Loading...
0350_001.pdfFrom: Jonathan Kramer <jonk@horeco.com> Sent: Tuesday, February 26, 2019 1:34 PM To: Nelson, Denise <Denise.Nelson @edmondswa.gov>; Miller, Chuck <Chuck.Miller@edmondswa.gov> Subject: FW: Message from KM_C454e Hi Denise & Chuck Hope all is well for you. Below are hopefully the changes you requested. With the reply to the questions you sent me last Friday afternoon. Next I will send the revised drawings Item (9) We increased the size of the heater in the attic to 3.5 ton from 3 ton this increased the CFM to 1350 cfm. I labeled the size of the ducts and added two additional exhaust fans and labeled duct size and cfm movement. We are supplying the 3.5 ton heater that is in the attic with 12" duct for incoming fresh air. And the return air is also 12" duct. The exhaust fans on the main floor will take the required "bad air" out of the building. Item (10) next email will have spec sheets showing required data for larger 3.5 ton heater unit. Item (12) The drawing now shows size of duct runs for all supply, exhaust and return air and amount of cfm per location. Item (13) Relocated intake vents for HRV's exhaust vents now vent out on west wall shows cfm and duct size Item (14,15) added one more wall heater and fresh air and exhaust air on north side of building. Item (16,17) See item 9 above Thank you, Jon W. Kramer From: bizhub(&allpointsheating.com[mailto:bizhub@allpointsheating.com] Sent: Tuesday, February 26, 2019 2:06 PM To: jonk horeco.com Subject: Message from KM_C454e -UL FEB Z U* 2ON SUIUPIW7 rvlf""I CITY & L Ul�ic�PI�7's