Loading...
0494 Magic Toyota Mech Binder For Permit.pdfABBREVIATIONS GENERAL - LEGEND 0 DIAMETER -■EQUIPMENT TAG TYPE ABV ABOVE AD ACCESS DOOR EQUIPMENT TAG NUMBER AFF ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT -•----DETAIL OR DIAGRAM NUMBER AP ACCESS PANEL -0 -■SHEET NUMBER WHERE DETAIL/DIAGRAM SHOWN APRVD APPROVED BF BELOW FLOOR 1 -•SECTION LETTER BFC BELOW FINISHED CEILING SHEET NUMBER WHERE SECTION IS SHOWN BOT BOTTOM BTU BRITISH THERMAL UNIT (�LD A REVISION CLOUD AND CHRONOLOGICAL NUMBER CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE DETAIL REFERENCE OUTLINE CIP CAST IN PLACE L - - - - J CLG CEILING POINT OF CONNECTION TO EXISTING OR TO CONC CONCRETE OTHERS' WORK CONN CONNECTION CW COLD WATER 1� KEY NOTE CALLOUTS DB DRY BULB DIMS DIMENSIONS WORK TO BE REMOVED DN DOWN DR DRAIN 0 4' 8' 16' DWG DRAWING DRAWING SCALE SCALE: 1 /8" = 1'-O" EA EACH EAT ENTERING AIR TEMPERATURE EF EXHAUST FAN HVAC - LEGEND EG EXHAUST GRILLE EQUIP EQUIPMENT ESP EXTERNAL STATIC PRESSURE AIR FLOW DIRECTION EWT ENTERING WATER TEMPERATURE SUPPLY OR OSA DUCT SECTION UP, ROUND OR RECTANGULAR EXH EXHAUST FF FINISHED FLOOR FPM FEET PER MINUTE RETURN, RELIEF OR EXHAUST DUCT SECTION UP, ROUND OR FT FOOT OR FEET RECTANGULAR FUT FUTURE GAL GALLON > < SUPPLY OR OSA DUCT SECTION DOWN, ROUND OR GALV GALVANIZED RECTANGULAR GD GREASE DUCT HP HORSEPOWER RETURN, RELIEF OR EXHAUST DUCT SECTION DOWN, ROUND HT HEIGHT OR RECTANGULAR HVAC HEATING, VENTILATING AND AIR-CONDITIONING RG - 100 RETURN AIR GRILLE, NUMBER INDICATES CFM QUANTITY HWR HEATING WATER RETURN HWRR HEATING WATER REVERSE RETURN HWS HEATING WATER SUPPLY CD - 100 SUPPLY AIR DIFFUSER, NUMBER INDICATES CFM QUANTITY IBC INTERNATIONAL BUILDING CODE ID INSIDE DIAMETER IFGC INTERNATIONAL FUEL GAS CODE EG - 100 EXHAUST AIR GRILLE, NUMBER INDICATES CFM QUANTITY IMC INTERNATIONAL MECHANICAL CODE IN INCHES IN WG INCHES WATER GAUGE SO - 100 SCREENED OPENING, NUMBER INDICATES CFM QUANTITY LAT LEAVING AIR TEMPERATURE LBS POUNDS EXISTING DUCTWORK LD LINEAR DIFFUSER _ - - - _ - _ LIN FT LINEAR FOOT OR FEET - - - - - - - SLSM SOUND LINED SHEET METAL LWT LEAVING WATER TEMPERATURE FLEXIBLE EQUIPMENT CONNECTION MAX MAXIMUM MBH 1000 BTU PER HOUR SFD COMBINATION FIRE AND SMOKE DAMPER MD MOTORIZED DAMPER MIN MINIMUM FD FIRE DAMPER MOCP MAX OVER CURRENT PROTECTION MUA MAKE UP AIR SD SMOKE DAMPER N/A NOT APPLICABLE OBD OPPOSED BLADE DAMPER VOLUME DAMPER OD OUTSIDE DIAMETER/DIMENSION OSA OUTSIDE AIR MOTORIZED DAMPER PH PHASE PN PROJECT NORTH (REFERENCE) TURNING VANES POC POINT OF CONNECTION PRESS PRESSURE PSI POUNDS PER SQUARE INCH ROUND TO ROUND 45° FITTING RA RETURN AIR RG RETURN GRILLE RL REFRIGERANT LIQUID LINE SPIN IN TAP RPBP REDUCED PRESSURE BACKFLOW PREVENTER RPM REVOLUTIONS PER MINUTE SQUARE TO ROUND 45° FITTING RS REFRIGERANT SUCTION LINE SA SUPPLY AIR SCHD SCHEDULE OF EQUIPMENT SFD SMOKE FIRE DAMPER 45° FITTING FOR DUCTWORK SG SIDEWALL GRILLE SOG SLAB ON GRADE GAS NATURAL GAS PIPING SL SOUND LINED SMACNA SHEET METAL NATIONAL ASSOCIATION CO CARBON MONOXIDE SENSOR SQ FT SQUARE FOOT OR FEET SS STAINLESS STEEL NO2 NITROGEN DIOXIDE SENSOR TDH TOTAL DYNAMIC HEAD �p OCCUPANCY SENSOR TG TRANSFER GRILLE TN TRUE NORTH SW SWITCH (ON/OFF/TIMER) TYP TYPICAL UNO UNLESS NOTED OTHERWISE O REMOTE SENSOR UPC UNIFORM PLUMBING CODE VFD VARIABLE FREQUENCY DRIVE SC SPEED CONTROLLER VTR VENT THROUGH ROOF W WATTS OR WIDTH OT THERMOSTAT W/ WITH W/O WITHOUT WB WET BULB ; TERMINAL UNIT WG WATER GAUGE REQUIRED EQUIPMENT CLEARANCE WSEC WASHINGTON STATE ENERGY CODE - - - - - J Ems 1. HEATING AND COOLING SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES AND AS REQUIRED BY 2015 WSEC SECTIONS C403.2.1 AND C403.2.2. 2. OUTSIDE AIR VENTILATION SHALL BE PROVIDED IN ACCORDANCE WITH 2O15 IMC TABLE 403.3 FOR MIN REQUIRED RATES AND NO MORE THAN 150% OF MIN RATES PER 2015 WSEC SECTION C403.2.6. DEMAND VENTILATION CONTROLS SHALL BE PROVIDED AS REQUIRED BY 2015 WSEC SECTION C403.2.6.2, FOR DENSELY OCCUPIED SPACES GREATER THAN 500 SQ Ff. 3. HVAC SYSTEMS HAVE BEEN DESIGNED TO COMPLY WITH 2O15 WSEC SECTION C302.1 AND TO MAINTAIN 72F MAX IN HEATING MODE AND 75F MIN IN COOLING MODE. CONTROLS SHALL BE CONFIGURED TO PROVIDE 5 DEGREE DEAD BAND PER WSEC SECTION C403.2.4.1.2. 4. CONTROLS FOR SYSTEMS THAT DO NOT OPERATE CONTINUOUSLY SHALL BE CAPABLE OF PROVIDING 7 DAY PROGRAMMABLE TEMPERATURE SETTINGS, AUTOMATIC SETBACK AND SHUTOFF AND OPTIMUM START AS REQUIRED BY 2015 WSEC SECTION C403.2.4.2. MOTORIZED DAMPERS SHALL BE PROVIDED FOR POSITIVE SHUTOFF AS REQUIRED BY 2015 WSEC SECTION C403.2.4.3, INCLUDING MAXIMUM LEAKAGE RATES. GRAVITY DAMPERS USED FOR OUTSIDE AIR INTAKE SHALL BE PROTECTED FROM WIND INFLUENCES. 5. DIRECT DIGITAL CONTROL (DDC) SYSTEMS SHALL BE PROVIDED AS REQUIRED BY 2015 WSEC SECTION C403.2.4.12.1 AND SHALL BE CAPABLE OF PROVIDING TRENDING, MONITORING AND SYSTEM DEMAND INFORMATION. 6. DUCT WORK SHALL BE INSULATED AND PROVIDED WITH VAPOR BARRIER AS REQUIRED BY 2012 WSEC SECTION C403.2J AND AS FOLLOWS: TYPE LOCATION R-VALUE OS AIR >2800 CFM IN CONDITIONED SPACE 19 OS AIR <2800 CFM IN CONDITIONED SPACE 7 SUPPLY OR RETURN IN UNCONDITIONED SPACE 6 SUPPLY OF RETURN OUTSIDE BUILDING 8 7. ALL DUCTWORK SPECIFIED SHALL BE CLASSIFIED AS LOW PRESSURE AND SHALL BE INSTALLED IN ACCORDANCE WITH 2O15 IMC REQUIREMENTS AND SMACNA STANDARD FOR 2" WG, UNLESS HIGHER STATIC PRESSURE ARE INDICATED ON DRAWINGS. 8. MECHANICAL PIPING, IF EXPOSED TO THE ENVIRONMENT, SHALL BE PROTECTED IN ACCORDANCE WITH 2O15 WSEC SECTION C403.2.9.1 AND ALL PIPING SHALL BE INSULATED AS REQUIRED BY 2015 WSEC SECTION C403.2.9. 9. AIRSIDE ECONOMIZERS SHALL BE USED AS A FIRST STAGE OF COOLING AND SHALL BE CAPABLE OF PROVIDING FULL OR PARTIAL COOLING CAPACITY DEPENDING ON THE COOLING DEMAND AND THE OUTSIDE AIR TEMPERATURE PER 2075 WSEC SECTION C403.3.1. FIXED DRY BULB CONTROL SHALL MODULATE THE OUTSIDE AIR FLOW DOWN TO THE MINIMUM AMOUNT AT OUTSIDE AIR TEMPERATURES OVER 75F. 10. SUPPLY AIR TEMPERATURE SHALL BE AUTOMATICALLY RESET FOR MULTIPLE ZONES AND SYSTEMS BASED ON DEMAND, AS REQUIRED BY 2015 WSEC SECTION C403.4.4.4 11. PROVIDE SEISMIC BRACING AND SUPPORTS IN ACCORDANCE WITH 2O12 IBC FOR SEISMIC DESIGN CATEGORY D AND BASED ON AN IMPORTANCE FACTOR OF 1.0 FOR ALL SYSTEMS, EXCEPTING THE GAS PIPING SHALL HAVE AN IMPORTANCE FACTOR OF 1.5. 12. PROVIDE EACH INDIVIDUAL GRILLE, REGISTER, DIFFUSER AND OUTSIDE AIR CONNECTION WITH A VOLUME DAMPER OR OTHER MEANS OF ADJUSTMENT AS REQUIRED BY 2015 IMC, SECTION 603.18. 13. HVAC DISTRIBUTION SYSTEMS SHALL BE BALANCED TO MINIMIZE THROTTLING LOSSES AS REQUIRED BY 2015 WSEC SECTION C408.2.2 14. FUNCTIONAL TESTING OF ALL MECHANICAL SYSTEMS SHALL BE PROVIDED TO ENSURE PROPER OPERATION IN ALL SEQUENCES OF OPERATION, INCLUDING POWER FAILURE AS REQUIRED BY 2015 WSEC SECTION C408.2.3. SYSTEMS COMMISSIONING PROVIDE COMMISSIONING PER SECTION C408 OF THE WSEC COMMERCIAL PROVISIONS. COPIES OF ALL EQUIPMENT DATA AND DOCUMENTATION THAT RELATES TO COMMISSIONING, SHALL BE PROVIDED TO THE OWNER AND MADE AVAILABLE TO THE AHJ WITHIN 90 DAYS OF RECEIPT OF COO, INCLUDING: 1. COMMISSIONING (Cx) PLAN, PRELIMINARY Cx REPORT, Cx COMPLIANCE CHECKLIST (2015 WSEC FIGURE C408.1.4.2) AND RELATED REPORTS, SUCH AS AIR BALANCING, START-UP AND PRESSURE TESTING DATA. 2. RECORD DRAWINGS DEPICTING FINAL INSTALLATION CONFIGURATIONS OF SYSTEMS AND EQUIPMENT AS REQUIRED BY 2015 WSEC SECTION C103.6. 3. IOM EQUIPMENT MANUALS SHALL INCLUDE MFG INFORMATION WITH MODEL NUMBERS AND OPTIONS, CONTROLS DATA, INCLUDING CALIBRATION AND DESIGN SETPOINT INFORMATION, AND RECOMMENDED MAINTENANCE SCHEDULE WITH CSUSA NW CONTACT INFORMATION. 4. TRAINING OF THE MAINTENANCE STAFF SHALL BE PROVIDED, INCLUDING REVIEW OF DOCUMENTATION, HANDS-ON DEMONSTRATION OF OPERATION AND START-UP PROCEDURES AND A TRAINING COMPLETION REPORT. 5. WHOLE BUILDING AND COMMISSIONING OF SYSTEMS THAT ARE NOT INCLUDED IN THE MECHANICAL CONTRACTOR'S SOW SHALL BE PROVIDED, IN ACCORDANCE WITH 2015 WSEC SECTION C408.1, BY OTHERS. 6. COMMISSIONING OF MECHANICAL SYSTEMS AND CONTROLS SHALL BE PROVIDED BY A CERTIFIED COMMISSIONING PROFESSIONAL AS REQUIRED FOR BUILDINGS WITH TOTAL COOLING CAPACITY OVER 240 MBH OR TOTAL HEATING CAPACITY OVER 300 MBH PER 2015 WSEC SECTION C408.1. THE PROPOSED PROJECT AT 21300 HIGHWAY 99, EDMONDS, WA CONSISTS OF A NEW TWO STORY REPLACEMENT STRUCTURE OF APPROXIMATELY 48,086 GROSS SQUARE FEET OF AUTOMOTIVE SALES, SERVICE AND PARTS SUPPORT. THE PROJECT ALSO INCLUDES ALL INFRASTRUCTURE AND SITE WORK NECESSARY TO SUPPORT THE STRUCTURE. BUILDING INF PROJECT ADDRESS: MAGIC TOYOTA 21300 HIGHWAY 99 EDMONDS, WA 98020 PROPERTY OWNER: BROADUS FAMILY LLC 120 - 116TH AVE NE BELLEVUE, WA 98004 TEL 425-775-4422 CONTACT: DAVID BROADUS SNO CO TAX PARCEL: 00580700000601 00580700000602 00580700000604 00580700000605 00580700000607 00580700000608 CITY OF EDMONDS, LOT LINE ADJUSTMENT PLN20170016 AND AS FILED WITH SNOHOMISH COUNTY AS DOCUMENT 201705165010 CREATING LOT 1 AND LOT 2 WAS FILED AND RECORDED ON 16 MAY 2017. AS OF THIS RE -SUBMITTAL OF PERMIT ISSUE DRAWINGS THE COUNTY HAS NOT ISSUED NEW PARCEL NUMBERS FOR THE AFFECTED PARCELS LISTED ABOVE. ZONING: GC-2 CONSTRUCTION TYPE: B/S-1 FIN FLR ELEV: +100'-0" (FIRST FLR) & +112'-10° (SECOND FLR) PARAPET ELEV: +128'-0" CLIMATE ZONE: 4C SNOHOMISH (WSEC TABLE C301.1) MECHANICAL SCOPE NEW MECHANICAL HVAC SYSTEMS TO SUPPORT CONSTRUCTION OF A 2 STORY STRUCTURE CONSISTING OF A SALES FLOOR, GENERAL OFFICE SPACE, A PARTS DEPARTMENT, SERVICE AREA AND PARKING DECK. MECHANICAL WORK INCLUDES THE FOLLOWING: 1. HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS TO SERVE THE AUTO SHOW ROOM AND OFFICE SPACES AS SHOWN ON THESE DRAWINGS. 2. EXHAUST SYSTEMS FOR RESTROOMS, BREAK ROOMS AND SERVICE AREA. 3. DUCTLESSS MINI SPLIT SYSTEM AIR-CONDITIONING UNITS FOR SMALL SERVER AND EQUIPMENT ROOMS. 4. AN IN SLAB HOT WATER (HYDRONIC) RADIANT HEATING SYSTEM IN THE SERVICE AND NEW CAR DELIVERY AREAS. 5. AN IN GROUND HOT WATER (HYDRONIC) RADIANT HEATING SYSTEM FOR SNOW MELT, TWO LOCATIONS. 6. ALL ASSOCIATED DUCTWORK, PIPING, GRILLES, REGISTERS, DIFFUSERS, ACCESSORIES AND STAND-ALONE CONTROLS, AS REQUIRED, FOR A COMPLETE INSTALLATION. 7. EQUIPMENT START-UP, AIR BALANCE, PROGRAMMING AND TRAINING FOR NEW EQUIPMENT, O&M MANUALS. ��1�:7_1 R1ml[HIX 1. COORDINATE ALL NEW WORK WITH THE STRUCTURE AND OTHER TRADES. FIELD VERIFY UNIT LOCATIONS, DROPS AND POSITIONS. HVAC EQUIPMENT WEIGHTS AND LOCATIONS SHALL BE APPROVED BY STRUCTURAL ENGINEER. 2. EQUIPMENT LOCATIONS, PIPE AND DUCTWORK DIMENSIONS SHOWN ON PLANS AND DETAILS ARE NOMINAL SIZES. 3. MAX FLEX DUCT LENGTH SHALL BE 8'-0". SUPPLY AND RETURN AIR DUCTWORK SHALL BE LINED WITH 1" SOUND LINER (SL) WITHIN 10' OF EQUIPMENT. 4. AN ACCESSIBLE GAS SHUT-OFF VALVE SHALL BE INSTALLED WITHIN 3' OF ALL GAS APPLIANCES. GAS PIPING SHALL RUN BELOW THE ROOF, UNLESS NOTED OTHERWISE. 5. HEATING AND COOLING LOAD CALCULATIONS USE THE FOLLOWING DESIGN TEMPERATURES IN ACCORDANCE WITH 2015 WSEC AND THE ASHRAE RECOMMENDED OUTDOOR DESIGN TEMPERATURES FOR WASHINGTON: SUMMER OSA: 83°F DB / 65F WB SA HEATING: 95°F MAX WINTER OSA: 247 DB SA COOLING: 55°F MIN 6. ROOM SENSORS SHALL BE MOUNTED ON WALLS NO MORE THAN 48" ABOVE FINISHED FLOOR FOR ADA ACCESSIBILITY, AS REQUIRED. 7. ALL LINE VOLTAGE WORK SHALL BE BY ELECTRICIAN (SEPARATE PERMIT). A 120-VOLT SERVICE RECEPTACLE SHALL BE LOCATED WITHIN 25' OF VICINITY MAP I I\VULV I JI 1 L APN 000140-0036 8. ALL DUCT MOUNTED SMOKE DETECTORS SHALL BE SUPPLIED AND INSTALLED BY THE MECHANICAL CONTRACTOR. SMOKE DETECTOR WIRING SHALL BE BY ELECTRICIAN; SIGNAL SHALL BE RECEIVED BY FIRE AND LIFE SAFETY. ALL FIRE/SMOKE DAMPERS AND SMOKE DETECTORS SHALL BE POWERED BY OTHERS. 9. SEE A-0.3 FOR REFERENCE TO AIR BARRIER NOTES AND ALLOWABLE INFILTRATION AT THE BULDLING ENVELOPE. LEGAL DESCRIPTION SOLNERS 5 ACRE TRACTS BLK 000 D-01- N 317 FT OF W 3 AC EXC 20 FT THOF. NE � Of THE NW � SECTION 29, TOWNSHIP 27N RANGE E4, W.M. APPLICABLE CODES 1. 2015 WASHINGTON STATE ENERGY CODE (WAC) CHAPTER 51-11) 2. 2015 INTERNATIONAL BUILDING CODE (WAC CHAPTER 51-50) 3. 2015 INTERNATIONAL MECHANICAL CODE (WAC CHAPTER 51-52), 4. 2015 INTERNATIONAL FUEL GAS CODE (WAC CHAPTER 51-52) 5. 2015 UNIFORM PLUMBING CODE (WAC CHAPTER 51-56) DRAWING INDEX SHEET # SHEET TITLE SCALE M001 MECHANICAL COVER SHEET N/A M002 MECHANICAL EQUIPMENT SCHEDULES N/A M003 MECHANICAL EQUIPMENT SCHEDULES N/A M004 MECHANICAL HVAC LOAD CALCULATIONS N/A M005 MECHANICAL HVAC LOAD CALCULATIONS N/A M006 ENERGY CODE COMPLIANCE FORMS N/A M007 ENERGY CODE COMPLIANCE FORMS N/A M100 MECHANICAL FIRST FLOOR PLAN - NORTH 1/8"=1'-0" M101 MECHANICAL FIRST FLOOR PLAN - SOUTH 1/8"=1'-0" M 102 MECHANICAL SECOND FLOOR PLAN - NORTH 1 /8"=1'-0" M103 MECHANICAL SECOND FLOOR PLAN - SOUTH 1/8"=1'-0" M104 MECHANICAL ROOF PLAN - NORTH 1/8"=1'-0" M105 MECHANICAL ROOF PLAN - SOUTH 1/8"=1'-0" M300 RADIANT PIPING LAYOUT - NORTH 1/8"=1'-0" M301 RADIANT PIPING LAYOUT - SOUTH 1/8"=1'-0" M302 RADIANT PIPING LAYOUT - EXTERIOR 3/32"=1'-0" M303 RADIANT PIPING SCHEMATIC DIAGRAM N/A M400 MECHANICAL DETAILS AS NOTED COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. z., 0 2 CDO W co Lu m Cn 00 N = i- m d. Qz �o N O Q QzS v w Q W cj w W E- p WU W firy W IL 3 oo zm Qo �00 2 i 0 � L 00 � SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL 08/11/2017 JOB NUMBER 117036 SHEET TITLE MECHANICAL COVER SHEET SHEET NUMBER COPYRIGHT NOTICE HEAT PUMP SCHEDULE TAG MANUFACTURER AND MODEL LOCATION DESCRIPTION MIN COOLING PERFORMANCE MIN HEATING PERFORMANCE R-410A PIPING MAX INDOOR FAN AIRFLOW (CFM) MAX SOUND (dB -A) CONTROLLER TYPE FILTER TYPE 60 HERTZ ELECTRICAL WEIGHT (LBS) NOTES: LIQUID (IN) SUCTION (IN) MAX LENGTH (FEET) TOTAL (MBH) SEER EER TOTAL (MBH) HSPF VOLT PH MCA AH-1 MITSUBISHI MSZ-GL15NA-Ul 223 - ELEV EQUIP RM DUCTLESS WALL 14,000 21.6 18,000 11.7 0.25 0.50 65 533 49 WIRELESS REMOTE ANTI ALLERGY ENZYME 208/230 1 1 22 1, 2, 3, 4, 5, 6, 7, 8, 9 CU-1 MITSUBISHI MUZ-GL15NA-Ul ROOF OUTDOOR UNIT 51 10 81 AH-2 MITSUBISHI MSZ-GL15NA-Ul 218 - IT RM DUCTLESS WALL 14,000 21.6 18,000 11.7 0.25 0.50 65 533 49 WIRELESS REMOTE ANTI ALLERGY ENZYME 208/230 1 1 22 1, 2, 3, 4, 5, 6, 7, 10 CU-2 MITSUBISHI MUZ-GL15NA-Ul ROOF OUTDOOR UNIT 51 10 81 AH-3 MITSUBISHI SLZ-KA15NA 171 - TECH LOUNGE CEILING CASSETTE 15,000 16.0 18,000 9.6 0.25 0.50 65 390 40 WIRED REMOTE POLYPRO HONEYCOMB 208/230 1 1 36 1, 2, 3, 4, 5, 6, 7, 8 CU-3 MITSUBISHI SUZ-KA15NA ROOF OUTDOOR UNIT 51 12 80 AH-4 MITSUBISHI SLZ-KA15NA 148 - WORK RM CEILING CASSETTE 15,000 16.0 18,000 9.6 0.25 0.50 65 390 40 WIRED REMOTE POLYPRO HONEYCOMB 208/230 1 1 36 1, 2, 3, 4, 5, 6, 7, 8 CU-4 MITSUBISHI SUZ-KA15NA ROOF OUTDOOR UNIT 51 12 80 AH-5 MITSUBISHI SLZ-KA15NA 147 - T&I CEILING CASSETTE 15,000 16.0 18,000 9.6 0.25 0.50 65 390 40 WIRED REMOTE POLYPRO HONEYCOMB 208/230 1 1 36 1, 2, 3, 4, 5, 6, 7, 8 CU-5 MITSUBISHI SUZ-KA15NA ROOF OUTDOOR UNIT 51 12 80 AH-6 MITSUBISHI SLZ-KA15NA 145 - SUPPORT CEILING CASSETTE 15,000 16.0 18,000 9.6 0.25 0.50 65 390 40 WIRED REMOTE POLYPRO HONEYCOMB 208/230 1 1 36 1, 2, 3, 4, 5, 6, 7, 8 CU-6 MITSUBISHI SUZ-KA15NA ROOF OUTDOOR UNIT 51 12 80 AH-7 MITSUBISHI SLZ-KA15NA 144 - SERVICE MGR CEILING CASSETTE 15,000 16.0 18,000 9.6 0.25 0.50 65 390 40 WIRED REMOTE POLYPRO HONEYCOMB 208/230 1 1 36 1, 2, 3, 4, 5, 6, 7, 8 CU-7 MITSUBISHI SUZ-KA15NA ROOF OUTDOOR UNIT 51 12 80 NOTES: 1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 2. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH AND CONVENIENCE OUTLET, AS APPLICABLE. 3. INCLUDES SINGLE POINT ELECTRICAL CONNECTION; INDOOR UNIT IS POWERED FROM OUTDOOR UNIT. 4. HEATING PERFORMANCE FOR HEAT PUMP ONLY AT HIGH HEAT, RATED IN ACCORDANCE WITH ARI STANDARD 340/360-7 AS APPROPRIATE. 5. PROVIDE WITH AFTER MARKET CONDENSATE PUMP; ROUTE CONDENSATE TO AN APPROVED LOCATION. 6. PROVIDE WITH MANUFACTURER'S RECOMMENDED ACCESSORIES FOR LOW AMBIENT COOLING APPLICATIONS. 7. PROVIDE WITH LOCKING REFRIGERANT CIRCUIT ACCESS PORT CAPS PER 2015 IMC SECTION 1101.10. 8. NO AIR SIDE ECONOMIZER IS PROVIDED PER 2015 WSEC SECTION C403.3.1 EXCEPTION 1 FOR QUALIFYING SMALL EQUIPMENT UNDER 33 MBH AND AT LEAST 15% MORE EFFICIENT THAN THE BASELINE CODE. 9. CONFIRM COOLING CAPACITY BASED ON FINAL ELEVATOR EQUIPMENT SELECTED BY OTHERS. 10. NO AIR SIDE ECONOMIZER IS PROVIDED PER 2015 WSEC SECTION C403.4 EXCEPTION 5 FOR EQUIPMENT TO COOL SERVER, ELECTRICAL AND TELECOM ROOMS AND AT LEAST 15% MORE EFFICIENT THAN THE BASELINE CODE. ELECTRIC WALL HEATER SCHEDULE TAG MANUFACTURER AND MODEL SIZE (IN) APPLICATION SIZE (IN) W x HT CAPACITY (BTU/HR) CAPACITY (WATTS) 60 HZ ELECTRICAL DATA MOUNTING WEIGHT (LBS) NOTES: VOLTS PHASE AMPS EWH-1 QMARK CWH1101DSF 151 - SPRINKLER RISER RM 10.5"xl2" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 EWH-2 QMARK CWH1101DSF 100 - VESTIBULE 10.5"xl2" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 EWH-3 QMARK CWH1101DSF 102 - VESTIBULE 10.5"xl2" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 EWH-4 QMARK CWH1101DSF 170 - TECH TOILET 10.5"xl2" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 EWH-5 QMARK CWH1101DSF 169 - TECH TOILET 10.5"xl2" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 EWH-6 QMARK CWH1101DSF 168 - TECH LOCKER 10.5"x 12" 1706 500 120 1 4.2 RECESSED 10 1, 2, 3 NOTES: 1. HEATERS MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 2. UNIT TO BE RECESSED MOUNTED IN BACK BOX. 3. THERMOSTAT IS INTEGRAL TO THE UNIT. 4. FRONT COVER TO BE POWDERED COATED WHITE, UNLESS NOTED OTHERWISE. LOUVERS SCHEDULE TAG MANUFACTURER AND MODEL LOCATION SIZE W x (IN) HT FACE SIZE SQ FT FREE AREA SQ FT MAX CFM FPM INTAKE OR EXHAUST NOTES: L-1 RUSKIN ACL 1245 SOUTH EXTERIOR 18 x 18 2.25 1.12 195 175 INTAKE 1, 2, 3, 4 L-2 RUSKIN ACL 1245 SOUTH EXTERIOR 88 x 36 22.0 11.0 4,160 380 INTAKE 1, 2, 3, 4 L-3 RUSKIN ACL 1245 SOUTH EXTERIOR 18 x 18 2.25 1.12 330 295 EXHAUST 1, 2, 3, 4 L-4 RUSKIN ACL 1245 SOUTH EXTERIOR 88 x 36 22.0 11.0 4,160 380 INTAKE 1, 2, 3, 4 L-5 RUSKIN ACL 1245 WEST EXTERIOR 40.5 x 36 10.1 5.05 1,920 380 INTAKE 1, 2, 3, 4 L-6 RUSKIN ACL 1245 EAST EXTERIOR 40.5 x 36 10.1 5.05 1,920 380 INTAKE 1, 2, 3, 4 L-7 RUSKIN ACL 1245 EAST EXTERIOR 40.5 x 36 10.1 5.05 1,920 380 INTAKE 1, 2, 3, 4 L-8 RUSKIN ACL 1245 EAST EXTERIOR 40.5 x 36 10.1 5.05 1,920 380 INTAKE 1, 2, 3, 4 L-9 RUSKIN ACL 1245 EAST EXTERIOR 18 x 18 2.25 1.12 330 295 INTAKE 1, 2, 3, 4 NOTES: 1. RUSKIN LOUVERS MAY BE SUBSTITUTED DEPENDING ON AVAILABILITY, OR SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 2. PROVIDE WITH BIRDSCREEN 3. PROVIDE WITH LOW LEAK CLASS 1A MOTORIZED DAMPER AT BUILDING ENVELOPE. 4. COLOR TO BE STANDARD MANUFACTURER COLOR SELECTED BY ARCHITECT, CUSTOM COLORS PROVIDED BY OTHERS. GRILLES. REGISTERS AND DIFFUSERS SCHEDULE TAG MANUFACTURER MODEL NECK SIZE (IN) FACE SIZE (IN) MAX AIRFLOW CFM THROW PATTERN BORDER TYPE MOUNTING NOTES: LD1 TITUS MCD 12" 48"x4" 475 VERTICAL T-BAR DROP IN 1, 2, 3 LD2 TITUS MCD 8" 48%4" 475 VERTICAL NONE RECESSED 1, 2, 3 LD3 TITUS MCD loll 48%4" 475 VERTICAL NONE RECESSED 1, 2, 3 CD1 TITUS MCD 6" 24"x24" 100 4 WAY T-BAR DROP IN 1, 2, 3 CD2 TITUS MCD 8" 24"x24" 200 4 WAY T-BAR DROP IN 1, 2, 3 CD3 TITUS MCD 10" 24"x24" 350 4 WAY T-BAR DROP IN 1, 2, 3 CD4 TITUS MCD 6" 12"xl2" 100 4 WAY HARD LID SURFACE 1, 2, 3 CD5 TITUS MCD 8" 12"xl2" 200 4 WAY HARD LID SURFACE 1, 2, 3 SD1 TITUS S301 - 12%3" 100 HORIZONTAL NONE DUCT 1, 2, 3 RG1 TITUS 50F - 24"x12" - - T-BAR DROP IN 1, 2, 3, 4 RG2 TITUS 50F - 48"x24" - - T-BAR DROP IN l , 2, 3, 4 EG1 TITUS PAR 6" 12"xl2" 100 - HARD LID SURFACE 1, 2, 3 EG2 TITUS PAR 8" 12%12" 200 - HARD LID SURFACE 1, 2, 3 EG3 TITUS PAR 10" 1 12%12" 1 350 - HARD LID SURFACE 1, 2, 3 NOTES: 1. GRD'S 2. REFER 3. FINISH 4. INSTAL L MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. TO FLOOR PLANS FOR DESIGN AIR FLOWS. COLOR TO BE WHITE UNLESS NOTED OTHERWISE. WITH SOUND LINED RETURN BOOT TO PLENUM. THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. Q rn Q 0 o co N 2 O o 0 W co w m w 00 N = i- rn d Qz �o N O Q WQ°° W Lo W E- pfi - d' U W U) firLL yW zm ooLL o s 0 bm SIGNED: 8/11 /2017 1:11 AlF/ &71 Cs] k,F.� 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11/2017 tOB AlRIBER SHEET TITLE MECHANICAL. EQUIPMENT SCHEDULES SHEET NUMBER 15T 7.5T 4T 6T 7.5T PACKAGED ROOFTOP UNIT SCHEDULE TAG MAKE AND MODEL DESCRIPTION DESIGN AIRFLOW UNIT FAN PERFORMANCE UNIT COOLING CAPACITY UNIT HEATING CAPACITY - MODULATING GAS FILTRATION ELECTRICAL DATA (60 HZ) SOUND RATING (dBA) WEIGHTS NOTES OSA (CFM) SA (CFM) SA (CFM) ESP (IN WG) BHP FLA TOTAL (MBH) SENS (MBH) ARI EER IEER INPUT (MBH) OUTPUT (MBH) EFFICIENCY % CONN SIZE (INCHES) DISPOSABLE # / SIZE VOLTS PH MCA MOCP BASE UNIT (LBS) TOTAL OPERATING (LBS) RTU-1 CARRIER 48TCDD 16B2A6-6UOGO GAS/DX ROOFTOP 538 6,104 6,000 0.50 2.66 4.9 184.78 137.04 10.80 12.4 180 146 81 3/4" 6 / 18x24x2 460 3 36 45 87 1,380 1,733 1, 2, 3, 4, 5, 6, 8, 9, 10 RTU-2 CARRIER 48TCDD08B2A6-6UOGO GAS/DX ROOFTOP 329 2,390 3,000 0.50 1.65 3.8 90.1 68.90 11.00 12.8 125 103 82 3/4" 4 / 16x2Ox2 460 3 20 25 82 835 1,092 1, 2, 3, 4, 5, 6, 8, 9, 10 RTU-3 CARRIER 48KCDA05A2A6-6UOAO GAS/DX ROOFTOP 343 1,588 1,600 0.50 0.78 2.5 48.73 37.51 14.0 SEER - 72 59 82 1 /2" 2 / 16x25x2 460 3 12 15 81 544 719 1, 2, 3, 4, 7, 8, 9, 10 RTU-4 CARRIER 48HCED07B2A6-6UOGO GAS/DX ROOFTOP 626 2,489 2,400 0.50 1.07 3.8 74.74 56.79 12.00 16.0 125 103 82 3/4" 4 / 16x2Ox2 460 3 16 20 82 590 765 1, 2, 3, 4, 5, 6, 8, 9, 10 RTU-5 CARRIER 48TCDD08B2A6-6UOGO GAS/DX ROOFTOP 491 3,177 3,000 0.50 1.65 3.8 90.1 68.90 11.00 12.8 125 103 82 3/4" 4 / 16x2Ox2 460 3 20 25 82 835 1,092 1, 2, 3, 4, 5, 6, 8, 9, 10 NOTES: 1. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 2. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT, AND POWERED CONVENIENCE OUTLET, AS APPLICABLE. 3. PROVIDE WITH MANUFACTURER'S 14" TALL ROOF CURB. 4. PROVIDE WITH MANUFACTURER'S ECONOMIZER OPTION (CLASS 1 A ULTRA LOW LEAK AND BAROMETRIC RELIEF). 5. PROVIDE WITH FACTORY MOUNTED RETURN AIR SMOKE DETECTOR. 6. PROVIDE WITH MANUFACTURER'S MEDIUM STATIC FAN OPTION WITH VFD CONTROLLER. 7. PROVIDE WITH MANUFACTURER'S MEDIUM STATIC FAN OPTION. 8. PROVIDE WITH MANUFACTURER'S DRY-BULB ECONOMIZER CONTROL OPTION. 9. PROVIDE WITH WALL -MOUNTED, 7-DAY PROGRAMMABLE THERMOSTAT AT 48" AFF MAX, HONEYWELL VISION PRO 8320 OR EQUAL. 10. INSTALL EACH UNIT WITH NATURAL GAS PRESSURE REGULATOR (INLET PRESSURE = 2 PSIG, OUTLET PRESSURE RANGE ADJ 5" WC MIN - 13" MAX). SEE PLUMBING DESIGN. EXHAUST FAN SCHEDULE COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. FAN PERFORMANCE ELECTRICAL DATA (60 HZ) 14 FLOW ESP FAN POWER FAN DRIVE MOTOR VOLTS PHASE FLA MOCP SOUND WEIGHT TAG MANUFACTURER AND MODEL DESCRIPTION APPLICATION SERVING (CFM) (IN WG) (HP OR W) RPM (HP) (dBA) (LBS) NOTES: EF-1 COOK FAN SQND-EC, #100SQN17DEC CENTRIFUGAL SQUARE INLINE TOILET RM EXHAUST RMS 168, 169, 170, 171 570 0.50 98W 1554 DIRECT 1/4 115 1 5.8 15 53 57 1, 2, 3, 5, 7, 8 EF-2 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM/CAFE EXHAUST RMS 104, 124, 125 370 0.50 73W 1406 DIRECT 1/4 115 1 5.8 15 55 22 1, 2, 3, 4, 5, 7, 8 EF-3 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM/JAN RM EXHAUST RMS 202, 203 100 0.50 31W 1241 DIRECT 1/4 115 1 5.8 15 51 22 1, 2, 3, 4, 5, 7, 8 (o EF-4 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM EXHAUST RMS 207, 210, 211 370 0.50 73W 1406 DIRECT 1/4 115 1 5.8 15 55 22 1, 2, 3, 4, 5, 7, 8 2 416J EF-5 COOK FAN ACE-B VFD, #490C11 B ROOFTOP DOWNBLAST SERVICE GARAGE EXHAUST RMS 140, 141, 142, 143, 161 18,750 0.50 3.61 HP 344 BELT 5 460 3 7.6 15 64 437 1, 2, 3, 4, 5, 6, 8, 9, 10 G CA CA EF-6 COOK FAN SQND-EC, #100SQN17DEC CENTRIFUGAL SQUARE INLINE ELEC/CO-GEN EXHAUST RM 181 600 0.50 105W 1586 DIRECT 1/4 115 1 5.8 15 52 57 1, 2, 3, 5, 7, 8 4) EF-7 COOK FAN SQND-EC, #135SQN17DEC CENTRIFUGAL SQUARE INLINE NEW CAR DELIVERY EXHAUST RM 117 1040 0.50 166W 1091 DIRECT 3/4 115 1 13.8 20 51 95 1, 2, 3, 4, 5, 6, 8, 9, 11 I (o EF-8 COOK FAN S ND -EC 90S N17DEC CENTRIFUGAL SQUARE INLINE COMPRESSOR LOBE RM EXH RM 180 200 0.50 47W 1462 DIRECT 1 6 115 1 4.4 15 50 95 1 2 3 5 7 80 >0 bm '~ EF-9 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST MECHANICAL ROOM EXHAUST RM 231 470 0.50 96W 1508 DIRECT 1/4 115 1 5.8 15 56 22 1, 2, 3, 4, 5, 7, 8 0 Wo Z NOTES: 1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 2. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH, EMERGENCY POWER PROVISIONS AND CONVENIENCE OUTLET, AS APPLICABLE. 3. EXHAUST FANS SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. ON/OFF SCHEDULING BY PROGRAMMABLE TIMER. TIME CLOCK WIRED BY ELECTRICIAN/PROVIDED 4. PROVIDE WITH MANUFACTURER'S OPTIONAL 14" ROOF CURB, OUTLET GUARD AND/OR BIRD SCREEN. 5. PROVIDE WITH CLASS 1A LOW LEAK MOTORIZED DAMPER (120V) AT BUILDING ENVELOPE EXHAUST DUCT PENETRATION AS REQUIRED PER 2015 WSEC SECTION C403.2.4.3. 6. PROVIDE WITH MANUFACTURER'S PREMIUM EFFICIENCY VFD RATED MOTOR. 7. EXHAUST FAN MOTORS SHALL BE PROVIDED WITH MANUFACTURER'S OPTIONAL SPEED CONTROLLER. [:l'/L100]MTO101[i%1� 8. PROVIDE EXHAUST FAN WITH ELECTRONICALLY COMMUTATED (ECM) MOTORS AS REQUIRED BY 2015 WSEC SECTION C403.2.10.3 FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE 1 /12 HORSEPOWER AND LARGER. 9. CONTROL BY UL LISTED TOXIC GAS SENSORS FOR CARBON MONOXIDE AND NITROUS DIOXIDE, LOCATED AS SHOWN ON THE FLOOR PLANS (HONEYWELL E3POINT OR EQUAL). FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS AT 20 HZ MINIMUM SPEED OR 0.05 CFM/SF, WHICHEVER IS GREATER. DURING ALL OCCUPIED HOURS, FAN SHALL RUN AT 60 HZ (FULL SPEED) UPON DETECTION OF GAS LEVELS AT OR ABOVE ACCEPTABLE LEVELS UNTIL LEVELS BELOW THE ACCEPTABLE LIMITS ARE REACHED OR FOR A MINIMUM RUN TIME OF 10 MINUTES. FULL SPEED ACTIVATION SHALL BE BASED ON A CO LEVELS OF 35 PPM OR HIGHER AND ON NO2 LEVELS AS DICTATED BY THE 8 HOUR OSHA PERMISSIBLE EXPOSURE LIMIT OR HIGHER. 10. SERVICE GARAGE EXHAUST SYSTEM HAS BEEN SIZED IN ACCORDANCE WITH 2O15 IMC SECTION 404.2 AT 0.75 CFM/SF X 24,950 SF = 18,750 CFM MINIMUM EXHAUST AIRFLOW. 11. NEW CAR DELIVERY EXHAUST SYSTEM HAS BEEN SIZED IN ACCORDANCE WITH 2O15 IMC SECTION 404.2 AT 0.75 CFM/SF X 1,386 SF = 1,040 CFM MINIMUM EXHAUST AIRFLOW. SUPPLY FAN SCHEDULE TAG COOK FAN SAND -EC, #100SQN17DEC MANUFACTURER AND MODEL DESCRIPTION APPLICATION SERVING FAN PERFORMANCE ELECTRICAL DATA (60 HZ) SOUND (dBA) WEIGHT (LBS) NOTES: FLOW (CFM) ESP (IN WG) FAN POWER (HP OR W) FAN RPM DRIVE MOTOR (HP) VOLTS PHASE FLA MOCP SF-1 COOK FAN SQND-EC, #90SQN 17DEC CENTRIFUGAL SQUARE INLINE DEDICATED OUTSIDE VENT AIR RMS 144, 145, 147, 148, 150, 151 130 0.375 24W 1221 DIRECT 1 /6 115 1 4.4 15 46 95 1, 2, 3, 4, 5, 6 SF-2 COOK FAN SQND-EC, #100SQN17DEC CENTRIFUGAL SQUARE INLINE DEDICATED OUTSIDE VENT AIR RMS 168, 169, 170, 171 490 0.375 66W 1342 DIRECT 1/4 115 1 5.8 15 48 57 1, 2, 3, 4, 5, 6 NOTES: 1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS. 1. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH, EMERGENCY POWER PROVISIONS AND CONVENIENCE OUTLET, AS APPLICABLE. 2. SUPPLY FANS SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. ON/OFF SCHEDULING BY PROGRAMMABLE TIMER. TIME CLOCK WIRED BY ELECTRICIAN/PROVIDED BY MECHANICAL. LEAK MOTORIZED DAMPER (120V) AT BUILDING ENVELOPE EXHAUST DUCT PENETRATION AS REQUIRED PER 2015 WSEC SECTION C403.2.4.3. BE PROVIDED WITH MANUFACTURER'S OPTIONAL SPEED CONTROLLER. LECTRONICALLY COMMUTATED (ECM) MOTORS AS REQUIRED BY 2015 WSEC SECTION C403.2.10.3 FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE 1 /12 K "i� /i► ' iIii► z., n o 0 W N W m fn � N = 00 Q z =) O Y N O Q O N 2 =) M co OCn o u W w � 0_of V z>_ w W fi `� OLL 00 zm 0 U fl- 00 SIGNED: 8/11 /2017 I :Z =kyI&A Cs] 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11 /2017 JOB NUMBER 117036 SHEET TITLE MECHANICAL EQUIPMENT SCHEDULES SHEET NUMBER r System Sizingr T- Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AM Air System Name - - -- - -- - - ---- -- - -- - - -- - - - RTU-1 --- - Equipment Class .._._._._ ._._._.__._._ ._.._.._._._.__. PKG ROOF Air System TYP e---------------- ---- -- ---- SZCAV Sizing Calculation Information Calculation Months _______________________ Jan to Dec Sizing Data --- _ ------- - ----- _ _.. -_ _- _ Calculated Central Cooling Coil Sizing Data Total coil load . _ _ -- . ___ ---- ------------------- ._ 12.3 Tons Total coil load 147.3 MBH Sensible coil load -------- 141.8 MBH Coil CFM at Oct 1300 __ __ __ __ 6104 CFM Max block CFM ---------------- _.___ _---_-- -__. 6104 CFM Sum of peak zone CFM _________________________ 6104 CFM Sensible heat ratio ---------------- --------------- __._. __.___ 0.963 ft2/Ton------- -- ---- - ----- -------- ----- -263.2 BTU/(hr•ft2) ......... ....__. --------------- --------- 45.6 Water flow @ 10.0 OF rise ________________________ N/A Central Heating Coil Sizing Data Max coil load - --------------------- 72.7 MBH Coil CFM at Des Htg _.__________ -...------..-- ____.._.....--6104 CFM Max coil CFM --- -- - - - - ----- ---------6104 CFM Water flow @ 20.0 OF drop - -------------------------- ------------------- N/A Supply Fan Sizing as Actual max CFM------- -------------------------------------------------------- 6104 CFM Standard CFM 6022 CFM ActualCFM/ft2max - -- -- 1 89 t2 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM-----------------------_---------------------------- 538 CFM CFM/ft2 ____ _ 0.17 CFM/ft2 Number of zones-------------------------------------1 Floor Area _.. -... --.... ----. -- --- 3232.0 ft2 Location ------------------------ Edmonds, Washington Zone CFM Sizing __________ Sum of space airflow rates Space CFM Sizing -------- Individual peak space loads Load occurs at _.------------------------------------------------------------- Oct 1300 OA DB / WB----------- -75.6 / 60.3 OF Entering DB / WB --.... _.. 76.4 160.5 °F Leaving DB / WB - ____ _____ _______ 54.6 / 51.6 OF Coil ADP ---------------- ------ ------- 49.2 OF Bypass Factor 0.198 Resulting RH --- --- ----- ----- - ------ ------------ 39 % Design supply temp. --------- -- - -- - - - 55.0 OF Zone T-stat Check _____ ____.1 of 1 OK Max zone temperature deviation _____________________ 0.0 OF Load occurs at---------------------------------- Des Htg 2 BTU/(h)aft- -- - -- - - - 22.5 Ent. DB / Lvg DB - - - - - - 67.4 / 78.5 OF Fan motor BHP ----------------------------------------------------- 1.00 BHP Fan motor kW - - - - 0.80 kW Fan static ----------------------------------------------------- 0.60 in wg CFM/ erson---__-------__-------_---------_---------_---- 26.89 CFM/ erson P P RTU-1 Hourly Analysis Program v5.01 Page 1 of 15 Air System Sizingr Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AM Air System Name _______________________________ RTU-4 Equipment Class .______ ____ ____.__. PKG ROOF Air System Type ------------ -- ---- -- ---- SZCAV Sizing Calculation Information Calculation Months ____ ____ __ __ Jan to Dec Sizing Data ----- ----------- ------ _ _---__- _-Calculated Central Cooling Coil Sizing Data Total coil load ---- _----------_--------------- --------------------------------- 5.8 Tons Total coil load 69.3 MBH Sensible coil load -------- _____ ------ 60.3 MBH Coil CFM at Jun 1500 _____ _ 2489 CFM Max block CFM ------------ _._._. __.__ __.__. 2489 CFM Sum of peak zone CFM _________________________ 2489 CFM Sensible heat ratio ____ -___-- ------- ------ 0.870 ft2/Ton------- -- -- ---------649.8 BTU/(hr•ft2)......... ------------- --- ---------------------------- --18.5 Water flow @ 10.0 OF rise ________________________ N/A Central Heating Coil Sizing Data Max coil load ---------------- 39.3 MBH Coil CFM at Des Htg ------ .--------- .--------------- .--------------- _._-. 2489 CFM Max coil CFM - - - - - - - - - - - 2489 CFM Water flow @ 20.0 OF drop --------------------------------------- N/A Supply Fan Sizing Data Actual max CFM------- -------------------------------------------------------- 2489 CFM Standard CFM 2456 CFM Actual max CFM/ft2------------------------------------------------------------ 0.66 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM------------- ----------------------------------------------- 626 CFM CFM/ft2 0.17 CFM/ft2 Number of zones ----- --- ----- -- - - - - - - -- - - - - -1 Floor Area _.. -... ---... ---...----- ......_ 3751.0 ft2 Location ------------------------ Edmonds, Washington Zone CFM Sizing _______ Sum of space airflow rates Space CFM Sizing _- __. Individual peak space loads Load occurs at---------------------------------------------------------------- Jun 1500 OADB/WB -- -----81.0/63.5 OF Entering DB / WB _.._... _ 77.5 / 63.1 OF LeavingDB/WB--------------- - ---- - 54.8/53.3 OF Coil ADP ----------------- ------ - -- - 51.9 OF Bypass Factor - - - - - - 0.112 Resulting RH ------ ----- ------ ------- ----------- 48 % Design supply temp. --------- -- - - - - - - 55.0 OF Zone T-stat Check .--------------------------------------------------------- .....1 of 1 OK Max zone temperature deviation _____________________ 0.0 OF Load occurs at _________________________________ Des Htg BTU/(hr-ft2) . --------- -------------- -------------- -------------------------- - 10.5 Ent. DB / Lvg DB - - 59.7 / 74.5 OF Fan motor BHP ------------------------------------------- 0.41 BHP Fan motor kW - - - - 0.32 kW Fan static ---------------------------------------------------- 0.60 in wg CFM/person_.________.______________-_______-______ 8.35 CFM/person RTU-4 r System Sizingr Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AM Air System Name - - -- - --- - --- - --- - --- - -- --- RTU-2 Equipment Class _._._ _. PKG ROOF Air System Type ------------- -- ---- -- ---- SZCAV Sizing Calculation Information Calculation Months _______________________ Jan to Dec Sizing Data_. ------- ------------ ___-_------ Calculated Central Cooling Coil Sizing Data Total coil load -_.__--------- _-.--_--------- 5.3 Tons Total coil load 63.6 MBH Sensible coil load -------- -------- 57.1 MBH Coil CFM at Jun 1400 ___ __ ____- 2390 CFM Max block CFM _.._--- _--_._ _..__. ____-- 2390 CFM Sum of peak zone CFM _________________________ 2390 CFM Sensible heat ratio -_-- ___-- _.__._. -------------.._-..0.897 ft2/Ton------- --- ---- - ----- -------- ----- -594.9 BTU/(hr•ft2) - -------- - - -------------------------------------------- 20.2 Water flow @ 10.0 OF rise ________________________ N/A Central Heating Coil Sizing Data Max coil load - - - - - ----------- --------- 27.7 MBH Coil CFM at Des ____________ Htg .___._.-...-_--------- __.. 2390 CFM Max coil CFM - - - - - - - - - - - 2390 CFM Water flow @ 20.0 OF drop ------------------------------------- N/A Supply Fan Sizing Data Actual max CFM---------------------------------------------- 2390 CFM Standard CFM 2358 CFM Actual max CFM/ft2------------------------------------------------------------ 0.76 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM-----------------------_---------------------------- 329 CFM CFM/ft2 0.10 CFM/ft2 Number of zones - - -- - -- -- - -- - - -- - -- - -- --- -- --- ----- ---1 Floor Area .. _ .... ----- _ _. _-----------3154.0 ft2 Location _______________________Edmonds, Washington Zone CFM Sizing _____ __ Sum of space airflow rates Space CFM Sizing _____. Individual peak space loads Load occurs at -. __--_- __.__---------- _._. ___---Jun 1400 OADB/WB 80.5/63.4 OF Entering DB / WB ---- 77.0 / 62.8 OF Leaving DB / WB ____ ___ __ ___54.6 / 53.4 OF Coil ADP ------ _--- - ---------- 52.3 OF Bypass Factor - 0.092 ResultingRH _. -- .--------------- .--------- ._.-.-.------- ____.----------- --_.--------47 % Design supply temp. - - - - - - - - - - - - - 55.0 OF Zone T-stat Check ---------------------- ..--- _.._ _ _--- ._-1 of 1 OK Max zone temperature deviation _____________________ 0.0 OF Load occurs at --- ------ ---------- ------ ---------- ------ ---------- ------ -- ------ Des Htg BTU/ hrft2 - - - - - -.__ - __.. 8.8 Ent. DB / Lvg DB 65.2 / 76.1 OF Fan motor BHP ------------------------------------------ 0.39 BHP Fan motor kW - - - - - 0.31 kW Fanstatic----------------------------------------------------------------------------------- 0.60 in wg CFM/person------_------_--_------_--_------_--_------_--_-__ 11.76 CFM/person Hourly Analysis Program v5.01 Page 4 of 15 Air System Sizing Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AM Air System Name _______________________________ RTU-5 Equipment Class _..__.. _-___.___ PKG ROOF Air System Type ---------------------- ---- SZCAV Sizing Calculation Information Calculation Months __ ____ ____ __ Jan to Dec Sizing Data _.------- ------ ____.. -__- _-Calculated Central Cooling Coil Sizing Data Total coil load _--- ------------- _--------------- --------------------------------- 6.5 Tons Total coil load 77.5 MBH Sensible coil load -------- __..__.. _.______ ------ 73.4 MBH Coil CFM at Jul 1600 ___________________________ 3177 CFM Max block CFM ------------------------------------------------------------- 3177 CFM Sum of peak zone CFM _________________________ 3177 CFM Sensible heat ratio -_-- ___-- _.__._. -----------.__._.0.948 ft2/Ton------- -- ------ ----- -671.0 BTU/(hr•ft2)------------------------- --------------------------------------------- _ 17.9 Water flow @ 10.0 OF rise ________________________ N/A Central Heating Coil Sizing Data Max coil load - ---------------- 35.5 MBH Coil CFM at Des Htg ------ .--------- .--------------- .--------------- _._-. 3177 CFM Max coil CFM - -- - ----- --3177 CFM Water flow @ 20.0 OF drop --------------------------------------- N/A Supply Fan Sizing Data Actual max CFM--------.--------------------------------------- 3177 CFM Standard CFM 3134 CFM Actual max CFM/ft2------------------------------------------------------------ 0.73 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM------------- ----------------------------------------------- 491 CFM CFM/ft2 0.11 CFM/ft2 Number of zones __ ___ _ ___ 1 Floor Area - -_ .... _ _ ----------- 4332.0 ft2 Location _______________________Edmonds, Washington Zone CFM Sizing ___ ___ Sum of space airflow rates Space CFM Sizing ...... Individual peak space loads Load occurs at ---------------------------------------------------------. Jul 1600 OADB/WB 81.5/63.4 OF Entering DB / WB ---- __- --------------- 77.1 / 62.7 °F LeavingDB/WB- ------------- -------55.4/54.2 OF Coil ADP -- ---- _------------------ ------- 53.2 OF Bypass Factor 0.092 Resulting RH _. -- .--------------- . ---_----------- ------------47 % Design supply temp. - - - - - 55.0 OF Zone T-stat Check --------------------- ------------ _._ --------------1 of 1 OK Max zone temperature deviation _____________________ 0.0 OF r System Sizingfor T- Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AM Air System Name - - -- - -- - ---- --- - --- - --- - -- --- RTU-3 Equipment Class _. PKG ROOF Air System Type ---------------- ---- -- ---- SZCAV Sizing Calculation Information Calculation Months _______________________ Jan to Dec Sizing Data -------- --------------- -._-_Calculated Central Cooling Coil Sizing Data Total coil load ------ -_- - ---- ___ ----------- _--- --.___ 3.5 Tons Total coil load 42.5 MBH Sensible coil load --- -------- ------ 37.4 MBH Coil CFM at Jun 1600 __ _ __ 1588 CFM Max block CFM ___. _____. _._._. _..___-- 1588 CFM Sum of peak zone CFM _________________________ 1588 CFM Sensible heat ratio ---------------- --------------- ___-- 0.880 ft2/Ton------- -- ---- - ----- -------------- -737.5 BTU/(hr•ft2) __ __. -.__. 16.3 Water flow @ 10.0 OF rise ________________________ N/A Central Heating Coil Sizing Data Max coil load - - - - --------------------- 20.6 MBH Coil CFM at Des Htg _.__________ -...------..-- ____.._.....--1588 CFM Max coil CFM - - - 1588 CFM Water flow @ 20.0 OF drop ------------------------------------ N/A Supply Fan Sizing as Actual max CFM----------------------------------------------1588 CFM Standard CFM 1567 CFM Actual max CFM/ft2------------------------------------------------------------ 0.61 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM-----------------------_---------------------------- 343 CFM CFM/ft2 . . -- - - 0.13 CFM/ft2 Number of zones--------------------------------------1 Floor Area ._ _ _ -- . ----.. ----.. ------------ -- 2615.0 ft2 Location ------------------------ Edmonds, Washington Zone CFM Sizing __________ Sum of space airflow rates Space CFM Sizing _. -- --- -------- Individual peak space loads Load occurs at ------------------ -.-.-.-Jun 1600 OADB/WB ----80.5/63.4 OF Entering DB / WB . -..-.- _.... .......... 77.2 / 62.6 OF Leaving DB / WB ____ __ ____ _____55.1 / 53.1 OF Coil ADP __._-. OF Bypass Factor - - - - - 0.146 Resulting RH - ---_-- ----_ ---_--. -------- ------- 46 % Design supply temp. --------- -- - -- - - - 55.0 OF Zone T-stat Check . -______-1 of 1 OK Max zone temperature deviation _____---- _------- _--- 0.0 OF Load occurs at BTU/ hrft2.._..._... Ent. DB / Lvg DB Des Htg ---------- 7.9 61.4 / 73.6 OF Fan motor BHP ------------------------------------------------------- 0.26 BHP Fan motor kW - - - 0.21 kW Fan static ---------------------------------------------------- 0.60 in wg CFM/person----------- ------------ ---- ------------ ---- ---- -------- ---- ------------ --- 13.72 CFM/person RTU-3 Hourly Analysis Program v5.01 Page 7 of 15 Design Weather r 117036 Magic Toyota Edmonds 08/09/2017 Comfort Systems USA - Northwest 01:30PM Design Parameters: City Name Edmonds Location Washington Latitude_------------------------ .-------- --------- - ------ - - -------- _.-------- _ __ 47.8 Deg. Longitude 122.3 Deg. Elevation 377.0 ft Summer Design Dry -Bulb 82.0 OF Summer Coincident Wet -Bulb 63.5 OF Summer Daily Range 16.0 OF Winter Design Dry -Bulb 24.0 OF Winter Design Wet -Bulb 20.0 OF Atmospheric Clearness Number 1.05 Average Ground Reflectance 0.20 Soil Conductivity 0.800 BTU/(hr-ft•°F) Local Time Zone (GMT +/- N hours) 8.0 hours Consider Daylight Savings Time No Simulation Weather Data N/A Current Data is User Modified Design Cooling Months January to December DESIGN NOTES 1. HEATING AND COOLING LOAD SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES ANS AS REQUIRED BY THE 2015 WSEC SECTIONS C403.2.1 AND C403.2.2 FOR CLIMATE ZONE 4C. OUTPUT CAPACITIES OF ALL EQUIPMENT IS NOTED IN THE EQUIPMENT SCHEDULES. 2. HVAC LOAD SUMMARY AND VENTILATION CALCULATIONS SHOWN ON M004 AND M005. 3. CALCULATIONS USE THE FOLLOWING BUILDING DESIGN TEMPERATURES AND THERMAL INSULATION VALUES IN ACCORDANCE WITH 2015 WSEC AND THE ASHRAE RECOMMENDED OUTDOOR DESIGN TEMPERATURES FOR WASHINGTON STATE UNLESS NOTED OTHERWISE: SITE COORD: LAT N47.80 LON W122.30 WEATHER DATA: EDMONDS, WA (WSEC) ELEVATION: 377 FT SUMMER DESIGN OSA: 82°F DB/63.5°F WB WINTER DESIGN OSA: 24°F DB INDOOR DESIGN: 72°F DB H/75°F DB C SA HEATING: 95°F MAX SA COOLING: 58°F MIN ROOF U-VALUE: 0.026 WALLS U-VALUE: 0.047 & 0.064 DOORS U-VALUE: 0.200 & 0.580 GL GLAZING U-VALUE: 0.290 GLAZING SHGC: 0.226 2. INTERIOR LIGHTING POWER ALLOWANCES PER 2015 WSEC TABLE C405.4.2(1) 0.66 TO 1.0 WATTS/SQ FT WERE USED IN THE HVAC SYSTEM SIZING CALCULATIONS, UNLESS NOTED OTHERWISE. 3. INTERIOR EQUIPMENT PLUG LOAD ALLOWANCES PER 2015 WSEC TABLE B102 OF 1.0 TO 2.0 WATTS/SQ FT WERE USED IN THE HVAC SYSTEM SIZING CALCULATIONS, UNLESS NOTED OTHERWISE. 4. OUTSIDE AIR MECHANICAL VENTILATION BASED ON 2015 IMC CHAPTER 4 W/ WA AMENDMENTS. WHERE KNOWN, SPECIFIC OCCUPANCIES UTILIZED THE ARCHITECTS SEATING PLAN AND HEAD COUNT, EXCEPTION TO IMC SECTION 403.2, OR ASHRAE 62.1, LATEST EDITION. COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST') AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. TiC N 00 Qo Q 0 o z 0 O CO Irl- N Li LL1 O o � LIJ � N w m Cn CD co N = I­_i C7, d O z � 0 OI- N O Q (D N U_ W �� co 0� wQ co w ; ILL! pvn W a� w U 1- 0 00 00 Qo � C 4 o �IL Srl- U � ow co SIGNED: 8/11 /2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 Load occurs at --__---_--_--__---_-_--_____--_--_____--_- Des Htg BTU/(hr-ft2) 8.2 Ent. DB /Lvg DB __________________________ ______________________________ 64.3 / 74.8 OF HVAC LOAD SUMMARY Fan motor BHP -------------------------------------- 0.52 BHP Fan motor kW - - - - - 0.41 kW Fanstatic----------------------------------------------------------------------------------- 0.60 in wg DESIGNED CSUSA NW / EE CFM/person-__-__-______-__-__-___-_-_-___-_-_-___-__-__ 17.52 CFM/person RTU -5 ' CHECKED ' CSUSA NW / SAL 08/11/2017 1 •, SHEET TITLE MECHANICAL HVAC LOAD CALCULATIONS Ed01:4Ai:lI1611:40 11� Hourly Analysis Program v5.01 Page 10 of 15 Hourly Analysis Program v5.01 Page 13 of 15 OUTSIDE AIR MECHANICAL VENTILATION CALCULATIONS Ventilation i i r Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AN 1. Summary Ventilation Sizing Method ____- Design Ventilation Airflow Rate Sum of Space OA Airflows ------- ------ -- --------- . 538 CFM Zone Name / Space Name Mult. Floor Area ft2 Maximum Occupants Maximum Supply Air CFM Required Outdoor Air (CFM/person Required Outdoor Air CFM/ft2 Required Outdoor Air CFM Required > Outdoor Air % of supply) Uncorrected Outdoor Air (CFM) Zone 1 101 - Display/Sales (1) 1 3232.0 20.0 6104.3 7.50 0.12 0.0 0.0 537.8 Totals (incl. Space Multipliers) 6104.3 537.8s Ventilation i i for RTU-2 Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AN 1. Summary Ventilation Sizing Method ------------------------------------ Design Ventilation Airflow Rate Sum of Space OA Airflows ------------------- 329 CFM Zone Name / Space Name Mult. Floor Area ft2 > Maximum Occupants Maximum Supply Air CFM Required Outdoor Air CFM/person Required Outdoor Air CFM/ft2 ; Required Outdoor Air CFM) Required Outdoor Air ` % of suppl 'Uncorrected Outdoor Air CFM Zone 1 133 - Service Work 1 135.0 1.0 81.9 5.00 0.06 0.0 0.0 13.1 103, 104, 131 -Multiple 1 2842.0 24.0 2190.4 5.00 0.06 0.0 0.0 290.5 106 - New Car Mgr 1 177.0 3.0 117.6 5.00 0.06 0.0 0.0 25.6 Totals (incl. Space Multipliers) 2389.9 1 329.2 Ventilation i Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AN 1. Summary Ventilation Sizing Method ._...__._. Design Ventilation Airflow Rate Sum of Space OA Airflows - -- - - - 343 CFM Zone Name / Space Name Mult. Floor Area ft2 Maximum Occupants Maximum Supply Air CFM Required Outdoor Air CFM/person Required Outdoor Air CFM/W) Required Outdoor Air CFM Required Outdoor Air % of supply) Uncorrected Outdoor Air (CFM) Zone 1 112 - F&I 1 125.0 3.0 124.7 5.00 0.06 0.0 0.0 22.5 113 - F&I 1 125.0 3.0 124.7 5.00 0.06 0.0 0.0 22.5 114 - F&I 1 125.0 3.0 124.7 5.00 0.06 0.0 0.0 22.5 115 - F&I 1 125.0 3.0 124.7 5.00 0.06 0.0 0.0 22.5 116 - F&I 1 125.0 3.0 124.7 5.00 0.06 0.0 0.0 22.5 118 - Corridor 1 164.0 0.0 19.1 0.00 0.06 0.0 0.0 9.8 119 - Corridor 1 276.0 0.0 34.3 0.00 0.06 0.0 0.0 16.6 122 - Parts 1 1018.0 2.0 526.1 5.00 0.12 0.0 0.0 132.2 110 - F&I MGR 1 158.0 3.0 109.1 5.00 0.06 0.0 0.0 24.5 126, 127, 128 - Multiple 1 284.0 4.0 218.6 5.00 0.06 0.0 0.0 37.0 129 - Parts Mgr 1 90.0 1.0 57.5 5.00 0.06 0.0 0.0 10.4 Totals (Incl. Space Multipliers) 1588.1 343.0 Ventilation i i Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AN 1. Summary Ventilation Sizing Method -------- Design Ventilation Airflow Rate ._ Sum of Space OA Airflows _..------- __---------- - ------------ 626 CFM Zone Name / Space Name Mult. Floor Area ft2 Maximum Occupants Maximum ;Supply Air CFM Required Outdoor Air (CFM/person Required Outdoor Air CFM/ft2 Required Outdoor Air CFM Required Outdoor Air % of supply) Uncorrected Outdoor Air (CFM) Zone 1 200 - File Storage 1 388.0 1.0 77.3 5.00 0.06 0.0 0.0 28.3 201 - Dealer 1 404.0 2.0 354.0 5.00 0.06 0.0 0.0 34.2 204 - Gen Mgr 1 410.0 2.0 378.7 5.00 0.06 0.0 0.0 34.6 205 - Waiting 1 691.0 20.0 320.2 5.00 0.06 0.0 0.0 141.5 208 - Conf/Training 1 773.0 44.0 1009.2 5.00 0.06 0.0 0.0 266.4 209 - Corridor 1 457.0 0.0 72.2 0.00 0.06 0.0 0.0 27.4 224 - Locker Rm 1 242.0 4.0 193.3 0.00 0.25 0.0 0.0 60.5 226 - Secure Files 1 158.0 1.0 36.6 5.00 0.06 0.0 0.0 14.5 227 - File Storage 1 228.0 1.0 47.9 5.00 0.06 0.0 0.0 18.7 Totals (incl. Space Multipliers) 2489.4 626.0 Ventilation i 1 r Project Name: 117036 Magic Toyota Edmonds 08/11/2017 Prepared by: Comfort Systems USA - Northwest 06:21AN 1. Summary Ventilation Sizing Method Design Ventilation Airflow Rate Sum of Space OA Airflows 491 CFM Zone Name / Space Name Mult. Floor Area (ft2) ; Maximum '; Occupants Maximum Supply Air (CFM) Required Outdoor Air (CFM/person) Required Outdoor Air (CFM/ft2) Required Outdoor Air (CFM} Required Outdoor Air (% of supply) Uncorrected' Outdoor Air (CFM)' Zone 1 213 - Generall Office 1 1122.0 10.0 825.2 5.00 0.06 0.0 0.0 117.3 214 - HR 1 181.0 2.0 184.0 5.00 0.06 0.0 0.0 20.9 215 - Office Mgr 1 175.0 2.0 221.7 5.00 0.06 0.0 0.0 20.5 216 - Corridor 1 181.0 0.0 29A 0.00 0.06 0.0 0.0 10.9 217 - IT Office 1 65.0 1.0 75.3 5.00 0.06 0.0 0.0 8.9 219 - Internet Sales 1 395.0 4.0 318.9 5.00 0.06 0.0 0.0 43.7 220 - Corridor 1 335.0 0.0 55.9 0.00 0.06 0.0 0.0 20.1 221 - Service Call Cntr 1 367.0 4.0 346.0 5.00 0.06 0.0 0.0 42.0 222 - Employee Lounge 1 316.0 4.0 440.3 5.00 0.12 0.0 0.0 57.9 225 - Parts 1 1195.0 1.0 680.6 5.00 0.12 0.0 0.0 148.4 Totals (incl. Space Multipliers) 3177.3 490.6 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM 2015 Washington State Energy Code Corr oliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Project Information Project Title: Magic Toyota Edmonds WA Date 8/11/2017 Applicant Information. Provide contact information for individual who can respond to For Building Dept. Use inquiries about compliance form information provided. Company Name: Comfort Systems USA NW Company Address: 18702 North Creek Parkway Edmonds WA 98011 Applicant Name: Sonny Winter, Project Manager Applicant Phone: (425) 883-9224 Project Description [2]New Building Building Addition Tenant Improvement QSystem Retrofit E:[No System Changes Briefly describe mechanical systems in New mechanical HVAC systems to support construction of a 2 story structure consisting of a sales floor, generatl the text box provided office space, a parts deparment, service area and parking deck. Mechanical work includes the following: heating, E Total Bldg Performance (TBP) ventilation and air conditioning systems to serve the auto showroom and office spaces, exhaust systems for restrooms breakrooms and service area ductless mini -split A/C units for small server and equipment rooms in p This path includes all mandatory slab hot water (hydronic) radiant heating system in the service and new car delivery areas,. snow melt, all provisions per C401.2 Option 2. p MECH-SUM, MECH-CHK; and C407 associated ductwork piping, rifles registers diffusers accessories and astand-alone controiss stems for a ' p p g' g g y Energy Analysis forms required, complete installation and equipment start-up, air balance and programming and owner triaining, O&M manuals. Load calculation summary MECH-LOAD-CALC Form Design Load Calculations Provide design load calculations for all mechanical systems and equipment serving the building heating, cooling or ventilating needs. If a load calculation summary is provided with the permit documents that includes all applicable compliance information then the MECH-LOAD-CALC form is not required. 0. Mechanical Plans L MECH-EQ Forms (TBD) Mechanical Schedules Indicate location of equipment compliance information. if provided on plans then MECH-EQ forms are not required, however, include on plans all applicable compliance information listed in MECH-EQ tables. DOAS is required per C403.6 effective July 1, 2017 (office, retail, education, library and fire station occupancies) All occupied, conditioned areas shall be served by a DOAS that delivers required ventilation air in a manner that does not require space conditioning fan operation. Space conditioning fans cycled off when no heating or cooling is required. Dedicated Outdoor Air Ventilation provided via natural ventilation per 2015 IMC in lieu of DOAS (C403.6, Exception 1) System Requirements and Ventilation and space conditioning provided by a HEVAV system per C403.7 in lieu of DOAS (C403.6, Exception ) High Efficiency VAV DOAS included in project, although not required (occupancy not office, retail, education, library or fire station) Alternate DOAS related allowances included in project: Prescriptive vertical fenestration maximum area allowance increased to 40% per C402.4,1.4 with 100% of conditioned floor area in building served by DOAS. E] Exception to air economizer per C403.3 Exception 1, include MECH-ECONO form. Project includes HVAC air distribution systems that provide heating and/or cooling If yes, provide a MECH-FANSYS -SUM form. Fan Power For one or more systems, the total fan motor nameplate hp of all fans in HVAC system exceeds Shp. Ifyes, provide a separate MECH-FANSYS form for each HVAC system exceeding the 5 horsepower threshold. Refer to Section C403.2.11 and MECH-FANSYS-DOC for requirements and exceptions. Hydronic chilled water -] Water -loop heat pump No hydronic systems HVAC Hydronic Systems tt-----tt Hydronic heating water L ,i Geothermal [ C406.2 More efficient HVAC equipment and fan systems Requires 90% of heating and cooling capacity to be equipment listed in tables C403.2.3(1)-(g) or air -to -wafer heat pumps and heat recovery chillers. All equipment listed in tables C403.2.3(1)-(7) must be 15% more efficient than minimum requirements. All stand alone supply, return, and exhaust fans over9hp must have FEQ>_ 71 and must be C406 Additional Efficiency selected within 10% of maximum total or static pressure. C406.6 Dedicated outdoor air system (DOHS) Options - Mechanical Requires 90% of conditioned floor area to be served by a DOAS per C403.6 that delivers required ventilation air in a manner that does not require space conditioning fan operation. C406.7 Reduced energy in service water heating Requires 90% of floor area be in occupancy types listed in C406.7:1 and that 60% of annual hot water energy use be provided by heat pump, waste heat recovery or solar water -heating systems. 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary, •• 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Equipment Type (s) JZ Hot water heating tank(s) Instantaneous 0 No service water systems Service Water Heating Dedicated boiler Heat exchange from space heat boiler or Systems central hot water/steam Distribution Type (s) 121 Circulation System On -demand Commissioning Commissioning is required for: I.....it, Mechanical systems per C408.2 Service water heating systems per C408.4 If required, commissioning shall be performed for all applicable systems regardless of individual equipment capacity. Exceptions to commissioning requirements: Total output capacity of all mechanical space conditioning systems in the building do not exceed 240,000 Btu/h cooling or 300,000 Btu/h heating. Mechanical systems commissioning not required. Capacity of largest service water heating system in building does not exceed 200,000 Btu/h. Service water heating systems commissioning not required. Low Energy and Semi -Heated Spaces (Note 6 and 7) Peak Space Heating Cooling Conditioning Space Area Served, Capacity, Btu/h Capacity, Btu/h Capacity, Compliance Type Location in Plan(s) Space(s) Served square feet (Note 4) (Note 5) Btu/6-sf Check Notes Semi- DOES NOT Smallest heated Sheet M100 151 - Sprinkler Riser Room 110 1,706 0 15.51 COMPLY, Manufactured Unit Selected Semi- (TOES NOT Smallest heated Sheet M100 100 - Entry Vestibule 60 1,706 0 28,43 COMPLY Manufactured Unit Selected Semi- DOES NOT Smallest heated Sheet M101 102 - Entry Vestibule 60 1,706 0 28.43 COMPLY Manufactured Unit Selected Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh. Note 5 - Provide total installed cooling capacity of system serving Low Energy space(s) in Btu/h. Not allowed for semi -heated spaces. Enter 0 if no cooling. Note 6 - Refer to Section C402.1.1 Low Energy Building. lntalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btu/h*sf. Note 7 - Refer to Section C402.1.1.1 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 Btu/h*sf. Only systems without electric resistance heating and no cooling are eligible for the wall insulation exception under semi -heated. 2015 WSEC MECH FORM, N�9RP0RHI1 1. HEATING AND COOLING LOAD SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES ANS AS REQUIRED BY THE 2015 WSEC SECTIONS C403.2.1 AND C403.2.2 FOR CLIMATE ZONE 4C. OUTPUT CAPACITIES OF ALL EQUIPMENT IS NOTED IN THE EQUIPMENT SCHEDULES. #IJIMA 0 11 IRTA I 30 3. CALCULATIONS USE THE FOLLOWING BUILDING DESIGN TEMPERATURES AND THERMAL INSULATION VALUES IN ACCORDANCE WITH 2015 WSEC AND THE ASHRAE RECOMMENDED OUTDOOR DESIGN TEMPERATURES FOR WASHINGTON STATE, UNLESS NOTED OTHERWISE: SITE COORD: LAT N47.8* LON W122.30 WEATHER DATA: EDMONDS, WA (WSEC) ELEVATION: 377 FT SUMMER DESIGN OSA:827 /i • i WINTER 1 /i SA HEATING: 95°F MAX SA COOLING: 58°F MIN ROOF U-VALUE: 0.026 WALLS U-VALUE: 0.047 & 0.064 DOORS U-VALUE: 0.200 & 0.580 GL GLAZING U-VALUE: 0.290 GLAZING SHGC: 0.226 COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 2. INTERIOR LIGHTING POWER ALLOWANCES PER 2015 WSEC TABLE C405.4.2(1) 0.66 TO 1.0 WATTS/SQ FT WERE USED IN THE HVAC SYSTEM SIZING CALCULATIONS, UNLESS NOTED L� OTHERWISE. r 3. INTERIOR EQUIPMENT PLUG LOAD ALLOWANCES 0 PER 2015 WSEC TABLE 6102 OF 1.0 TO 2.0 LL W -4)Cn WATTS/SQ FT WERE USED IN THE HVAC L SYSTEM SIZING CALCULATIONS, UNLESS NOTED r OTHERWISE. m i 4. OUTSIDE AIR MECHANICAL VENTILATION BASED ON 2015 IMC CHAPTER 4 W/ WA AMENDMENTS. WHERE KNOWN, SPECIFIC OCCUPANCIES UTILIZED THE ARCHITECTS SEATING PLAN AND HEAD COUNT, EXCEPTION TO IMC SECTION 403.2, OR ASHRAE 62.1, LATEST EDITION. 0 UJ H cf)CD 00 >- Q O Y N Q z , = 0000 00 W � tf) W N � d- U � O O zm N 0 I` 00 SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11/2017 tOB A11:1BER 1 • SHEET TITLE MECHANICAL HVAC LOAD CALCULATIONS SHEET NUMBER c L i' ' J COPYRIGHT NOTICE 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 3 of 7 THIS LAYOUT/DESIGN IS A Mechanical Permit Plans Checklist MECH-CHK Mechanical Permit Plans Checklist MECH-CHK Mechanical Permit Plans Checklist MECH-CHK COPYRIGHTED WORK OWNED BY 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST') AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. FM co O M Q >111111111111111 Q o TT_ !!1� N V `^ v ) Z 0 O N n Q W O (� W4�, , ll— W C0 UJ I on �o Co 3: 00 C\1 � O Q O � 0 H T O Q " N � � O INN (O �e Cf) � O LU W Q o0 .. W W �j W 1-- and -J d- W Cn 0 N W �ry 0 0 ~ ¢ O 3 O LY] O 2(0CD 0 co 0> o � 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 4 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 5 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 6 of 7 U (0 Z Mechanical ._ rmit . ._ rmit . ._ rmit Plans Checklist MECH-CHK 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 � A. L.� WAS F T �tti� � �yy ` z �11 38898 ST� ski �SSj�NALGZ SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11/2017 JOB NUMBER 2015 WSEC MECH FORM 117036 SHEET TITLE ENERGY CODE COMPLIANCE FORMS SHEET NUMBER M 006 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 -Page 1 of 7 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes Equipment -Sizing, Performance and Type Identif e ui ment to be used in manufacturin industrial or commercial rocesses that do not Y q p g, p NA C403.1 Exempt process equipment provide space conditioning; identify provisions applicable to this equipment per C403.1 exception Provide load calculations performed per ASHRAE Std 183 or equivalent, using design M004, Yes C403.2.1 Load calculations parameters per C302 and Appendix C; include load adjustments to account for energy M005 recove Ma is To ota Edmonds WA 8 li 2017 Project Title: g y Date The followin information is necessa to check a ermit a lication for tom liance with the mechanical s stems and e ui ment re uirements of the 9 ry p pp p Y q p q Washin ton State Ener Code Commercial Provisions. 9 9Y Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes For su I and return ductwork located in unconditioned s ace or outdoors indicate R-value PPY P of insulation on ductwork on plans; identify climate zone; note exceptions taken M001 For supply ductwork located in conditioned space, identify if design supply temperature is < C403.2.8.1 Yes C403.2:8.2 Duct insulation 55°F or > 105°F and indicate R-value of insulation on this ductwork on plans;. note exception taken M001 For OSA ductwork, shafts and plenums, indicate R-value of insulation on these elements on plans per Table C402.1.3 for steel -framed walls; note. exception taken M001 Piping Systems Yes C403.2.9 Pi in insulation P g Indicate design temperature range of fluid conveyed in piping and thickness of insulation (in inches) on hydronic piping plans; or exception taken M001 Yes C403.2.9.1 Piping insulation exposed to Indicate method of protection of pipe insulation from damage /degradation on hydronic piping weather plans M001 Economizers Identify in equipment schedules on plans or in MECH-EO forms all cooling systems requiring M002, air economizer controls M003 Yes C403.3 Air economizer required Provide MECH-ECONO form indicating systems utilizing air economizer exceptions, including those with water -side economizer in lieu of air economizer; indicate on plans eligible M002, exceptions) taken and measures to comply with exceptions) M003 Yes C403.3.1 Integrated economizer Indicate air and water -side economizers are configured for partial cooling operation even M001, M002, operation -air and water where additional mechanical cooling is required to meet the load M003 Yes C403.3.2 Economizer heating system Verify control method of HVAC systems with economizers does not increase building heating M001, M002, impact - airand water energy usage during Normal operation M003 Yes C403.3.3.1 Air economizer capacity Indicate modulating OSA and return air dampers are configured to provide up to 100% OSA M001, M002, for cooling M003 Verify mechanical cooling controls are interlocked with air economizer controls so the outside M001, air damper remains in 100% openposition when mechanical cooling is also required to meet M002, C403.3.1 the cooling load, until the leaving air temperature is < 45°F M003 Yes C403.3.3.2 Integrated air economizer M001, For systems with cooling capacity >_ 65,000 Btu/h, verify that control of economizer dampers is M002, not based only on mixed air temperature; or exception taken M003 Yes C403.3.3.3 Air economizer high limit controls Indicate high limit shut-off control method and required high limit per Table C403.3.3.3 M003 For eligible systems where water -side economizer may be provided in lieu of air economizer, NA C403.3.4.1 Water economizer capacity indicate system is capable of 100%design cooling capacity at 50°F db / 45°F wb OSA temperatures NA C403.3.4.2 Water economizer Indicate pressure drop across precooling coils and heat exchangers in water economizer maximum pressure. drop system do not exceed pressure drop limit Yes C403.3.1 DX air handling equipment For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, refer to HVAC M001, M002, control System Controls for requirements M003 DX equipment economizer For DX air handlers with economizer and cooling capacity ? 54,000 Btu/h, provide a fault M001, Yes C403.2.4.7 fault detection and detection and diagnostics (FDD) system to monitor economizer system operation and report M002, diagnostics. faults M003 Systems Requiring Energy Recovery For systems with design OSA > 5,000 cfm, or design supply air cfm and % OSA exceeding the values in Tables C403:5.1(1) or (2), indicate exhaust air ER method; or exception taken with su ortin calculations Pp g Ener recover ER - gY Y( ) For rooms served by multiple systems with aggregate design OSA > 5,000 cfm, or aggregate NA C403.5.1 ventilation /exhaust. systems design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate exhaust air ER method; or exception taken with supporting calculations Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50% based on delta between OSA and return air enthalpies at design conditions Laboratory exhaust systems For buildings with total lab exhaust > 5,000 cfm, indicate method of energy recovery used to NA C403.2.7.2 (energy recovery) pre -condition laboratory make-up air; ER effectiveness (min 25°F); or alternative. method per exception (VAV exhaust, semi -conditioned makeup, or GERM calculation) For buildings with pools or spas with water surface area > 200 sf, indicate exhaust air ER C404.10.4 Pools and permanent spas method and use of waste heat (preheat ventilation air, pool water or service hot water); or NA (under exhaust systems exception taken C404.11) (energy recovery) Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air temperature at design conditions by >_ 36°F Energy recovery - For buildings with on -site steam heating systems, indicate condensate water ER For buildings that use off -site generated steam where condensate is not returned to the NA C403.5.2 steam condensate systems source, indicate on -site condensate water ER Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessa Ma is To ota Edmonds WA 8 li 2017 Project Title: Date J 9 Y The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. A licable Code Section Code Provision Information Required - Must be in permit documents Location in Buildin De artment es,no,na Documents Notes For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote refrigeration capacity for coolers /freezers, indicate condenser ER and use of captured energy (service water heating, space heating, or dehumidification reheating) NA C403.5.3 Energy recovery - For buildings with >_ 40,000 sf conditioned floor area and with ? 1,000,000 Btu/h of remote cooler /freezer condensers refrigeration capacity for coolers /freezers,. indicate condenser ER and use of captured energy for service water heating and also for space heating, or dehumidification reheating For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and NA C403.5.4 Energy recovery - design service hot water load. > 250,000 Btu/h, indicate condenser ER to pre -heat service condenser systems water; or exception taken. Provide calculations showing the amount of Yecovered heatthat is utilized (60% of peak heat rejection load or pre-heatservice water to 85°F). Hydronic System Controls For hydronic system pump motors >_ 7.5 hp, indicate method of variable flow control (VSD or C403.2.13 Variable flow control - equivalent method that requires>_ 30%design wattage at 50%design fluid flow}; note NA C403.4.2.7 hydronicsystem pumps exception taken Identify whether hydronic coils have DDC controls and associated manner of pump speed control (differential pressure, zone. hydronic demand, etc) For boilers that provide building heating, indicate controls that provide heating water temperature setback based on outdoor temperature M303 For heating and chilled water systems > 300,000 Btu/h, indicate systems are configured to C403.2.5 H dronic s stem setback automatically reset supply water temperature based upon demand; or exceptiontaken. Yes If system pump motor hp >_ 3 hp, also indicate controls automatically reduce flow by >_ 50%. M303 C403.4.2.4 and part load controls For chilled water systems (>_ 300,000 Btu/h, pump motor hp >_ 3 hp}that serve water-cooled unitary air conditioners, indicate VSD or staged pumps in chilled water system and heat rejection loop that reduce pump flow so that one control valve. is nearly wide open, or to maintain a minimum differential pressure; or exception taken M303 Yes C403.4.2 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers M303 NA C403.4.6 Hot gas bypass limitation For cooling equipment with hot gas bypass, provide either multiple step unloading or continuous capacity modulation; indicate bypass capacity per Table C403.4.6 NA C403.4.2.2 Two -pipe changeover Indicate changeover deadband (min 15°F), heating /cooling mode scheduling and systems changeover temperature range (limit 30°F) NA C403.4.2.6 Chiller /boiler plant pump Indicate controls are configured to automatically reduce overall plant flow and shut-off flow isolation through individual chillers and .boilers when not in use For cooling towers with fan motors >_ 7.5 hp, indicate VSD and method to adjust fan speed C403.2.13.1.1 Heat rejection equipment -( ad'usted based on leavin fluid tem erature or condenser tem erature ressure of heat J g P P / P NA C403.4.3.1.1 C403.4.3.1.2 variable flow control rejection device) For multiple -cell heat rejection equipment with VSD, indicate controls that ramp all fans in unison NA C403.4.3.3 Heat rejection equipment - Indicate open -circuit cooling towers with multiple pumps or VSD control are designed so all cooling tower flow turndown cells can be run in parallel NA C403.4.2.3.1 Water loop heat pump - Indicate capability of central equipment to provide minimum 20°F water supply temperature deadband deadband between heat rejection and Beat addition modes; or exception taken Water loop heat pump - Indicate type of cooling tower (open- or closed-circuit) in equipment schedule; indicate method NA C403.4.2.3.2.1 heat rejection equipment, used to limit system heat loss when heat rejection is not needed Zone 4 Water loop heat pump - For open- or closed-circuit cooling towers, provide a heat exchanger that separates the cooling NA C403.4.2.3.2. heat rejection equipment, tower and heat um loo P P P Zone 5 NA C403.4.2.3.3 Water too heat um P P P For h dronic heat um s stems with totals stem ower 10 h indicate 2-wa isolation Y P P Y Y P P' Y isolation valves valves on each heat pump and variable flow system control Dedicated Outdoor Air Systems (DOAS) -Optional through 6/30J16, Prescriptive 7J1/2016 For buildings with office, retail, education, library and fire station spaces, identify these spaces Yes C403.6 Dedicated outdoor air on plans; indicate that ventilation air in each occupied space is provided via a DOAS system; C403.6.3 systems or documentcompliance with C403.6:3 Impracticality; or exception taken (buildings complying with C402.4.1.4 or C406.6 may not utilize exceptions) M003 Energy recovery ventilation For all DOAS systems, indicate exhaust air ER method; or exception taken with supporting NA C403.6.1 with DOAS calculations. Indicate ER rated effectiveness that increases OSA enthal b > 50% based on PY y " delta between OSA and return air enthalpies at design conditions. Indicate equipment associated with the delivery of zone level heating and cooling (fans, Heating /cooling system hydronic pumps, primary air dampers, etc) are configured to shut off, and central equipment is NA C403.6.2 controls with DOAS configured to turn down, when there is no call for heating or cooling in the zone they serve If applying Exception to heating /cooling fans used for air mixing in the space during deadband periods, include fan watts per cfm in equipment schedule Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes C403.2.4.10 Group R2 / R3 dwelling For primary space conditioning system, indicate 5-2 programmable thermostats capable of two NA C403.2.4.11 units, Group R2 sleeping setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or units both), required temperature range and at minimum a 10°F deadband; or exception taken M002, Indicate method of ventilation air delivery (natural or mechanical) for each zone M003 C403.2.6 If mechanically delivered, indicate that systems are configured to provide not more than 150% M004, Yes C403.2.11.4 Ventilation of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE M005 62.1 or other applicable code (WAG, OSHA, etc); or exception taken If delivered via natural ventilation, identify required elements per IMC including minimum NIA openable area to the outdoors or qualifying adjoining spaces Identify spaces > 500 sf with occupant load > 25 people/1,000 sf per IMC; for each space Demand controlled indicate whether it is served by an HVAC system with total design OSA > 3,000 cfm, and / or NA C403.2.6.2 ventilation the system has airside economizer or automatic modulating OSA damper; indicate OSA controls are configured to provide demand controlled ventilation or provide supporting documentation fora lied exce tion PP P For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based NA C403.2.6.3 Occupancy sensors OSA control when space is unoccupied and method (closes OSA damper or shuts -off equipment); or alternate means provided toautomatically reduce OSA when space is partially occupied C403.2.6.4 Enclosed loading dock For enclosed loading docks, indicate ventilation /exhaust system method of activation (gas NA C403.2.6.4,1 ventilation detection system for CO and NO2, or occupancy sensors), and control method (staged or modulatin g) M002 Yes C403.2.6.4 Enclosed parking garage For enclosed parking garages, indicate ventilation !exhaust system activated by gas detection M003 C403.2.6.4.2 ventilation system for CO and NO2, and control method (staged or modulating); or exception taken Provide calculations that show a balanced accounting of total kitchen exhaust (include all hoods) with % ofsupply air, transfer air from adjacent spaces, and make-up air;. if applicable, indicate that direct make-up air to each hood does not exceed 10% df hood exhaust NA C403.2.7.1 Kitchen exhaust hoods For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would otherwise be exhausted) NA C403.2.7.2 Laboratory exhaust systems Refer to Systems Requiring Energy Recovery for requirements Variable flow capacity - For HVAC fan motors >_ 7.5 hp, indicate method of variable flow control (VSD, or equivalent NA C403.2.13 HVAC system fans control method that reduces design air volume by 50% at 1/3 static design pressure); note exception taken For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, indicate number of cooling stages provided and method (multiple compressors and / or variable speed M002, DX air handler variable compressors}; indicate minimum displacement (capacity reduction) as % of full load M003 M001, Yes C403.3.1 cooling control (Under Integrated M002, Economizer) Indicate control method (cooling capacity controlled in response to space temperature, space M003, temperature controlled by modulating supply airflow, or both) M004, M005 > For DX air handling units with cooling capacty_ 65,000 Btu/h and evaporatroe and chilled water air handling units with fan >_ 0.25 hp, indicate whether system is single zone or multiple zone and related control method coolin ca acit controlled in res onse to s ace ( 9 P Y P P temperature, space temperature is controlled by modulating supplyairflow, or both) NIA For mechanical cooling systems (includes DX and chilled water coifs) that control cooling capacity in response tospace temperature - Provide a minimum of two stages of fan control; Yes C403.2.11.5 Fan airtlow control indicate minimum fanspeed is <_B6% of full speed drawing <_ 40% of full speed fan power M002, during periods of low cooling or ventilation only M003 For other mechanical cooling systems (includes DX and chilled water coils) that control space tem erature b modulatin airflow in lieu of or in addition to controllin ca acit in res onse P Y 9 ( , � 9 P Y P to s ace tem erature -Provide fan controls for modulatin su I airflow indicate minimum P P ) 9 PPY fan speed is s 50% of full speed drawing <_ 30% of full speed fan power during periods of low cooling or ventilation only; or exception taken N(A Provide central and zone level DDC controls as required based on system application, No C403.2.4.12 DDC system capabilities capacity or size thresholds and other qualification per Table C403:2.4.12.1 Identify all DDC system input! output control points; indicate capability for trending and raphical displa Ducting Systems C403.2.8.1 Indicate on plans that all ductwork is constructed and sealed per IMC M001 For OSA ductwork, also indicate on plans that ductwork meets air leakage requirements per Yes C403.2.8:3 Duct construction C402:5and vapor retarder requirements per the IBC M001 Yes C403.2.8.3 Duct pressure classifications. Identif location of low medium and hi h ressure ductwork on fans Y g P P M001 NA C403.2.8.3.3 High pressure duct leakage Indicate high pressure duct leakage testing requirements on plans; provide test results to test jurisdiction when completed Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes C402.4.1.4 Increased prescriptive NA C403.6 maximum vertical Indicate that all occupied, conditioned spaces are served by a DOAS per C403.6 fenestration area with DOAS Additional Efficiency Package Option, Dedicated Outside Air Systems (DOAS) NA C406.6 Building provided with To comply with additional efficiency package option, indicate that 90% or more of all occupied, DOAS conditioned spaces are served bya DOHS per C403.6 Multiple Zone Air Systems Air systems serving multiple Identify supply air systems serving multiple zones and the zones they serve on plans; indicate NA C403.4.4 whether system is VAV and method of primary air control; or provide supporting zones documentation for applied exception to VAV Provide equipment schedules on plans or MECH-EO form that list all VAV air terminals and types For each air terminal include: maximum airflow rates for primary supply air during zone peak VAV systems serving NA C403.4.4 multiple zones heating and zone peak cooling; maximum airflow during reheating, retooling or mixing; minimum airflow rate to maintain required ventilation, and the basis for these values; if IMC or ASHRAE 62.1 multiple zone equation is basis for minimum flow rates, provide calculation on plans NA C403.4.4.1 Single duct VAV terminal Indicate single duct terminal units are configured to reduce primary supply air before reheating units or retooling NA C403.4.4.2 Dual duct systems -terminal For systems with separate warm air and cool air ducts, indicate terminal units are configured to units reduce the flow from one duct to minimum before mixing with air from the other duct Indicate locations of duct static pressure sensors on plans; include at least one sensor per major duct branch; verify controller Setpoint pressure at each sensor is <_ 1.2 inch w.g. For systems with zone level DDC, indicate controls are configured to monitor zone damper NA C403.4.1.1 VAV system static C403:4,1.2 pressure sensors - and DDC Positions and reset static pressure Setpoint based on the zone requiring most pressure; sensors set points include control logic that automatically detects and generates an alarm if any zone excessively drives reset logic, and allows building operators to exclude zones from reset logic Multiple -zone VAV system For systems with zone level DDC controls, indicate controls are configured to automatically NA C403.4.4.3 ventilation optimization reduce outdoor airflow in response to changes in system ventilation efficiency; or exception controls taken NA C403.4.4.4 VAV system supply air reset Indicate controls automatically reset supply air temperature in response to building loads or outdoor air temperature; or exception taken Multiple Zone HVAC Systems, High Efficiency VAV -Required for systems utilizing C403.6 DOAS Exception 2, must comply with all 16 provisions NA C403.7, Air economizer Indicate system is configured for 100% air economizer operation and complies with all related Item 1 economizer requirements per C403.3 (without economizer exceptions) NA C403.7, Direct digital controls (DDC) Provide DDC controls for all components of system; identify all DDC system input /output Item 2 control points; indicate capability for trending and graphical display For systems with minimum OSA > 2,500 cfm, indicate outdoor airflow monitoring station that NA C403.7, Outdoor airflow measures OSA intake under all load conditions; indicate control sequence that increases or Item 3 measurement and reduction reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency (per C403:4.4.3 without exceptions) or DCV (per C403:2.6.2) NA C403.7, Supply airflow measurement For systems with minimum OSA > 2,500 cfm, indicate supply airflow monitoring station Item 4 capable of measuring supply air delivered to VAV terminals under all load conditions C403.7, Zone isolation and Verify maximum area served by a single HEVAV system is <_ 50,000 sf, or one entire floor, NA Item 5 maximum area served whichever is greater; in addition if a system serves > 25,000 sf, that includes areas that are expected to be occupied non -simultaneously, indicate zone isolation controls per C403.2.4.4 C403.7, Interior /exterior zone Verify that VAV terminals serving interior cooling driven loads are sized per design supply air NA Item 6 design supply air temperature that is 5°F higher than VAV terminals serving exterior zones temperature C403.7, Maximum air terminal inlet Identify air terminals with minimum primary airflow setpoints > 50% of maximum setpoint in NA Item 7 velocity equipment schedule or MECH-EO form; indicate air terminal inlet velocity does not exceed 900 fpm NA C403.7, Sequence of operation Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC Item 8 36 NA C403.7, Maximum allowable system Verify fan system bhp is <_ 90% of the bhp limit per Option 2 equation in Table C403.2.11.1(1), Item 9 brake horsepower provide MECH-FANSYS form for each system Indicate all series and parallel terminal fans have electronically commutated motors; indicate NA C403.7, Fan -powered terminal unit DDC control system is configured to vary air terminal fan speed as a function of the load; Item 10 motor and control indicate fan speed during periods of low heating, low cooling, or ventilation only is <_ 66% of peak design air flow or provide supporting documentation for applied exception COPYRIGHT NOTICE 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 7 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 2 THIS LAYOUT/DESIGN IS A Mechanical Permit Plans Checklist MECH-CHK Service Water Heating Permit Plans Checklist SWH-CHK COPYRIGHTED WORK OWNED BY 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST') AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. O0 Q O T�T !!1� V Z 0 p z l� 0 0 r N � W O O 0 I.-: N W m fn ( N = H O Q Z O Y OF— N O Q O _ 0 � W Q o0 W �4 W H .4 Z�- p W U W a� 0 00 1—LL om �o S o U (0 fl- ow 0 0� o 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 U (0 Z Power echanical Fan System ' • 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 ls A• L OF WA tiR V � z .p 38898 p w� �� ��'GIST$4�' Ct�' �SSjCNAL�� SIGNED: 8/11 /2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11 /2017 JOB NUMBER 2015 WSEC MECH FORM, 117036 SHEET TITLE ENERGY CODE COMPLIANCE FORMS SHEET NUMBER M007 Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes C403.7, Application of single duct Indicate VAV terminal types on plans; verify fan -powered terminal units only serve perimeter NA Item 11 and fan -powered terminal zones with envelope loads;. verify all other zones are served by single duct terminal units units C403.7, Fan -powered terminal unit Indicate DDC controls are configured to automatically reset the primary supply air cfm setpoint NA Item 12 primary air reset of all fan -powered terminal units to the minimum required to maintain ventilation during occupied heating or deadband, based. upon the VAV air handling unit OSA ventilation fraction For spaces > 150 sf with occupant density >_ 25 people ! 1000 sf, indicate space is served by a NA C403.7, High occupancy space dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint; also Item 13 controls. indicate occupancy sensor control that automatically reduces minimum ventilation to zero and sets back room heating and cooling setpoints by >_ 5°F For server, electronic equipment, telecom or similar spaces with cooling loads > 5 W/sf, NA C403.7, Dedicated HVAC systems indicate spaces are served by independent HVAC systems that are separate from HPVAV Item 14 systems serving rest of building; indicate dedicated HVAC systems have air economizer controls or energy recovery per C403:3 Exception 9 Indicate whether systems are served by a high efficiency heating water plant, or a high efficiency chilled water plant If complying via high efficiency heating water plant: Indicate all VAV terminals have hydronic heating coils served. by heating water system with either gas -fired boiler(s) with thermal NA C403.7, Central plant efficiency efficiency >_ 90%, air -to -water heat pumps, or heat recovery chillers If complying via high efficiency chilled water plant: Indicate all VAV air handlers have cooling Item 15 coils se Project Title: Magic Toyota Edmonds WA Date 8/11/2017 For Building Dept. Use HVAC Air Distribution System Schedule List all HVAC systems that have the capability to provide heating and/or cooling to the spaces they serve. System or Primary Supply Fan ID Speed Control (Note 1) Description (Note 2) System Total ' Nameplate HP ' {Note 3} Fan Power Calculation i Required (Note 4) RTU-1 CV PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING 3 No RTU-2 CV PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING 2 No RTU-3 CV PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING 1 No RTU-4 CV PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING 1 No RTU-5 CV PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING 2 No Note 1 -Constant Volume (CV), Variable Air Volume (VAV), or Hospital/Lab CV system that qualifies for VAV budget per C403.2.11.1 Exception 1. Single zone VAV systems shall comply as CV. Note 2 =Describe system type and list all fans (or groups of fans) associated with the delivery and removal of conditioned air by the system.. Include all supply, return/relief, exhaust and exhaust hoods (>1 hp), make-up air, dedicated outside air (DOHS), booster fans, and series fah -powered terminals: VAV parallel fan -powered terminals and economizer relief fans do not need to be included if the fans do not operate at peak conditions. Note 3 = Enter the total nameplate hp of all fans associated with the delivery and removal of conditioned air by the system. Note 4 -This form automatically identifies whether aMECH-FANSYS form is required to demonstrate compliance with the fan power allowance (Yes), or this information is not required because the system has a combined total nameplate motor hp that is 5 hp or less (No) MECH-FANSYS.: Forms A MECH-FANSYS farm shall be provided for each system with total nameplate hp greater than 5 hp. Select (Add Fan System Form): to generate an additional form, Added forms can be deleted with button in cell E32 of he added form. 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 -Page 1 of 2 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 Project Title: Magic Toyota Edmonds WA Date 8/11/2017 The following information is necessary to check a permit application for compliance with the mechanicial systems and equipment requirements of the Washington State Energy Code, Commercial Provisions. Applicable Code Section Code Provision Information Required - Must be in permit documents Location in Building Department es,no,na Documents Notes Equipment -Sizing, Performance and Type Yes C404.2 SWH equipment type and Provide equipment schedule on plans indicating type and capacity; indicate efficiency complies efficiency with required federal standard P002, P003 For individual SWH equipment serving an entire building with >_ 1,000,000 Btu/h capacity, indicate thermal efficiency ? 90%; or exception taken For buildings with aggregate capacity of all SHW equipment >_ 1,000,000 Btu/h (exclude < High input -rated SWH NA C404.2.1 systems 100,000 Btu/h equipment from threshold calculation), indicate average capacity weighted thermal efficiency >_ 90%; or exception taken If applying Exception 1 for site -solar or site -recovered energy, provide calculations and source of annual service water heating energy use estimate Yes C404.4 Heat traps Indicate piping connected to equipment have heat traps on supply and discharge P001 Yes C404.5 Insulation under electric For electric water heaters located in unconditioned spaces or on concrete floors, indicate R-10 water heater insulation under equipment P001 Piping Systems Indicate thickness of piping insulation on plans per Table C403.2.9; verify insulation is provided Yes C404.6 Insulation of piping -from the water heater to the final fixture in a line, from the inlet /outlet piping at water heater to heat trap (up to 8 feet), and on piping that is heat traced; note exceptions taken p001 Indicate method of compliance on tans for all runs connecting service hot water source p piping 9 Yes C404.3 Efficient SWH supply piping to hot water fixture (maximum pipe length or maximum pipe volume method per Table. C404:3.T � provide calculations for all runs documenting the total length and / or volume )� P piping 9 P001 Service Water Heating System Controls For circulation systems with dedicated return piping, indicate controls are configured to automatically start pump based on demand for hot water and shut-off pump when there is no demand and when the desired water temperature is met P001 Yes C404.7.1 Heated -water circulating C404.8 systems For circulation systems with cold water supply serving as the return indicate controls piping 9 are configured to automatically start based on demand for hot water and shut-off um Y pump pump when there is no demand, or when temperature of water entering the cold water supply pipe is >_ 104°F P001 For heat trace systems provided to maintain temperature of service hot water in P piping, NA C404.7.2 Heat trace system controls indicate controls are configured to de -energize system when there is no demand for hot water Y and when the desired water temperature is met NA C404.7.3 Controls for hot water Forsystems with separate water heater and storage tank indicate controls are configured to 9 storage limit operation time of pump after end of heating cycle to <_ 5 minutes For SWH, pool /spa and pressure boosting pump motors >_ 7.5 hp, indicate method of variable 0 flow control VSD ore equivalent method that requires _ 30 /o design wattage at 50%desi n ( q 9 NA C403.2.13 Variable flow control - fluid flow); note exception taken C403.4.2.7 pumps Identify basis of pump speed control (differential or static pressure setpoint, pressure, zone load demand, etc Pools and Permanent Spas -Equipment and Controls (Sections are under C404.11} Pool heating equipment Provide equipment schedule on plans indicating type and capacity for all pool heating NA C404.10.1 efficiency equipment; indicate efficiency complies with required federal standard; for heat pump water heaters indicate COP >_ 4 NA C403.2.13 Variable flow control - Refer to Service Water Heating System Controls NA C404.10.1 Pool heater on /off controls Indicate automatic on /off control based on scheduling and readily accessible on /off switch C404.10.2 on heater that operates independent of thermostat setting; note exceptions taken For all pools and in -ground permanent spas, indicate a vapor retardant cover on plans NA C404.10.3 Pool covers For all pools and in -ground spas heated to > 90°F, indicate cover shall include insulation >_ R- 12 NA C404.10.3 Pool assembly insulation For all pools and in -ground spas heated to > 90°F, Indicate on plans. that sides and bottom are provided with insulation >_ R-12 NA C404.12 Energy consumption of Indicate portable spa complies with Association of Pool and Spa Professionals APSP-14 portable spas Energy Recovery (ER) Systems -Service Water Heating and Pool Systems C404.10.4 For buildings with pools or permanent spas with water surface area > 200 sf, indicate exhaust (Section Pools and permanent spas air ER method and use of waste heat (preheat ventilation air, pool water or service hot water); NA under exhaust systems or exception taken Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air C404.11) (energy recovery) temperature at design conditions by >_ 36°F For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote refrigeration capacity for coolers /freezers, indicate if condenser ER will be used to pre -heat. NA C403.5.3 Energy recovery - service water For buildings with >_ 40,000 sf conditioned floor area and with >_ 1,000,000 Btu/h of remote cooler /freezer condensers refrigeration. capacity for coolers /freezers,. indicate if condenser ER will be used to pre -heat service water For buildings with 24-hour operation and > 1,500,000 Btu/h of heat rejection capacity and NA C403.5.4 Energy recovery - design SWH load > 250,000 Btu/h, indicate condenser ER to pre -heat service water; or condenser systems exception taken. Provide calculations showing the amount of recovered heat that is utilized (60% of peak heat rejection load or pre -heat service water to 85°F). NA C404.10 Drain water heat recovery For systems incorporating drain water ER, indicate system design complies with CSA 655.2 units. (or CSA 55.1 for Group R); indicate potable waterside pressure loss at design flow is < 10 psi Service Water Heating Energy Use Metering NA C404.9 SWH energy usage in For Group R-2 multi -family buildings with central SWH systems, provide metering of hot water dwelling units energy usage per dwelling unit;. indicate metering and data reporting method SWH equipment energy use For new buildings 5Q,000 sf and building additions 25,000 sf, with total SWH equipment NA C409.3.2 metering capacity >_ 50 kW (>_ 170,600 Btu/h), verfiy energy use metering of all SWH equipment will be provided per C409 Additional Efficiency Package Option, Reduced Energy Use In Service Water Heating -Must comply with both provisions to be eligible To comply with additional efficiency package option, verify that >_ 90 % of the conditioned floor NA C406.7.1 Eligible building type area of the building is one or more of the occupancies identified in this section OR; g P Provide whole building energy analysis per C407 that demonstrates the SWH load in the > 0 building is _ 10 /o of total building energy loads To comply with additional efficiency option, provide documentation that verifies package P 0 _ 60 /° of building annual SWH ever is provided b high efficiency sources heat water 9 9Y p Y Y ( pump heater with COP >_ 3, waste heat recovery, solar water -heating system); NA C406.7.2 C403.5.4 Load fraction For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and design service hot water load > 250,000 Btu/h (per C403.5.4); provide documentation that 0 verifies >_ 100 /o of building annual SWH energy is provided by condenser energy recovery or other high efficiency source Documentation and Specific System Requirements to Supporting Commissioning Indicate that all SWH equipment and controls for which the WSEC requires control functions q Scope of service water and / or configuration to perform specific functions are required to be commissioned;+D7 P101 For buildings where the largest SWH system has ? 200,000 Btu/h total output capacity, Yes C408.4 heating systems commissioning indicate that all SWH systems regardless of individual capacity are required to be commissioned. Indicate that all pool and permanent spa water heating systems regardless of individual capacity are required to be commissioned q ' Scope of pool and Indicate that energy recovery equipment that heats pool water regardless of capacity is NA C408.4.1.3 permanent spa systems required to be commissioned; commissioning Identify all pool heating and energy recovery equipment and controls that the WSEC defines as being capable of and / or configured to perform specific functions. Indicate in plans and specifications that Cx per C408 is required for all applicable service water heating systems; P001 Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2 C404.13 C408.1.1 Commissioning including: narrative description of activites, responsibilities of the Cx team, schedule of Yes C408.1.2 requirements in construction activities including verification of project close out documentation per C103:6, and conflict of C408.1.4.2 documents interest plan (if required); P001 C103,6 Include in general summary that a Cx project report or Compliance Checklist (Figure C408.1.4.2) shall be completed by the Certified Cx Professional and provided to the owner prior to the final mechanical inspection. P001 Yes C408.4.1 Functional performance Identify in plans and specifications the intended operation of all equipment and controls during testing criteria all modes of operation, including inte M-ECHANICAL FIRST FLOOR -PLAN ---NORTH, i GENERAL NOTES: 1. AREAS IN WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEM PER IMC 502.14, TO BE PROVIDED BY OTHERS. 2. THE VEHICLE EXHAUST SYSTEM SHALL BE ENGINEERED BY OTHERS WITH DESIGN BY A REGISTERED DESIGN PROFESSIONAL OR SHALL BE FACTORY BUILT EQUIPMENT DESIGNED AND SIZED FOR THE PURPOSE. 3. THIS PROJECT UTILIZES A RETURN AIR PLENUM ABOVE CEILING SPACES AND A SUCH ALL MATERIALS IN THIS PLENUM SHALL MEET THE REQUIREMENTS OF IMC 602.2.1. 4. LOUVERS REPRESENT FLOW THROUGH NET FREE AREA AND MUST BE COORDINATED WITH THE ARCHITECT FOR INSTALLATION INTO THE TILT UP STRUCTURE. 5. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN ROUTING AND REFERENCE ONLY, SEE THE M-300 SERIES DRAWINGS FOR RADIANT PIPING DETAILS. RADIANT HEAT ZONE REFERENCE: 250 CFM I I I /L _.._.__ _ ! INTERIOR: ----- _ - - ---------- - r - v 1 + _` "1200I_ _ J �I T 0 GG„ __' __ _ , RZ B: 9.24 GPM ACROSS 17 CIRCUITS AND 2 MANIFOLDS l/ _________ - L-1 - C01-25 - 'r lT _ ; RG-1 RZ-C: 5.58 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-D: 8.27 GPM ACROSS 15 CIRCUITS AND 2 MANIFOLDS IF f .;'�``W." �`' RZ-E: 1.81 GPM ACROSS 5 CIRCUITS AND 1 MANIFOLD 4-- 4- Co2-12 C T C, " .. - _ a 6 0 i� 8"0 ------------� - I \ -- ----- - CD1 25 E,�� EWH-6 � \ r — � -- - 4 688 CFM r aLsl �_�PAEG2-175 F z z _ - �9 "�, , \ 4,688 CFM i � 1 mm124x24 SCREENED �,E ��`, t���„ i 2r4x24 SCREENED OPENINGI - 1 I �I I \ I I (OPENING , RZ D1 i--------------------- ' ----- i } _ _ - _ 1 �: _ __v_ _-- -- - ' I / C� EF-5 VFD RZ-D i - - ( Jp{ L - - -_--- - L------ ------ ---------------------`-- r � -------------------- ............. RZ-F - --- -- - - - -- %� -- ----- 21 RADIANT ZONE C _. 0 CO L.. - ' �, _ / — ' — 1 T�.v�l� �o ... i t ' F 'I I--r -J I F I F r J L J88x36 L I � gy-m, _ L----J L----J 11.0 SQ. FT. NFA 5,680 CFM I _ , T !-ir - -- I. RZ-C RADIANT PIPING MAIN L,---1--------►--------------- -----1------- -------------- �_______IL -11 ��. T 1 2 / T/Ct, c, I a, T EF-6 L-x: 2004" L-x: 20"x14" / 1.95 SQ. FT. NFA 12 ~} 1.95 SQ. FT. NFA i` / 1050 CFM _ ' \, l 1050 CFM -J� EXTERIOR: RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS KEY NOTES: 0 EXTERIOR ZONE (SNOW MELT) 2Q INTERIOR ZONE (COMFORT HEATING) 3Q SEE SHEET M303 FOR RADIANT PIPE SIZING A 1A t1 N 7 S H H 1 7 1 COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. • • 0 J 0 z.: N a� 00 Q� = p O z O p CO lir- N p L1J O o w tz U) w m co N = co -� O Q z � Y N O Q LL Co INS110 � o0� Lu W w � co 00 pco W �w �� oo zm o QLL �� 1(0 o U bm & CO SIGNED: 8/11 /2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL 08/11 /2017 tOB A 1 -: 11 ., SHEET TITLE MECHANICAL FIRST FLOOR PLAN - NORTH Ed01:4Ai,Ill 611Ail 4 1 1 - - -_ -- - - - ---------- ---- ------ - f ., GENERAL NOTES: 1. AREAS IN WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEM PER IMC 502.14, TO BE PROVIDED BY OTHERS. 2. THE VEHICLE EXHAUST SYSTEM SHALL BE ENGINEERED BY OTHERS WITH DESIGN BY A REGISTERED DESIGN PROFESSIONAL OR SHALL BE FACTORY BUILT EQUIPMENT DESIGNED AND SIZED FOR THE PURPOSE. 3. THIS PROJECT UTILIZES A RETURN AIR PLENUM ABOVE CEILING SPACES AND A SUCH ALL MATERIALS IN THIS PLENUM SHALL MEET THE REQUIREMENTS OF IMC 602.2.1. 4. LOUVERS REPRESENT FLOW THROUGH NET FREE AREA AND MUST BE COORDINATED WITH THE ARCHITECT FOR INSTALLATION INTO THE TILT UP STRUCTURE. 5. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN ROUTING AND REFERENCE ONLY, SEE THE M-300 SERIES DRAWINGS FOR RADIANT PIPING DETAILS. RADIANT HEAT ZONE REFERENCE: INTERIOR: RZ-A: 11.23 GPM ACROSS 19 CIRCUITS AND 2 MANIFOLDS RZ-B: 9.24 GPM ACROSS 17 CIRCUITS AND 2 MANIFOLDS RZ-C: 5.58 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-D: 8.27 GPM ACROSS 15 CIRCUITS AND 2 MANIFOLDS RZ-E: 1.81 GPM ACROSS 5 CIRCUITS AND 1 MANIFOLD EXTERIOR: RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS KEY NOTES: (1) SEE SHEET M303 FOR RADIANT PIPE SIZING COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. • • 0 z.: N a� 00 Q� Uj = p O z O p co III N p L1J O o � w U) W m Cn co N = O Q z � Y OF- N O Q 0 N LL Co F LL Co co 0 0000 W ¢ LU 75; Lu W F— p W o0 �� oo zm o QLL �� J o U � I co ;t ( I CD1-1 A � �'� o -- _ � � � �WAsh�' ti _, � � � EG2-150 a ` � � g;,� :D OPENINGI / I -= \ RG1 � -- ------`i % I` =,� --P3889E8�oG2-150 � � D2-GIST TO RTU-3 sioxL 2"C L----------------- -- ---------------- --- a t I I i SIGNED: 8 11 2017 .Ea .-. -.S-- - ----- "-8"0 - REVISIONS z - CD2-150 �1 12 0. ISSUE FOR PERMIT 8/11/2017 `i~% L-2 20"x14" 1.95 SQ. FT. NFA 1050 CFM � o 0 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11 /2017 JOB NUMBER 117036 SHEET TITLE MECHANICAL FIRST FLOOR PLAN - SOUTH Ed01:4AClII1611:40 1'I ■ 1�1J MECHANICAL FIRST FLOOR PLAN - SOUTH �_�;_�.1 �_,� ��_�;- �,__,1. ISCALE: 1 /8" = V-0" GENERAL NOTES: 1. THIS PROJECT UTILIZES A RETURN AIR PLENUM ABOVE CEILING SPACES AND A SUCH ALL MATERIALS IN THIS PLENUM SHALL MEET THE REQUIREMENTS OF IMC 602.2.1. 2. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN ROUTING AND REFERENCE ONLY, SEE THE M-300 SERIES DRAWINGS FOR RADIANT PIPING DETAILS. RADIANT HEAT ZONE REFERENCE: INTERIOR: RZ-A: 11.23 GPM ACROSS 19 CIRCUITS AND 2 MANIFOLDS RZ-B: 9.24 GPM ACROSS 17 CIRCUITS AND 2 MANIFOLDS RZ-C: 5.58 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-D: 8.27 GPM ACROSS 15 CIRCUITS AND 2 MANIFOLDS RZ-E: 1.81 GPM ACROSS 5 CIRCUITS AND 1 MANIFOLD EXTERIOR: RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS KEY NOTES: 1� RADIANT PIPING TO MECH ROOM, SEE M303. A 1 N 7 1 A S H H 1 7 1 KEY PLAN MECHANICAL SECOND FLOOR PLAN - NORTH COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. • • 0 z.: N a� 00 Q� Uj = p O z O p co lir- N p L1J O o � W%,m, w � U) W m Cn co N = ~ d00 Q z :D O Y OF- N O Q 0 N LL Co F LL Co co 0 0000 W ¢ LU 75; Lu W F- pcnW �0 �� oo zm o QLL �� J o U � & co SIGNED: 8/11 /2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11 /2017 JOB NUMBER 117036 SHEET TITLE MECHANICAL SECOND FLOOR PLAN - NORTH Ed01:4AClII161140 ISCALE: 1 /8" = V-0" 5 -------------------------------------------------------- -- -------------- --- -------------- -- ----------- -:I- E L. 7-7- 0 IJ 0 2 CD2-200 UP TO EF-3 - ------------- - 3 1-70 EG 6"0 CD1-100 CD2-200 ------------ 8"0 gjorRG1 EG1 -70 RG1 LE 0 "AG E 2 U RG1 rl2xlO, 04 1200: ic,41 \-12x10 RG1 ic,41 CD1 -90: CD1-90 36xl:2 28x14 UP TO P TO AHU: 4 %HU-4 (sF 'CURE CI ES 22,, C-80 2 \j. 5) -------------------- ---------- — LDl -475 CD2-200 LD1-425 —12"0 1604 -8"o XCD2-200 1,80 LDl -425 12"0-\ 2"0 " i CD1 -90 0 Q-1 - XR 20U 20xl 6 2000 24x 16 � 1 2"0 2"0 2"0 t IbIN 2406 ............. Fill lo"o lo"o C0111T T -)09: ----------- - CD3-250 CD3-250 R 12xl2 CD1-100 \ -6"0 UP TO EF-2 G2-2000 - — -------------- ------- ------------ 7 ---------------- ---------- T I ---------- - - ----- r 20xl 6 RG1'--- ---------------- T EG 'AIOMIN T I Tal ------------------- I 1604- UP TO EF-4 RG1 L 8"o CD2-150 2"0 00 2"0 A GENERALNOTES: 1 THIS PROJECT UTILIZES A RETURN AIR PLENUM ABOVE CEILING SPACES AND A SUCH ALL MATERIALS IN THIS PLENUM SHALL MEET THE REQUIREMENTS OF IMC 602.2.1. B -LDl -475 -LDl -425 i I M P401 m 1-425 14425 LDl -425 �/- -`1 ---------- --------- ---- ------------------ D ilmlyzip OMNI$ LDl -425 E 1-425 1-425 COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 2w-C 0 CD ui t:: U) U-1 m 3: :D co co -C-,,Jj -r co d 00 :D 0 0 F- c"I 0 < LL Co 0 co 0000 w Lu 0 75; Lu 0 cf) U) Lu U) p cn = W oo 2: cn 0 LL 2i C\l 0 0 AM& co SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 w --------------------------- - DESIGNED p -- - ------------ - - -------- -- -- -------- --- - ------------- �,�: r ----------------------- ----------- - -- — ------ G 36xl2�. c --- -- CSUSA NW EE 28x14 r i i UP TO 01! CE UP TO i i AHU-5 CD2- 00 CHECKED !AHU-5 CD2-250 CSUSA NW SAL D2-150 c N71 CD2-150 "0 ............... 8"0 RG1 0 0 8 0—� --------------- CD2-15 08/11/2017 -4 L4 --------------------------------------------------- -- 8"0 12*� CDx-150 RG1 JOB NUMBER 10"o r lo"o - -- --- -10"o i Cc 117036 "o 1 8"0 2"0 CD1-50 _0 8"0 6"0 CD3-250 CD3-225 SHEET TITLE CD2-20 RG1 CD3-250 CD3-250 A A MECHANICAL r . ............. RG1 SECOND FLOOR ------- — -- - ----- H PLAN - SOUTH N s SHEET NUMBER KEY PLAN M 1 0 3 zi 3 ISCALE: 1/8" = V-0" 12 1 11 1 1 9 ? `1 < �� i �1 ! i - I - _ - - - - I -- —I - - '* I �. I � I I z ti � I W - - - - - i� -_ \ - _ t i i' I , ft 1 j (80 CU-3 LBS (80 LBS) (80,/LBS) CU-7 (801BS) I 4 /F /f (80 LBS) } (578 LBS) , f ,F r j --------- --------- --- -- I ------------------------------------------N- ---------- / I 1 f` f --------------- --- \ ----------------------------- ----------------------------------- / / I I , ' 4 \ I -------------- ------ ---- - _ _ _ --- i ----------- I I I EF-9 (95 LBS) I 1' �11 j 10 _________ - (� MECHANICAL_ R00 PLAN - NORTH _ - --_____ ___ ___ ___ SCALE: 1 /8" = 1 '-0" GENERAL NOTES: 1. PROJECT STRUCTURAL ENGINEER TO PROVIDE ENGINEERING CALCULATIONS FOR SEISMIC ANCHORAGE OF THE ROOF TOP UNITS AND ANY OTHER ROOF TOP EQUIPMENT IN EXCESS OF 400 POUNDS. 2. PROJECT STRUCTURAL ENGINEER TO SPECIFY THE REQUIREMENTS FOR CONNECTION OF THE ROOF TOP UNITS TO THE CURBS AND THE CONNECTION METHOD OF THE CURBS TO THE ROOF STRUCTURE. A t1 N 7 1 A S H H 1 7 1 KEY PLAN COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. z., G O r W r M fn 0000 N _ Q z =) O Y N O Q N � =) (o LLCM0 O :u� �JE cn W Lf� W I— p N W Z U �- W 00 O m Qo O o U 00 SIGNED: 8 11 2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11/2017 JOB NUMBER 117036 SHEET TITLE MECHANICAL ROOF PLAN - NORTH s l:144AZ0161A4:1 7 6 5 J 2 --------------- — -------------------- ---- ------------- ---- ---- — I - -------------- - -- - ----- -------- --- - -------------- - --- --------------- --- - -------------- - --- --------------- ---- ---------- -- - -- - -------------- - --- --------------- ---- --------------- --- -- - ----------------- - --- ------------------- --- - ------------------ A GENERAL NOTES: -------------- - - - --------- 1 PROJECT STRUCTURAL ENGINEER TO PROVIDE -------------- -------- --------- ENGINEERING CALCULATIONS FOR SEISMIC ANCHORAGE OF THE ROOF TOP UNITS AND ANY (90 LBS) OTHER ROOF TOP EQUIPMENT IN EXCESS OF 400 POUNDS. 2. PROJECT STRUCTURAL ENGINEER TO SPECIFY THE REQUIREMENTS FOR CONNECTION OF THE ROOF TOP UNITS TO THE CURBS AND THE CONNECTION V. METHOD OF THE CURBS TO THE ROOF STRUCTURE. - ---------- _J ---- ------------------- --- ------------------- ---- _,tip ------------------- ---- ------------------- --- ------------------ t ,, E L L 00, 1 KEY PLAN COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 90-11 0 :5 0 mfn ZD co j --r c\j ob QCy) :z =) 0 CN 0 < C� LL U) � =) c") cc) 0 U) c) 7-- U) cc) ui LLJ LO LLJ F— W p of C\j U) -�7 > Lu W W F- IL F 3 00 2: cn 0 LL 2i c\j 0 C) U 00 SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11/2017 JOB NUMBER 1 117036 SHEET TITLE MECHANICAL ROOF PLAN - SOUTH s E i m 14 4 A Z L11 6 1 A 4 :1 M105 [.IMIECHANICAL ROOF PLAN SOUTH SCALE: CALE: 1/8" = 1'-0" 7 GENERAL NOTES: ------- - ------ -------- �'l -- ------- - IT 1. RADIANT ZONE OUTLINES ARE SHOWN ON -------------------------------------------- ................................................................................ M102 AND M103. :A 2. THIS SHEET SHOWN THE SUB SLAB RADIANT + PIPING AS IT WILL LAY OUT IN THE SPACE - -------------------------------------------- FROM THE MANIFOLDS, DETAILS OF THE ............................................... INSTALLATION SHALL BE PROVIDED IN SHOP ------ �/ - ---------------------------------------------------------------- --- ►- ----- - ------------------------------------------ DRAWINGS. _j IF 3. HYDRONIC PIPING MAINS FROM THE BOILER TO - ------- - -- - --- ------ ------- -------------------------- ----- - -- -------------- THE MANIFOLDS ARE SHOWN ON M102 AND M103. ............ .......... ....... ------------- ---------------------- 4. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - IS SHOWN ON M303. --------------------- ----------------- KEY NOTES: (D MANIFOLD FOR EXTERIOR RAMP (SNOW MELT) (Z MANIFOLD FOR EXTERIOR SERVICE DRIVE .............. (SNOW MELT) A R—Z --A-21 COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 0 :5 0 fn co co =) 0 0 cn 7;7 F— 0 < LL Cn 0 U) 75; U) ccoo UJ w ui co w p j ui �� um FLL 00 2: cn 0 2i C14 0 C) 0 4w 00 SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 �4 ---- -- -------- -- -------- - --------- - --------- -- — -- --- ---------------- --- - -- ----------------- ----- -------------------- -- ------ El - - ----- - ------------------------------------- - - ----- DESIGNED ------------------ - ------------ CSUSA NW EE F` f CHECKED CSUSA NW / SAL DATE 08/11/2017 JOB NUMBER 1 117036 ------------- - ------------------- SHEET TITLE ----------------- ----- - - ------------------------- RADIANT PIPING LAYOUT - NORTH N s SHEET NUMBER KEY PLAN M 300 z 7i RADIANT PIPING LAYOUT - SOUTH 4 5 3 r 4 B ------ ---- ---------------------- ---- ----------------- ---- ----------------- E ------ --- ---------------------- �` ----------------- GENERAL NOTES: 1. RADIANT ZONE OUTLINES ARE SHOWN ON M102AND M103. 2. THIS SHEET SHOWS THE SUB SLAB RADIANT PIPING AS IT WILL LAY OUT IN THE SPACE FROM THE MANIFOLDS, DETAILS OF THE INSTALLATION SHALL BE PROVIDED IN SHOP DRAWINGS. 3. HYDRONIC PIPING MAINS FROM THE BOILER TO THE MANIFOLDS ARE SHOWN ON M102 AND M103. 4. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM IS SHOWN ON M303. o� � o 0 �.o MENc� -- o 0 KEY PLAN COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 0 2W-C CN C) 00 Q< � r 'S 0 C6 m n C:) 7' c) 0 co IT- C,q LLJ 0 Lu U) U-1 m 3: co 00 -C-,,Jj -r �— cy) -�t 00 Of =) 0 0— �C-4 0 < C)f 0 (14 LL C0 2: CP E M 2 =) 0U) U) 0000 ujQ Lu Lu 6i 1_ CQ U) U) Lu U) p0 = Ld �� IL oo 2: 0 LL C\l 0 CD 0 00 SIGNED: 8/11/2017 REVISIONS 0. ISSUE FOR PERMIT DESIGNED CSUSA NW / EE 8/11/2017 CHECKED CSUSA NW / SAL 08/11/2017 JOB NUMBER 117036 SHEET TITLE RADIANT PIPING LAYOUT - SOUTH SHEET NUMBER [K I ills SCALE: 1/8" = l'-O" Lea% ( �.r---------------- GENERAL NOTES: 1. RADIANT ZONE OUTLINE FOR THE EXTERIOR RAMP IS SHOWN ON SHEET M304 AND THE MANIFOLD SUPPORTING IT IS SHOWN ON SHEET M102. 2. RADIANT ZONE OUTLINE FOR THE EXTERIOR SERVICE ENTRY/EXIT IS SHOWN ON SHEET C-1.1 AND THE MANIFOLD SUPPORTING IT IS SHOWN ON SHEET M102. 3. THIS SHEET SHOWS THE SUB SLAB RADIANT PIPING AS IT WILL LAY OUT IN THE SPACE FROM THE MANIFOLDS, DETAILS OF THE INSTALLATION SHALL BE PROVIDED IN SHOP DRAWINGS. 4. HYDRONIC PIPING MAINS FROM THE BOILER TO THE MANIFOLDS ARE SHOWN ON M102 AND M 103. 5. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM IS SHOWN ON M303. A 1 N 7 1 A S H H 1 7 1 KEY PLAN COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. • • 0 z., N 00 Q� 0 Uj = n O z O p M IT- N o W O o � w U) W m co co N = ~ Oo d 00 Q z � O Y N O Q O N LL Co F 2 =) 0 0000 W Q W 75; Lu W 1— ui U) p �� oo zm o QLL �0 o co e SIGNED: 8/11 /2017 REVISIONS 0. ISSUE FOR PERMIT DESIGNED CSUSA NW / EE 8/11/2017 CHECKED CSUSA NW / SAL 08/11 /2017 JOB NUMBER 117036 SHEET TITLE RADIANT PIPING LAYOUT - EXTERIOR SHEET NUMBER 3" (88.75 GPM) 2" (49.13 GPM) 2" (39.62 GPM) I Y Y I B-1 I B-2 399 MBH I 399 MBH J LJ C o ■ : I= P-2 vFD -1- W HX-1 W CO-GEN----------------------I BASIS OF DESIGN: 1. BOILERS TO BE STAGED NATURAL GAS COMBUSTION IN COMPLIANCE WITH WSEC C403.2.4.8. 2. DUAL BOILERS TO BE STAGED PER LOAD REQUIREMENTS AND OPERATE LEAD LAG WITH TURN DOWN CAPABILITY. 3. SNOW MELT SYSTEM SHALL BE DISABLED WHEN OUTSIDE AIR TEMPERATURE IS GREATER THAN 49 F. 4. INDOOR DESIGN TEMPERATURE IN SERVICE AREA = 65'F. 5. FLOOR TEMPERATURE RANGE = 74-75°F, NOT TO EXCEED 80°F. 6. FLOOR SURFACE IS SLAB ON GRADE WITH NO COVERING. MAIN PIPING LOOP FROM BOILERS TO MANIFOLDS TO BE SCH 10 STEEL. 7. RADIANT PIPING FROM MANIFOLD TO BE I" REHAU RAUPEX O2 BARRIER PIPE. 8. SYSTEM TO CONTAIN PROPYLENE GLYCOL AS REQUIRED FOR PROTECTION OF PIPE IN SNOW MELT APPLICATIONS. 9. RADIANT SUPPLY TEMPERATURE CALCULATED TO BE 100°F. 10. RADIANT SUPPLY/RETURN TEMPERATURE DIFFERENTIAL TO BE 20°F. 11. MANIFOLD FLOW BE REGULATED BY CONTROL VALVE WITH FEEDBACK FROM SLAB SENSOR. 12. SERVICE AREA CALCULATION IS 12 BTUH/SQUARE FOOT. 13. SNOW MELT APPLICATION IS 17.6 BUTH/SQUARE FOOT. 14. PIPE SPACING BASED ON 10". 15. BOILERS TO BE NATURAL GAS AND BACKUP TO A CO-GEN SYSTEM UTILIZING WASTE HEAT. 16. MAIN PUMPS TO BE ON VFD'S CONTROLLED BY DIFFERENTIAL PRESSURE. i���iP►I�111�I��1��il�l[�I�I\��I�J��I7I►[eIiP►i[i��1>��'������������I���I:ZiI:ZiI►��1�/1��:[�I��I:7\'�91►[e�� SNOW MELT LOOP [I�IZ1Z11 6141 " (39.62 GPM) /-2" (34.04 GPM) " (28.70 GPM) 1j" (19.43 GPM) ---------I----<---2 I �---------T--------q I � ---------T-----------� 9 UNDER SLAB CIRCUITS 9 UNDER SLAB CIRCUITS 1i" (13.85 GPM) TO SLAB SENSOR I I I I r-- - - - - - - I r 5.58 GPM i i 8.27 GPM T I I I SERVICE ENTRY SNOW MELT TO SLAB SENSOR I� I RZ-C /� T 4.43 GPM RZ-D1 3.84 GPM RZ-D2 'I i 10 UNDER SLAB CIRCUITS 8 UNDER SLAB CIRCUITS 9 UNDER SLAB CIRCUITS - - - - - - - - - - - -------->--------J I L-- T I TO SLAB SENSOR I tGPM 5 T 10 UNDER SLAB CIRCUITS 1" (5.58 GPM) COPYRIGHT NOTICE THIS LAYOUT/DESIGN IS A COPYRIGHTED WORK OWNED BY COMFORT SYSTEMS USA (NORTHWEST), INC. ("COMFORT SYSTEMS NORTHWEST") AND COMFORT SYSTEMS NORTHWEST HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED COPYING, PUBLICATION OR USE OF THIS LAYOUT/DESIGN AND TO OBTAIN DAMAGES THEREFORE. 0 cn W U) o 00 Q 0 U' N Q Z r W < G W N v � � r H 00 77 N 0 ti 00 SIGNED: 8/11 /2017 0 0 H U) W m 3: j= N H 00 O� ::) 0 O Q LL (n 0 U) U 2 Lu U) w H U ry O LL 'S 7-5 0 0 REVISIONS 0. ISSUE FOR PERMIT 8/11/2017 DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL DATE 08/11 /2017 tOB A11:111BER i • SHEET NUMBER ., ,IM MWN MMINOWMAINKORWAAMOMI SCALE: NTS 10' MIN FROM ANY EA INSULATED REFRIGERANT PIPING TO/FROM COPYRIGHT NOTICE FRESH AIR INTAKES OUTDOOR CONDENSING UNIT THIS LAYOUT/DESIGN IS A COORDINATE WITH COPYRIGHTED WORK OWNED BY ROOF PLANS COMFORT SYSTEMS USA OUTDOOR UNIT (NORTHWEST), INC. ("COMFORT TOP - - --------- CEILING FINISHED LI M MANUFACTURER'S WALL CU-x (SEE SCHEDULE) SYSTEMS NORTHWEST") AND RETURN AIRFLOW MOUNTING PLATE INSULATED REFRIGERANT PIPING TO/FROM INDOOR COMFORT SYSTEMS NORTHWEST DUCTLESS WALL UNIT BOLTED STEEL FAN COIL (AH) UNIT HEREBY RESERVES ITS RIGHT TO PREVENT UNAUTHORIZED FASTEN MOUNTING PLATE MOUNTING BRACKETS COPYING, PUBLICATION OR USE o TO WALL PER MANUFACTURER'S OF THIS LAYOUT/DESIGN AND TO DOWNBLAST CENTRIFUGAL SUPPLY AIRFLOW_.. -__`INSTALLATION INSTRUCTIONS OBTAIN DAMAGES THEREFORE. EXHAUST VENTILATOR, ALUMINUM AIRFLOW ROOF MOUNTED, DIRECT DRIVE INDOOR FAN COIL UNIT 92# ELECTRONICALLY COMMUTATED = WOOD, METAL STUD OR u- 0 LL CMU WALL, SEE ARCH PLANS VARI-FLOW MOTOR :�i < 0 FOR SPECIFIC WALL TYPE. EQUIPMENT RAILS LOW LEAK CLASS 1A RATED co 0 + ANCHOR BOLT TO CONC SLAB AT GRADE FASTEN DUCT TO CURB tEA EA MOTORIZED DAMPER IN TRAY '' INSULATION, 3# DENSITY ROOF CURB FLASHING00 ROOF CURB, 18 GA GALV STEEL FLOOR LINE CO C) FINISHED ROOF ROOF PER 12- SLOPE) (11 f NOTES: NOTES: 1. SEE EQUIPMENT SCHEDULE FOR AH-3/HP-3 MFG SYSTEM MODEL NUMBERS, POWER EXH DUI 1. AH-3/HP-3 SYSTEM SERVES ELEVATOR EQUIPMENT ROOM COOLING/HEATING LOADS ON REQUIREMENTS AND INCLUDED CONTROLS AND ACCESSORIES. FIRST FLOOR PER ARCH PLANS AND ELEVATOR SUBMITTALS. 0 2. SEE EQUIPMENT SCHEDULE FOR AH-3/HP-3 MFG SYSTEM MODEL NUMBERS, POWER = p NOTES: REQUIREMENTS AND INCLUDED CONTROLS AND ACCESSORIES. p 77 1. SEE EXHAUST FAN SCHEDULE FOR MFG MODEL NUMBERS AND INCLUDED CURB 3. INDOOR UNIT AH-3 IS POWERED FROM OUTDOOR UNIT HP-3. O 0 ACCESSORIES. FAN AND CURB BY SAME MANUFACTURER. N75; 'Q �' EXH FAN DETAIL EF-1, 2 K4WALL FAN COIL UNIT DETAIL AH-3 KTN CONDENSING UNIT DETAIL SCALE: NONE M4.1 SCALE: NONE NMl- ji SCALE: NONE SYSTEM POWER SUPPLY 208-230V/60HZ/1PH 10' MIN FROM ANY OSA INTAKE CD 0 0 V, FRESH AIR INTAKES Lu W OUTDOOR HIP UNIT COORDINATE WITH uj CARRIER 38MAQB09R--3 PLUMBING PLANS W 00 HP-3 (0.75T) HP-x > 00 ry < z 0 0 U) PACKAGED ROOFTOP UNIT (RTU) C-4 0 < o N u- w M 0 cQ co C ui ui 3: co cn ry EXTERIOR /D Lu U) cn ui ry p LAG BOLTS, SEE 4) - - -------------------------------- - STRUCTURAL FOR SIZES RTU, AHU OR ROOF - ry 0 0 m u- 75; INTERIOR AND SPACING INTAKE HOOD C\j 0 CD INSULATED REFER TUBING INDOOR UNIT POWERED FLASHING L 0 FROM OUTDOOR UNIT. LINE VOLTAGE BY ELEC CONTRACTOR - - R�l INSULATED ROOF CURB, BY MC. TYPICAL PLUMBING VENT >0 0 FACTORY RTU CURB = ROOF CURB AND RTU BY SAME MANUFACTURER ROOFING (BY GC) FINISHED ROOF A. AH-x W F. A DUCTLESS WALL UNIT AH-x - - -------------------------------------------------------------------------------- --- --------------------------------------------------------------------------------------- E-q c, ........... .......... j, NOTES: ILACD-1 1. SEE EQUIPMENT SCHEDULE FOR AH-x/CU-x MFG SYSTEM MODEL NUMBERS, POWER REQUIREMENTS AND INCLUDED CONTROLS AND ACCESSORIES. NOTES: 38898 GIST 1. SEE RTU SCHEDULES FOR MFG MODEL NUMBERS AND INCLUDED CURB ACCESSORIES. FAN SIGNAL AND CURB BY SAME MANUFACTURER (14- ROOF CURB OPTION). SIGNED: 8/11/2017 HEAT PUMP SYSTEM SCHEMATIC HP-3 K'6-'ROOFTOP UNIT MOUNTING DETAIL K'lo' OUTSIDE AIR INTAKE DETAIL SCALE: NONE M4.1 SCALE: NONE M4.1 SCALE: NONE REVISIONS 0. ISSUE FOR PERMIT 8/11/20171 MIN 1-1/2" WIDE HANGER BAND DESIGNED CSUSA NW / EE CHECKED CSUSA NW / SAL FLEX DUCT DATE MIN RADIUS IS 1 X DIAMETER CLAMP 08/11/2017 ATTACH W/METAL CLIPS OR SCREWS JOB NUMBER --------------------------------------------------------------------------- 117036 SHEET TITLE CEILING MECHANICAL DIFFUSER DETAILS SHEET NUMBER M400 K'9-'CEILING DIFFUSER DETAIL M4.1 SCALE: NONE