Hi Denise & Chuck
Hope all is well for you. Below are hopefully the changes you requested. With the reply to the questions
you sent me last Friday afternoon. Next I will send the revised drawings
Item (9) We increased the size of the heater in the attic to 3.5 ton from 3 ton this increased the CFM to
1350 cfm. I labeled the size of the ducts and added two additional exhaust fans and labeled duct size
and cfm movement. We are supplying the 3.5 ton heater that is in the attic with 12" duct for incoming
fresh air. And the return air is also 12" duct. The exhaust fans on the main floor will take the required
"bad air" out of the building.
Item (10) next email will have spec sheets showing required data for larger 3.5 ton heater unit.
Item (12) The drawing now shows size of duct runs for all supply, exhaust and return air and amount of
cfm per location.
Item (13) Relocated intake vents for HRV's exhaust vents now vent out on west wall shows cfm and duct
size
Item (14,15) added one more wall heater and fresh air and exhaust air on north side of building.
Item (16,17) See item 9 above