRIGHT GREEN NeeDLES COTONCA3Teft TIAMNeRr I GAL LOW GLOSSY-LeAF ZnOuNocovex spAcE BEARBERRY COTONEASTeR 18 IN. ON CENTER CLeNATIS ARMANDII I GAL TRAIN ONTO FENCE eVERGReCM MENATIS LANDSCAPE NOTES 1. THE SU5GRADe OF ALL LANDSCAPE AREAS SHALL Be SCARIFIrD AND LARGE! ROCKS. ROOTS. AND CONSTRUCTION DEBRIS SHALL BE REMOVED PRIOR TO PLACEMENT OF TOPSOIL. 2. A MINIMUM DEPTH OF SIX INCHES ICOMPACTrDI BLENDED MANUFACTURED TOPSOIL SHALL be INSTALLED IN ALL LANDSCAPE BEDS. 21 LAWN AREAS SHALL BE PLANTED WITH NUMBER ONE GRADE R�LLI!D SOD. STAGGERING JOINTS TO AVOID SEAMS. 4. ALL TREES SHALL BE STAKED AS NECESSARY TO PREVENT LEANING OR DAMAGE TO THE ROOTBALL AS SHOWN ON DETAIL SHEET L3.1. ALL TREES. SHRUBS. AND GROUNDCOVrRS SHALL BE FERTILIZrD AS NECESSARY TO ACCOMMODATE SIZE AND CURRENT GROWI NG SEASON. S. A TH Rrr'INCH LAYER OF FINELY GROUND BARK MULCH SHALL BE INSTALLED IN ALL PLANTED 5eDS. CASORON OR OTHER CHEMICAL WEED CONTROL MAY Be APPLIED. BUT CONTRACTOR ASSUMES ALL RISK FOR ADVER Se ePP7CTS ON PLANTS. SOD. AND/OR SOIL. 6. THE ENTIRE PROJECT SHALL Be LEFT IN A SPOTLESS CONDITION AT COMPLETION. THE OWNER SHALL BE FURNISHED WITH A FULL SET Of' INSTRUCTIONS FOR MAINTENANCE OF THE PLANTINGS AND I C IRRIGAT ON SYSTEM. ALON , WITH ALL TOOLS . KEYS.ANO OTHER eOUIPMeNT NECESSARY TO OPERATE AND MAINTAIN THE IRRIGATION SYSTEM. 7. THE CONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR AND THE OWNER TO DETERMINE THE BEST LOCATION FOR THE! AUTOMATIC IRRIGATION CONTROLLER. I'- THE LANDSCAPE ARCHITECT RESERVES THE RIGHT TO REQUIRE SUBMITTALS REGARDING THE SELECTION OF' IRRIGATION CONTROLLER. TOPSOIL AND BARK PRODUCTS. PERENNIAL FLOWER SELECTIONS. AND PROPOSED PLANT MATERIAL SUBSTITUTIONS. 0. THE LANDSCAPE CONTRACTOR SHALL FURNISH A ONe-YEAR WARRANTY ON ALL WORKMANSHIP AND MATERIALS RELATING TO THE LANDSCAPING AND IRRIGATION OF THE PROJECT. ANY ITEMS FAILING DURING THIS PERIOD SHALL BE REPLACED WITH eQUAL OR BETTER AT NO COST To OWNER. 040 STATE OF 0 5 10 2.0 SCALE LAURIE A. FREEMAN CERTIFICATE NO. 626 COPYRIGHT 1000 -- ALL RIGHTS RESERVED ATTACHM aL Pre -application meetin February 12, 1999 — 9:00 a.m. Applicant: Carletti Architects Site Address: 21822 and 21830-76h Avenue West Medical Building Attending: Representing Ci1y Sta Gordy Hyde, Rob Chave, John Westfall, Conni Curtis. Representing Applican : Peter Carletti, Carletti Architects; Kathryn Emory, R E C E I V E D TCI Engineers MAR 191999 Rob asked Applicant to explain his project. EDMONDS FIRE DEPT Applican : There are two existing residences on the site (21822 and 21830-76fl' Avenue West). What we're proposing to do is remove the two residences and construct a new medical clinic (approximately 4,683 ST) for a group of urologists. Currently the property is zoned RM2.4. We have filed for a Conditional Use Permit on the property and for SEPA. A DNS has been issued, and our hearing is scheduled for March 4 at 9:30 a.m. I've had conversations with Karissa and Brian of the Planning Division and with Jeannine Graf of the Building Division. We are -going to file for ADB today. The Applicant went over the plans, noting setbacks, square footage of building, indicated 23 parking stalls — one barrier free. Applicant provided landscape plan showing trees to be removed and location and type of trees to be added. He also provided an irrigation plan. This will be submitted with ADB. In addition will be submitting the application for a free-standing monument sign. Sign will use ground lighting and the base will be landscaped. Will be a one-story building with metal weathered copper roofing, brick wainscot, approximately 3'4" high, wraps entire perimeter of building with a pre -cast concrete steel cap. Dark bronze aluminum store -front windows, "stucco" -type natural white finish. No rooftop mounted mechanical units — all mechanical units will be in second -floor attic space. Two pole lights, couple of ground lights at the side, and some ball packs around the building. Building Division was unable to attend meeting, but Applicant had spoken with Jeannine prior to today. They discussed height calcs, and datum points are indicated on the plans. The Applicant then addressed drainage. Most of site drains onto 76h Avenue West; parking lot will just drain into catch basins as shown; 48" diameter underground storage, orifice release into the existing storm drainage system in the street. Need a lateral sewer connection and will replace the driveway. Applicant asked if City is aware of any downstream drainage issues. Engineering (Go : We have reviewed primarily traffic and stormwater design. Water quality amendments are required for the outside parking lot areas. Our ordinance provides for bioswales, but there are alternatives that are also approved — a wet pipe can be used, filtered systems .... for specifics on this issue, contact Don Fiene, our Hydraulics Engineer. Provide all information required on checklist for ADB application (site cross -sections, driveway slopes, etc.) With the number of stalls you are creating, you are right on the cusp of requiring what we call a high -traffic load driveway, and it looks like you are designing a standard residential driveway. A high -traffic load driveway is merely a drop curb situation where you'd have a wheel chair ramp on each side — I have typically required a high traffic load driveway anytime you're providing more than 20 parking stalls. Because you're right on the cusp and are this far along in the design, we may not require it — I will let you know. Driveway dimension is 24' minimum — it looks like you have all your dimensions on these plans as to traffic stalls, etc. We do have a need for a traffic report for SEPA. The Traffic Engineer has asked for the following information: trip generation, traffic distribution, level of service analysis of the following intersections: 76fl'Avenue West/22Wh Street SW 76hAvenue West/Highway 99 76thAvenue West/216 h Street SW 220th Street SW/84h Avenue West 76'hAvenue West/212th Street SW 22Wh Street SW/Highway 99 Page I Pre -Application Meeting February 12, 1999 Carletti Architects/Medical Building Applicant indicated the traffic report had been completed and submitted with SEPA and that they have been provided with projected amount of impact fee. Per Applicant, Jeannine had called him two days ago indicating that she would not be in attendance today, so he sent her a memo confirming their conversation. She didn't have any issues, and he had no more questions regarding building issues. John asked if Jeannine agreed with the B-Occupancy. Applicant: The Applicant stated he could meet UBC 304.1 #8 and allowable area per table 5B. We talked about the fact that we're okay in allowable area. For 5-N, when you're less than 20 feet, bearing walls haveto be one -hour, so we have the two indicated on our plans. We talked about the fact that parapets wouldn't be required since we're greater than 10 feet, you can have unprotected openings; therefore no parapets required. We talked about the overhangs and the fact that in the code overhead projections all the way up to 30", so since you could have unprotected openings, those don't need protecting. Note: Ais is subject to UBC 503.2. 1, the 30 " overhang is an ECDC code, not UBC Fire/Building �Lohn) John indicated a fire alarm requirement for corridors and office uses required by building code in lieu of one -hour corridor construction — is that a trade-off there? Applicant indicated no — we don't need it because in the new UBC, all the rooms only require one exit, so every exit exits out into this hallway — under the new UBC, a hallway is considered an intervening room. Lobbies aren't considered as intervening rooms, so since the doors are all going through intervening room, you have no rated com'dors. Per Applicant, Jeannine agreed with the conceptual design, but means of egress will be checked during pen -nit review. John asked then if no second exit required. Applicant pointed out two exits. Per, Applicant, Jeannine indicated that the distance appeared to be adequate, but the architect should check the half -diagonal rule for spacing of exits. John asked if Jeannine had discussed med. gas with him. Applicant said yes, she needs to know quantity of gasses that are there. John asked if Applicant had certified installer — to provide Building Division with that information. Applicant indicated a requirement from Medicare regarding one -hour separation walls in various other rooms. Per John, one hydrant will be required spaced at 300'. Applicant indicated they will place the hydrant on the side of the street where the water main is. Fire extinguishers are indicated throughout. Per Applicant, there will be an emergency generator backup because of a Medicare requirement. Applicant indicated that in talking with Jeannine, the issue was brought up regarding the two separate properties and property lines — dowe need to do a lot line adjustment, a lot aggregation? Rob said that a lot line adjustment will be required. Applicant asked what happens about these trees? Do we have an ordinance for removing these trees or do we evaluate that with the landscaping plan? Per Rob, it's evaluated with the landscaping plan for ADB. CAMy Documents\Engscc\DEVELOP\Pre-AppMtgs\PreApp2.12.99. Ldm Page 2 i/.viebFIRS Fire Incident Report Edmonds Fire Department incident Number: EF07000998 Exposure: 0 Incident Date: 3/23/2007 3urisdictional Station: 20 Location Type: Street address Address: 21822 76 AVE W City: Edmonds State: WA Zip: 98026 Incident Type: Alarm system sounded, no fire - unintentional Shift: A Alarms: 1 Grid: EF156 Aid Type: None Alarm Time: (17:00:19) 3/23/2007 Arrival Time: (17:05:28) 3/23/2007 Last Unit Cleared Time: (17:19:56) 3/23/2007 Actions Taken: Investigate HazMat Released: None Property Value: 0 Property Loss: 0 Fire Service Deaths: Fire Service Injuries: 0 Contents Value: 0 Contents Loss: 0 Civilian Deaths: Civilian Injuries: 0 Detector: Officer In Charge: PATRICK HEPLER Assignment: Command Mixed Property Use: Not mixed use Property Use: Clinics, Doctors offices, hemodialysis centers wc[TIRS Fire Incident Report Edmonds Fire Department Person('s) Involved Business name: Manager Role: Other Name: Hope Durnais Phone Number: 4256708950 Address: Apparatus and Personnel Apparatus ID Personnel ID('s) L20 EF0128 EF2208 EF2400 YL wc[TIRS Fire Incident Report Edmonds Fire Department Incident Number: EF07000998 Exposure: 0 Incident Date: 3/23/2007 Narrative Ladder 20 was dispatched to a Commercial Fire Alarm at 21822 76 Ave W, and Sound Urological. On arrival at the one story, wood framed, medical office clinic, with no visible problem from the exterior, no bells or strobes, L20 was met by the manager of the clinic, Ms Hope Dumais. She stated that is was a false alarm. She followed up by saying that an employee opened the autoclave, and when she did it burped out steam and heat, setting off the smoke/rate of rise detector right above the unit. Ms Dumais reset the system prior to our arrival. On investigation, Ms Dumais showed 1-20's crew the autoclave in a small back room, with a detector right ablve the unit, and no problem was found. The unit was a Tuttnauer Auotclave Steam Sterilizer- MN-3870E, SN-9606177. No one was hurt in the incident either. Ns Dumais stated that it has happened before, and I recommended that the unit be moved to a location that is not near a detector, due to the nature of the unit to expell heat and steam upon opening it. L20 then went in service. Lt PATRICK HEPLER incident Hillpry'W" 140'450= Cose Wumbevsg 4. Qm� A $EF07001-1- i-ri"""4" , %4 zwy"A nit Entered a w" A a Ww" M&O 0 03W/07' 0 Dispatched "'A Enroute 4- Onicene 4, 4" I Closed -AN - WAT ax a N ANW; A w 00/20W 1011067" v- Wit ial Type: FAC initial Al-Irm Leyel; Final Alarm Level: I Final Types FAC (FIRE ALRRM,- COMMERCIAL) fri; I Dispa: Police BLK: E014 Fire BW Ajp,Pagei 455PI7 Gravp:' EFIA Beat; EF20 Sr ",L`0156 Lou: R1822 76 PV W E,')[,l �k,LJNII U ROW) 1AL Awn 1 hTnAT k 1141. hT 9W V Lou Info: �.`30(.JND UR111"!,LOGICAL ASSOCIATES, QA boo Names ADT/TRAVIS - Addr; R/1657 1701165W 7" ­Ph�&ne�. F""'. 7 7, /165§ (S0744 ) ENTR",i` NO RESET ON FIRE ALM COVIRS SMOKE ROOK SOU0 /1659 (SC712 ) DISP E20 #VF012P HEPLERwP-L Q) CEIMIRI 4EPP400 PqDSPqqN,S-F ruyl #EF2200 DOWLIqQJ,F CE,M,RJ 1609 SASNCAS NO W07001112 ASST 7&w $ASNCPS 1ACH sW07001435 /1700 (SC737 AID TAC21 /1700 PREMPT E20, 91700- DISPI� L2Q REFOIRS HEPLQPjP-L'(B) EQM,R] #EF1200 DOWLIN%J-F CE,M,R] #EF2400 ANDERSO%B-F.EQM3 /1659? (SC744 SUPP LOCK SOUND UROLOGICAL ASSOCIATES,, NAM: HOPIFI'l ADR: 21822 76 AV W IEDM, PHOr 42577571667 PZP CALLING FRON ON81GH-r AND SWE THERE ISY !'-,I k PROBLEMS- THIM XHEY AU10 C LAVE SET IT OFF /1701 (SC737 ) ENROUT L28 /f703 (SC726 ) ONSCNE L20 I ME,D OFC BLUSINVI /1705 QC744 ) CHANSE ALM COXALLINS BACK SAYING PREMISE ADVISED EUER 1' YTHIGN I S :OK, /1719 QC706 AOR 1-20, /1711 L23 R";