0494 Magic Toyota Mech Binder For Permit.pdfABBREVIATIONS
GENERAL
- LEGEND
0
DIAMETER
-■EQUIPMENT TAG TYPE
ABV
ABOVE
AD
ACCESS DOOR
EQUIPMENT TAG NUMBER
AFF
ABOVE FINISHED FLOOR
AHU
AIR HANDLING UNIT
-•----DETAIL
OR DIAGRAM NUMBER
AP
ACCESS PANEL
-0 -■SHEET
NUMBER WHERE DETAIL/DIAGRAM SHOWN
APRVD
APPROVED
BF
BELOW FLOOR
1 -•SECTION
LETTER
BFC
BELOW FINISHED CEILING
SHEET NUMBER WHERE SECTION IS SHOWN
BOT
BOTTOM
BTU
BRITISH THERMAL UNIT
(�LD A
REVISION CLOUD AND CHRONOLOGICAL NUMBER
CD
CEILING DIFFUSER
CFM
CUBIC FEET PER MINUTE
DETAIL REFERENCE OUTLINE
CIP
CAST IN PLACE
L - - - - J
CLG
CEILING
POINT OF CONNECTION TO EXISTING OR TO
CONC
CONCRETE
OTHERS' WORK
CONN
CONNECTION
CW
COLD WATER
1�
KEY NOTE CALLOUTS
DB
DRY BULB
DIMS
DIMENSIONS
WORK TO BE REMOVED
DN
DOWN
DR
DRAIN
0 4' 8'
16'
DWG
DRAWING
DRAWING SCALE
SCALE: 1 /8" =
1'-O"
EA
EACH
EAT
ENTERING AIR TEMPERATURE
EF
EXHAUST FAN
HVAC -
LEGEND
EG
EXHAUST GRILLE
EQUIP
EQUIPMENT
ESP
EXTERNAL STATIC PRESSURE
AIR FLOW DIRECTION
EWT
ENTERING WATER TEMPERATURE
SUPPLY OR OSA DUCT SECTION UP, ROUND OR RECTANGULAR
EXH
EXHAUST
FF
FINISHED FLOOR
FPM
FEET PER MINUTE
RETURN, RELIEF OR EXHAUST DUCT SECTION UP, ROUND OR
FT
FOOT OR FEET
RECTANGULAR
FUT
FUTURE
GAL
GALLON
> <
SUPPLY OR OSA DUCT SECTION DOWN, ROUND OR
GALV
GALVANIZED
RECTANGULAR
GD
GREASE DUCT
HP
HORSEPOWER
RETURN, RELIEF OR EXHAUST DUCT SECTION DOWN, ROUND
HT
HEIGHT
OR RECTANGULAR
HVAC
HEATING, VENTILATING AND
AIR-CONDITIONING
RG - 100
RETURN AIR GRILLE, NUMBER INDICATES CFM QUANTITY
HWR
HEATING WATER RETURN
HWRR
HEATING WATER REVERSE RETURN
HWS
HEATING WATER SUPPLY
CD - 100
SUPPLY AIR DIFFUSER, NUMBER INDICATES CFM QUANTITY
IBC
INTERNATIONAL BUILDING CODE
ID
INSIDE DIAMETER
IFGC
INTERNATIONAL FUEL GAS CODE
EG - 100
EXHAUST AIR GRILLE, NUMBER INDICATES CFM QUANTITY
IMC
INTERNATIONAL MECHANICAL CODE
IN
INCHES
IN WG
INCHES WATER GAUGE
SO - 100
SCREENED OPENING, NUMBER INDICATES CFM QUANTITY
LAT
LEAVING AIR TEMPERATURE
LBS
POUNDS
EXISTING DUCTWORK
LD
LINEAR DIFFUSER
_ - - - _ - _
LIN FT
LINEAR FOOT OR FEET
- - - - - - -
SLSM SOUND LINED SHEET METAL
LWT
LEAVING WATER TEMPERATURE
FLEXIBLE EQUIPMENT CONNECTION
MAX
MAXIMUM
MBH
1000 BTU PER HOUR
SFD COMBINATION FIRE AND SMOKE DAMPER
MD
MOTORIZED DAMPER
MIN
MINIMUM
FD FIRE DAMPER
MOCP
MAX OVER CURRENT PROTECTION
MUA
MAKE UP AIR
SD SMOKE DAMPER
N/A
NOT APPLICABLE
OBD
OPPOSED BLADE DAMPER
VOLUME DAMPER
OD
OUTSIDE DIAMETER/DIMENSION
OSA
OUTSIDE AIR
MOTORIZED DAMPER
PH
PHASE
PN
PROJECT NORTH (REFERENCE)
TURNING VANES
POC
POINT OF CONNECTION
PRESS
PRESSURE
PSI
POUNDS PER SQUARE INCH
ROUND TO ROUND 45° FITTING
RA
RETURN AIR
RG
RETURN GRILLE
RL
REFRIGERANT LIQUID LINE
SPIN IN TAP
RPBP
REDUCED PRESSURE BACKFLOW
PREVENTER
RPM
REVOLUTIONS PER MINUTE
SQUARE TO ROUND 45° FITTING
RS
REFRIGERANT SUCTION LINE
SA
SUPPLY AIR
SCHD
SCHEDULE OF EQUIPMENT
SFD
SMOKE FIRE DAMPER
45° FITTING FOR DUCTWORK
SG
SIDEWALL GRILLE
SOG
SLAB ON GRADE
GAS
NATURAL GAS PIPING
SL
SOUND LINED
SMACNA
SHEET METAL NATIONAL ASSOCIATION
CO
CARBON MONOXIDE SENSOR
SQ FT
SQUARE FOOT OR FEET
SS
STAINLESS STEEL
NO2
NITROGEN DIOXIDE SENSOR
TDH
TOTAL DYNAMIC HEAD
�p
OCCUPANCY SENSOR
TG
TRANSFER GRILLE
TN
TRUE NORTH
SW
SWITCH (ON/OFF/TIMER)
TYP
TYPICAL
UNO
UNLESS NOTED OTHERWISE
O
REMOTE SENSOR
UPC
UNIFORM PLUMBING CODE
VFD
VARIABLE FREQUENCY DRIVE
SC
SPEED CONTROLLER
VTR
VENT THROUGH ROOF
W
WATTS OR WIDTH
OT
THERMOSTAT
W/
WITH
W/O
WITHOUT
WB
WET BULB
; TERMINAL UNIT
WG
WATER GAUGE
REQUIRED EQUIPMENT CLEARANCE
WSEC
WASHINGTON STATE ENERGY CODE
- - - - -
J
Ems
1. HEATING AND COOLING SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH
STANDARD ENGINEERING PRACTICES AND AS REQUIRED BY 2015 WSEC
SECTIONS C403.2.1 AND C403.2.2.
2. OUTSIDE AIR VENTILATION SHALL BE PROVIDED IN ACCORDANCE WITH 2O15
IMC TABLE 403.3 FOR MIN REQUIRED RATES AND NO MORE THAN 150% OF
MIN RATES PER 2015 WSEC SECTION C403.2.6. DEMAND VENTILATION
CONTROLS SHALL BE PROVIDED AS REQUIRED BY 2015 WSEC SECTION
C403.2.6.2, FOR DENSELY OCCUPIED SPACES GREATER THAN 500 SQ Ff.
3. HVAC SYSTEMS HAVE BEEN DESIGNED TO COMPLY WITH 2O15 WSEC
SECTION C302.1 AND TO MAINTAIN 72F MAX IN HEATING MODE AND 75F
MIN IN COOLING MODE. CONTROLS SHALL BE CONFIGURED TO PROVIDE 5
DEGREE DEAD BAND PER WSEC SECTION C403.2.4.1.2.
4. CONTROLS FOR SYSTEMS THAT DO NOT OPERATE CONTINUOUSLY SHALL BE
CAPABLE OF PROVIDING 7 DAY PROGRAMMABLE TEMPERATURE SETTINGS,
AUTOMATIC SETBACK AND SHUTOFF AND OPTIMUM START AS REQUIRED BY
2015 WSEC SECTION C403.2.4.2. MOTORIZED DAMPERS SHALL BE PROVIDED
FOR POSITIVE SHUTOFF AS REQUIRED BY 2015 WSEC SECTION C403.2.4.3,
INCLUDING MAXIMUM LEAKAGE RATES. GRAVITY DAMPERS USED FOR OUTSIDE
AIR INTAKE SHALL BE PROTECTED FROM WIND INFLUENCES.
5. DIRECT DIGITAL CONTROL (DDC) SYSTEMS SHALL BE PROVIDED AS REQUIRED
BY 2015 WSEC SECTION C403.2.4.12.1 AND SHALL BE CAPABLE OF
PROVIDING TRENDING, MONITORING AND SYSTEM DEMAND INFORMATION.
6. DUCT WORK SHALL BE INSULATED AND PROVIDED WITH VAPOR BARRIER AS
REQUIRED BY 2012 WSEC SECTION C403.2J AND AS FOLLOWS:
TYPE LOCATION R-VALUE
OS AIR >2800 CFM IN CONDITIONED SPACE 19
OS AIR <2800 CFM IN CONDITIONED SPACE 7
SUPPLY OR RETURN IN UNCONDITIONED SPACE 6
SUPPLY OF RETURN OUTSIDE BUILDING 8
7. ALL DUCTWORK SPECIFIED SHALL BE CLASSIFIED AS LOW PRESSURE AND
SHALL BE INSTALLED IN ACCORDANCE WITH 2O15 IMC REQUIREMENTS AND
SMACNA STANDARD FOR 2" WG, UNLESS HIGHER STATIC PRESSURE ARE
INDICATED ON DRAWINGS.
8. MECHANICAL PIPING, IF EXPOSED TO THE ENVIRONMENT, SHALL BE
PROTECTED IN ACCORDANCE WITH 2O15 WSEC SECTION C403.2.9.1 AND ALL
PIPING SHALL BE INSULATED AS REQUIRED BY 2015 WSEC SECTION
C403.2.9.
9. AIRSIDE ECONOMIZERS SHALL BE USED AS A FIRST STAGE OF COOLING AND
SHALL BE CAPABLE OF PROVIDING FULL OR PARTIAL COOLING CAPACITY
DEPENDING ON THE COOLING DEMAND AND THE OUTSIDE AIR TEMPERATURE
PER 2075 WSEC SECTION C403.3.1. FIXED DRY BULB CONTROL SHALL
MODULATE THE OUTSIDE AIR FLOW DOWN TO THE MINIMUM AMOUNT AT
OUTSIDE AIR TEMPERATURES OVER 75F.
10. SUPPLY AIR TEMPERATURE SHALL BE AUTOMATICALLY RESET FOR MULTIPLE
ZONES AND SYSTEMS BASED ON DEMAND, AS REQUIRED BY 2015 WSEC
SECTION C403.4.4.4
11. PROVIDE SEISMIC BRACING AND SUPPORTS IN ACCORDANCE WITH 2O12 IBC
FOR SEISMIC DESIGN CATEGORY D AND BASED ON AN IMPORTANCE FACTOR
OF 1.0 FOR ALL SYSTEMS, EXCEPTING THE GAS PIPING SHALL HAVE AN
IMPORTANCE FACTOR OF 1.5.
12. PROVIDE EACH INDIVIDUAL GRILLE, REGISTER, DIFFUSER AND OUTSIDE AIR
CONNECTION WITH A VOLUME DAMPER OR OTHER MEANS OF ADJUSTMENT
AS REQUIRED BY 2015 IMC, SECTION 603.18.
13. HVAC DISTRIBUTION SYSTEMS SHALL BE BALANCED TO MINIMIZE THROTTLING
LOSSES AS REQUIRED BY 2015 WSEC SECTION C408.2.2
14. FUNCTIONAL TESTING OF ALL MECHANICAL SYSTEMS SHALL BE PROVIDED TO
ENSURE PROPER OPERATION IN ALL SEQUENCES OF OPERATION, INCLUDING
POWER FAILURE AS REQUIRED BY 2015 WSEC SECTION C408.2.3.
SYSTEMS COMMISSIONING
PROVIDE COMMISSIONING PER SECTION C408 OF THE WSEC COMMERCIAL
PROVISIONS. COPIES OF ALL EQUIPMENT DATA AND DOCUMENTATION THAT
RELATES TO COMMISSIONING, SHALL BE PROVIDED TO THE OWNER AND MADE
AVAILABLE TO THE AHJ WITHIN 90 DAYS OF RECEIPT OF COO, INCLUDING:
1. COMMISSIONING (Cx) PLAN, PRELIMINARY Cx REPORT, Cx COMPLIANCE
CHECKLIST (2015 WSEC FIGURE C408.1.4.2) AND RELATED REPORTS,
SUCH AS AIR BALANCING, START-UP AND PRESSURE TESTING DATA.
2. RECORD DRAWINGS DEPICTING FINAL INSTALLATION CONFIGURATIONS OF
SYSTEMS AND EQUIPMENT AS REQUIRED BY 2015 WSEC SECTION C103.6.
3. IOM EQUIPMENT MANUALS SHALL INCLUDE MFG INFORMATION WITH MODEL
NUMBERS AND OPTIONS, CONTROLS DATA, INCLUDING CALIBRATION AND
DESIGN SETPOINT INFORMATION, AND RECOMMENDED MAINTENANCE
SCHEDULE WITH CSUSA NW CONTACT INFORMATION.
4. TRAINING OF THE MAINTENANCE STAFF SHALL BE PROVIDED, INCLUDING
REVIEW OF DOCUMENTATION, HANDS-ON DEMONSTRATION OF OPERATION
AND START-UP PROCEDURES AND A TRAINING COMPLETION REPORT.
5. WHOLE BUILDING AND COMMISSIONING OF SYSTEMS THAT ARE NOT
INCLUDED IN THE MECHANICAL CONTRACTOR'S SOW SHALL BE PROVIDED,
IN ACCORDANCE WITH 2015 WSEC SECTION C408.1, BY OTHERS.
6. COMMISSIONING OF MECHANICAL SYSTEMS AND CONTROLS SHALL BE
PROVIDED BY A CERTIFIED COMMISSIONING PROFESSIONAL AS REQUIRED
FOR BUILDINGS WITH TOTAL COOLING CAPACITY OVER 240 MBH OR TOTAL
HEATING CAPACITY OVER 300 MBH PER 2015 WSEC SECTION C408.1.
THE PROPOSED PROJECT AT 21300 HIGHWAY 99, EDMONDS, WA CONSISTS
OF A NEW TWO STORY REPLACEMENT STRUCTURE OF APPROXIMATELY
48,086 GROSS SQUARE FEET OF AUTOMOTIVE SALES, SERVICE AND PARTS
SUPPORT. THE PROJECT ALSO INCLUDES ALL INFRASTRUCTURE AND SITE
WORK NECESSARY TO SUPPORT THE STRUCTURE.
BUILDING INF
PROJECT ADDRESS:
MAGIC TOYOTA
21300 HIGHWAY 99
EDMONDS, WA 98020
PROPERTY OWNER:
BROADUS FAMILY LLC
120 - 116TH AVE NE
BELLEVUE, WA 98004
TEL 425-775-4422
CONTACT: DAVID BROADUS
SNO CO TAX PARCEL:
00580700000601
00580700000602
00580700000604
00580700000605
00580700000607
00580700000608
CITY OF EDMONDS, LOT
LINE ADJUSTMENT PLN20170016 AND AS FILED WITH
SNOHOMISH COUNTY AS
DOCUMENT 201705165010 CREATING LOT 1 AND LOT
2 WAS FILED AND RECORDED ON 16 MAY 2017. AS OF THIS RE -SUBMITTAL
OF PERMIT ISSUE DRAWINGS
THE COUNTY HAS NOT ISSUED NEW PARCEL
NUMBERS FOR THE AFFECTED PARCELS LISTED ABOVE.
ZONING:
GC-2
CONSTRUCTION TYPE:
B/S-1
FIN FLR ELEV:
+100'-0" (FIRST FLR) & +112'-10° (SECOND FLR)
PARAPET ELEV:
+128'-0"
CLIMATE ZONE:
4C SNOHOMISH (WSEC TABLE C301.1)
MECHANICAL
SCOPE
NEW MECHANICAL HVAC SYSTEMS TO SUPPORT CONSTRUCTION OF A 2 STORY
STRUCTURE CONSISTING OF A SALES FLOOR, GENERAL OFFICE SPACE, A PARTS
DEPARTMENT, SERVICE AREA AND PARKING DECK. MECHANICAL WORK
INCLUDES THE FOLLOWING:
1. HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS TO SERVE THE
AUTO SHOW ROOM AND OFFICE SPACES AS SHOWN ON THESE DRAWINGS.
2. EXHAUST SYSTEMS FOR RESTROOMS, BREAK ROOMS AND SERVICE AREA.
3. DUCTLESSS MINI SPLIT SYSTEM AIR-CONDITIONING UNITS FOR SMALL
SERVER AND EQUIPMENT ROOMS.
4. AN IN SLAB HOT WATER (HYDRONIC) RADIANT HEATING SYSTEM IN THE
SERVICE AND NEW CAR DELIVERY AREAS.
5. AN IN GROUND HOT WATER (HYDRONIC) RADIANT HEATING SYSTEM FOR
SNOW MELT, TWO LOCATIONS.
6. ALL ASSOCIATED DUCTWORK, PIPING, GRILLES, REGISTERS, DIFFUSERS,
ACCESSORIES AND STAND-ALONE CONTROLS, AS REQUIRED, FOR A
COMPLETE INSTALLATION.
7. EQUIPMENT START-UP, AIR BALANCE, PROGRAMMING AND TRAINING FOR
NEW EQUIPMENT, O&M MANUALS.
��1�:7_1
R1ml[HIX
1. COORDINATE ALL NEW WORK WITH THE STRUCTURE AND OTHER TRADES.
FIELD VERIFY UNIT LOCATIONS, DROPS AND POSITIONS. HVAC EQUIPMENT
WEIGHTS AND LOCATIONS SHALL BE APPROVED BY STRUCTURAL
ENGINEER.
2. EQUIPMENT LOCATIONS, PIPE AND DUCTWORK DIMENSIONS SHOWN ON
PLANS AND DETAILS ARE NOMINAL SIZES.
3. MAX FLEX DUCT LENGTH SHALL BE 8'-0". SUPPLY AND RETURN AIR
DUCTWORK SHALL BE LINED WITH 1" SOUND LINER (SL) WITHIN 10' OF
EQUIPMENT.
4. AN ACCESSIBLE
GAS SHUT-OFF VALVE
SHALL BE INSTALLED WITHIN 3'
OF ALL GAS APPLIANCES.
GAS PIPING
SHALL RUN BELOW THE ROOF,
UNLESS NOTED
OTHERWISE.
5. HEATING AND COOLING LOAD CALCULATIONS USE THE FOLLOWING DESIGN
TEMPERATURES
IN ACCORDANCE WITH
2015 WSEC AND THE ASHRAE
RECOMMENDED
OUTDOOR DESIGN TEMPERATURES FOR WASHINGTON:
SUMMER OSA:
83°F DB / 65F WB
SA HEATING: 95°F MAX
WINTER OSA:
247 DB
SA COOLING: 55°F MIN
6. ROOM SENSORS SHALL BE MOUNTED ON WALLS NO MORE THAN 48"
ABOVE FINISHED FLOOR FOR ADA ACCESSIBILITY, AS REQUIRED.
7. ALL LINE VOLTAGE WORK SHALL BE BY ELECTRICIAN (SEPARATE PERMIT).
A 120-VOLT SERVICE RECEPTACLE SHALL BE LOCATED WITHIN 25' OF
VICINITY MAP
I I\VULV I JI 1 L
APN 000140-0036
8. ALL DUCT MOUNTED SMOKE DETECTORS SHALL BE SUPPLIED AND
INSTALLED BY THE MECHANICAL CONTRACTOR. SMOKE DETECTOR WIRING
SHALL BE BY ELECTRICIAN; SIGNAL SHALL BE RECEIVED BY FIRE AND
LIFE SAFETY. ALL FIRE/SMOKE DAMPERS AND SMOKE DETECTORS SHALL
BE POWERED BY OTHERS.
9. SEE A-0.3 FOR REFERENCE TO AIR BARRIER NOTES AND ALLOWABLE
INFILTRATION AT THE BULDLING ENVELOPE.
LEGAL DESCRIPTION
SOLNERS 5 ACRE TRACTS BLK 000 D-01- N 317 FT OF W 3 AC EXC
20 FT THOF.
NE � Of THE NW � SECTION 29, TOWNSHIP 27N RANGE E4, W.M.
APPLICABLE CODES
1. 2015 WASHINGTON STATE ENERGY CODE (WAC) CHAPTER 51-11)
2. 2015 INTERNATIONAL BUILDING CODE (WAC CHAPTER 51-50)
3. 2015 INTERNATIONAL MECHANICAL CODE (WAC CHAPTER 51-52),
4. 2015 INTERNATIONAL FUEL GAS CODE (WAC CHAPTER 51-52)
5. 2015 UNIFORM PLUMBING CODE (WAC CHAPTER 51-56)
DRAWING INDEX
SHEET #
SHEET TITLE
SCALE
M001
MECHANICAL COVER SHEET
N/A
M002
MECHANICAL EQUIPMENT SCHEDULES
N/A
M003
MECHANICAL EQUIPMENT SCHEDULES
N/A
M004
MECHANICAL HVAC LOAD CALCULATIONS
N/A
M005
MECHANICAL HVAC LOAD CALCULATIONS
N/A
M006
ENERGY CODE COMPLIANCE FORMS
N/A
M007
ENERGY CODE COMPLIANCE FORMS
N/A
M100
MECHANICAL FIRST FLOOR PLAN - NORTH
1/8"=1'-0"
M101
MECHANICAL FIRST FLOOR PLAN - SOUTH
1/8"=1'-0"
M 102
MECHANICAL SECOND FLOOR PLAN - NORTH
1 /8"=1'-0"
M103
MECHANICAL SECOND FLOOR PLAN - SOUTH
1/8"=1'-0"
M104
MECHANICAL ROOF PLAN - NORTH
1/8"=1'-0"
M105
MECHANICAL ROOF PLAN - SOUTH
1/8"=1'-0"
M300
RADIANT PIPING LAYOUT - NORTH
1/8"=1'-0"
M301
RADIANT PIPING LAYOUT - SOUTH
1/8"=1'-0"
M302
RADIANT PIPING LAYOUT - EXTERIOR
3/32"=1'-0"
M303
RADIANT PIPING SCHEMATIC DIAGRAM
N/A
M400
MECHANICAL DETAILS
AS NOTED
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
z.,
0
2
CDO
W
co
Lu
m
Cn 00
N =
i-
m
d.
Qz
�o
N
O Q
QzS
v
w Q
W cj
w
W E-
p
WU
W
firy
W
IL
3
oo
zm
Qo
�00
2
i
0
�
L
00
�
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
08/11/2017
JOB NUMBER
117036
SHEET TITLE
MECHANICAL
COVER SHEET
SHEET NUMBER
COPYRIGHT NOTICE
HEAT PUMP SCHEDULE
TAG
MANUFACTURER AND MODEL
LOCATION
DESCRIPTION
MIN COOLING
PERFORMANCE
MIN HEATING
PERFORMANCE
R-410A PIPING
MAX INDOOR
FAN AIRFLOW
(CFM)
MAX
SOUND
(dB -A)
CONTROLLER
TYPE
FILTER
TYPE
60 HERTZ ELECTRICAL
WEIGHT
(LBS)
NOTES:
LIQUID
(IN)
SUCTION
(IN)
MAX LENGTH
(FEET)
TOTAL (MBH)
SEER
EER
TOTAL (MBH)
HSPF
VOLT
PH
MCA
AH-1
MITSUBISHI MSZ-GL15NA-Ul
223 - ELEV EQUIP RM
DUCTLESS WALL
14,000
21.6
18,000
11.7
0.25
0.50
65
533
49
WIRELESS
REMOTE
ANTI ALLERGY
ENZYME
208/230
1
1
22
1, 2, 3, 4, 5, 6, 7, 8, 9
CU-1
MITSUBISHI MUZ-GL15NA-Ul
ROOF
OUTDOOR UNIT
51
10
81
AH-2
MITSUBISHI MSZ-GL15NA-Ul
218 - IT RM
DUCTLESS WALL
14,000
21.6
18,000
11.7
0.25
0.50
65
533
49
WIRELESS
REMOTE
ANTI ALLERGY
ENZYME
208/230
1
1
22
1, 2, 3, 4, 5, 6, 7, 10
CU-2
MITSUBISHI MUZ-GL15NA-Ul
ROOF
OUTDOOR UNIT
51
10
81
AH-3
MITSUBISHI SLZ-KA15NA
171 - TECH LOUNGE
CEILING CASSETTE
15,000
16.0
18,000
9.6
0.25
0.50
65
390
40
WIRED
REMOTE
POLYPRO
HONEYCOMB
208/230
1
1
36
1, 2, 3, 4, 5, 6, 7, 8
CU-3
MITSUBISHI SUZ-KA15NA
ROOF
OUTDOOR UNIT
51
12
80
AH-4
MITSUBISHI SLZ-KA15NA
148 - WORK RM
CEILING CASSETTE
15,000
16.0
18,000
9.6
0.25
0.50
65
390
40
WIRED
REMOTE
POLYPRO
HONEYCOMB
208/230
1
1
36
1, 2, 3, 4, 5, 6, 7, 8
CU-4
MITSUBISHI SUZ-KA15NA
ROOF
OUTDOOR UNIT
51
12
80
AH-5
MITSUBISHI SLZ-KA15NA
147 - T&I
CEILING CASSETTE
15,000
16.0
18,000
9.6
0.25
0.50
65
390
40
WIRED
REMOTE
POLYPRO
HONEYCOMB
208/230
1
1
36
1, 2, 3, 4, 5, 6, 7, 8
CU-5
MITSUBISHI SUZ-KA15NA
ROOF
OUTDOOR UNIT
51
12
80
AH-6
MITSUBISHI SLZ-KA15NA
145 - SUPPORT
CEILING CASSETTE
15,000
16.0
18,000
9.6
0.25
0.50
65
390
40
WIRED
REMOTE
POLYPRO
HONEYCOMB
208/230
1
1
36
1, 2, 3, 4, 5, 6, 7, 8
CU-6
MITSUBISHI SUZ-KA15NA
ROOF
OUTDOOR UNIT
51
12
80
AH-7
MITSUBISHI SLZ-KA15NA
144 - SERVICE MGR
CEILING CASSETTE
15,000
16.0
18,000
9.6
0.25
0.50
65
390
40
WIRED
REMOTE
POLYPRO
HONEYCOMB
208/230
1
1
36
1, 2, 3, 4, 5, 6, 7, 8
CU-7
MITSUBISHI SUZ-KA15NA
ROOF
OUTDOOR UNIT
51
12
80
NOTES:
1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
2. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH AND CONVENIENCE OUTLET, AS APPLICABLE.
3. INCLUDES SINGLE POINT ELECTRICAL CONNECTION; INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.
4. HEATING PERFORMANCE FOR HEAT PUMP ONLY AT HIGH HEAT, RATED IN ACCORDANCE WITH ARI STANDARD 340/360-7 AS APPROPRIATE.
5.
PROVIDE
WITH
AFTER MARKET CONDENSATE PUMP; ROUTE CONDENSATE
TO AN APPROVED LOCATION.
6.
PROVIDE
WITH
MANUFACTURER'S RECOMMENDED ACCESSORIES FOR LOW
AMBIENT COOLING APPLICATIONS.
7.
PROVIDE
WITH
LOCKING REFRIGERANT CIRCUIT ACCESS PORT CAPS PER
2015 IMC SECTION 1101.10.
8. NO AIR SIDE ECONOMIZER IS PROVIDED PER 2015 WSEC SECTION C403.3.1 EXCEPTION 1 FOR QUALIFYING SMALL EQUIPMENT UNDER 33 MBH AND AT
LEAST 15% MORE EFFICIENT THAN THE BASELINE CODE.
9. CONFIRM COOLING CAPACITY BASED ON FINAL ELEVATOR EQUIPMENT SELECTED BY OTHERS.
10. NO AIR SIDE ECONOMIZER IS PROVIDED PER 2015 WSEC SECTION C403.4 EXCEPTION 5 FOR EQUIPMENT TO COOL SERVER, ELECTRICAL AND TELECOM
ROOMS AND AT LEAST 15% MORE EFFICIENT THAN THE BASELINE CODE.
ELECTRIC WALL HEATER SCHEDULE
TAG
MANUFACTURER AND MODEL
SIZE (IN)
APPLICATION
SIZE (IN)
W x HT
CAPACITY
(BTU/HR)
CAPACITY
(WATTS)
60 HZ ELECTRICAL DATA
MOUNTING
WEIGHT
(LBS)
NOTES:
VOLTS
PHASE
AMPS
EWH-1
QMARK CWH1101DSF
151 - SPRINKLER RISER RM
10.5"xl2"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
EWH-2
QMARK CWH1101DSF
100 - VESTIBULE
10.5"xl2"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
EWH-3
QMARK CWH1101DSF
102 - VESTIBULE
10.5"xl2"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
EWH-4
QMARK CWH1101DSF
170 - TECH TOILET
10.5"xl2"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
EWH-5
QMARK CWH1101DSF
169 - TECH TOILET
10.5"xl2"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
EWH-6
QMARK CWH1101DSF
168 - TECH LOCKER
10.5"x 12"
1706
500
120
1
4.2
RECESSED
10
1, 2, 3
NOTES:
1. HEATERS MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
2. UNIT TO BE RECESSED MOUNTED IN BACK BOX.
3. THERMOSTAT IS INTEGRAL TO THE UNIT.
4. FRONT COVER TO BE POWDERED COATED WHITE, UNLESS NOTED OTHERWISE.
LOUVERS SCHEDULE
TAG
MANUFACTURER
AND MODEL
LOCATION
SIZE
W x
(IN)
HT
FACE SIZE
SQ FT
FREE AREA
SQ FT
MAX
CFM
FPM
INTAKE OR
EXHAUST
NOTES:
L-1
RUSKIN
ACL
1245
SOUTH EXTERIOR
18 x
18
2.25
1.12
195
175
INTAKE
1, 2,
3,
4
L-2
RUSKIN
ACL
1245
SOUTH EXTERIOR
88 x
36
22.0
11.0
4,160
380
INTAKE
1, 2,
3,
4
L-3
RUSKIN
ACL
1245
SOUTH EXTERIOR
18 x
18
2.25
1.12
330
295
EXHAUST
1, 2,
3,
4
L-4
RUSKIN
ACL
1245
SOUTH EXTERIOR
88 x
36
22.0
11.0
4,160
380
INTAKE
1, 2,
3,
4
L-5
RUSKIN
ACL
1245
WEST EXTERIOR
40.5
x 36
10.1
5.05
1,920
380
INTAKE
1, 2,
3,
4
L-6
RUSKIN
ACL
1245
EAST EXTERIOR
40.5
x 36
10.1
5.05
1,920
380
INTAKE
1, 2,
3,
4
L-7
RUSKIN
ACL
1245
EAST EXTERIOR
40.5
x 36
10.1
5.05
1,920
380
INTAKE
1, 2,
3,
4
L-8
RUSKIN
ACL
1245
EAST EXTERIOR
40.5
x 36
10.1
5.05
1,920
380
INTAKE
1, 2,
3,
4
L-9
RUSKIN
ACL
1245
EAST EXTERIOR
18 x
18
2.25
1.12
330
295
INTAKE
1, 2,
3,
4
NOTES:
1. RUSKIN LOUVERS MAY BE SUBSTITUTED DEPENDING ON AVAILABILITY, OR SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER.
REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
2. PROVIDE WITH BIRDSCREEN
3. PROVIDE WITH LOW LEAK CLASS 1A MOTORIZED DAMPER AT BUILDING ENVELOPE.
4. COLOR TO BE STANDARD MANUFACTURER COLOR SELECTED BY ARCHITECT, CUSTOM COLORS PROVIDED BY OTHERS.
GRILLES. REGISTERS AND DIFFUSERS SCHEDULE
TAG
MANUFACTURER
MODEL
NECK SIZE
(IN)
FACE SIZE
(IN)
MAX AIRFLOW
CFM
THROW
PATTERN
BORDER
TYPE
MOUNTING
NOTES:
LD1
TITUS MCD
12"
48"x4"
475
VERTICAL
T-BAR
DROP IN
1, 2, 3
LD2
TITUS MCD
8"
48%4"
475
VERTICAL
NONE
RECESSED
1, 2, 3
LD3
TITUS MCD
loll
48%4"
475
VERTICAL
NONE
RECESSED
1, 2, 3
CD1
TITUS MCD
6"
24"x24"
100
4 WAY
T-BAR
DROP IN
1, 2, 3
CD2
TITUS MCD
8"
24"x24"
200
4 WAY
T-BAR
DROP IN
1, 2, 3
CD3
TITUS MCD
10"
24"x24"
350
4 WAY
T-BAR
DROP IN
1, 2, 3
CD4
TITUS MCD
6"
12"xl2"
100
4 WAY
HARD LID
SURFACE
1, 2, 3
CD5
TITUS MCD
8"
12"xl2"
200
4 WAY
HARD LID
SURFACE
1, 2, 3
SD1
TITUS S301
-
12%3"
100
HORIZONTAL
NONE
DUCT
1, 2, 3
RG1
TITUS 50F
-
24"x12"
-
-
T-BAR
DROP IN
1, 2, 3, 4
RG2
TITUS 50F
-
48"x24"
-
-
T-BAR
DROP IN
l , 2, 3, 4
EG1
TITUS PAR
6"
12"xl2"
100
-
HARD LID
SURFACE
1, 2, 3
EG2
TITUS PAR
8"
12%12"
200
-
HARD LID
SURFACE
1, 2, 3
EG3
TITUS PAR
10"
1 12%12"
1 350
-
HARD LID
SURFACE
1, 2, 3
NOTES:
1. GRD'S
2. REFER
3. FINISH
4. INSTAL
L
MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
TO FLOOR PLANS FOR DESIGN AIR FLOWS.
COLOR TO BE WHITE UNLESS NOTED OTHERWISE.
WITH SOUND LINED RETURN BOOT TO PLENUM.
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
Q
rn
Q
0
o
co
N
2
O
o
0
W
co
w
m
w 00
N =
i-
rn
d
Qz
�o
N
O Q
WQ°°
W Lo
W E-
pfi
- d'
U
W U)
firLL
yW
zm
ooLL
o
s
0
bm
SIGNED: 8/11 /2017
1:11 AlF/ &71 Cs] k,F.�
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
tOB AlRIBER
SHEET TITLE
MECHANICAL.
EQUIPMENT
SCHEDULES
SHEET NUMBER
15T
7.5T
4T
6T
7.5T
PACKAGED ROOFTOP UNIT SCHEDULE
TAG
MAKE AND MODEL
DESCRIPTION
DESIGN AIRFLOW
UNIT FAN PERFORMANCE
UNIT COOLING CAPACITY
UNIT HEATING CAPACITY - MODULATING GAS
FILTRATION
ELECTRICAL DATA (60 HZ)
SOUND
RATING
(dBA)
WEIGHTS
NOTES
OSA
(CFM)
SA
(CFM)
SA
(CFM)
ESP
(IN WG)
BHP
FLA
TOTAL
(MBH)
SENS
(MBH)
ARI
EER
IEER
INPUT
(MBH)
OUTPUT
(MBH)
EFFICIENCY
%
CONN SIZE
(INCHES)
DISPOSABLE
# / SIZE
VOLTS
PH
MCA
MOCP
BASE UNIT
(LBS)
TOTAL OPERATING
(LBS)
RTU-1
CARRIER 48TCDD 16B2A6-6UOGO
GAS/DX ROOFTOP
538
6,104
6,000
0.50
2.66
4.9
184.78
137.04
10.80
12.4
180
146
81
3/4"
6 / 18x24x2
460
3
36
45
87
1,380
1,733
1, 2, 3, 4, 5, 6, 8, 9, 10
RTU-2
CARRIER 48TCDD08B2A6-6UOGO
GAS/DX ROOFTOP
329
2,390
3,000
0.50
1.65
3.8
90.1
68.90
11.00
12.8
125
103
82
3/4"
4 / 16x2Ox2
460
3
20
25
82
835
1,092
1, 2, 3, 4, 5, 6, 8, 9, 10
RTU-3
CARRIER 48KCDA05A2A6-6UOAO
GAS/DX ROOFTOP
343
1,588
1,600
0.50
0.78
2.5
48.73
37.51
14.0 SEER
-
72
59
82
1 /2"
2 / 16x25x2
460
3
12
15
81
544
719
1, 2, 3, 4, 7, 8, 9, 10
RTU-4
CARRIER 48HCED07B2A6-6UOGO
GAS/DX ROOFTOP
626
2,489
2,400
0.50
1.07
3.8
74.74
56.79
12.00
16.0
125
103
82
3/4"
4 / 16x2Ox2
460
3
16
20
82
590
765
1, 2, 3, 4, 5, 6, 8, 9, 10
RTU-5
CARRIER 48TCDD08B2A6-6UOGO
GAS/DX ROOFTOP
491
3,177
3,000
0.50
1.65
3.8
90.1
68.90
11.00
12.8
125
103
82
3/4"
4 / 16x2Ox2
460
3
20
25
82
835
1,092
1, 2, 3, 4, 5, 6, 8, 9, 10
NOTES:
1. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
2. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT, AND POWERED CONVENIENCE OUTLET, AS APPLICABLE.
3. PROVIDE WITH MANUFACTURER'S 14" TALL ROOF CURB.
4.
PROVIDE
WITH
MANUFACTURER'S ECONOMIZER OPTION (CLASS 1 A ULTRA LOW LEAK AND BAROMETRIC RELIEF).
5.
PROVIDE
WITH
FACTORY MOUNTED RETURN AIR SMOKE DETECTOR.
6.
PROVIDE
WITH
MANUFACTURER'S MEDIUM STATIC FAN OPTION WITH VFD CONTROLLER.
7.
PROVIDE
WITH
MANUFACTURER'S MEDIUM STATIC FAN OPTION.
8.
PROVIDE
WITH
MANUFACTURER'S DRY-BULB ECONOMIZER CONTROL OPTION.
9.
PROVIDE
WITH
WALL -MOUNTED, 7-DAY PROGRAMMABLE THERMOSTAT AT 48" AFF MAX, HONEYWELL VISION PRO 8320 OR EQUAL.
10.
INSTALL
EACH
UNIT WITH NATURAL GAS PRESSURE REGULATOR (INLET PRESSURE = 2 PSIG, OUTLET PRESSURE RANGE ADJ 5" WC MIN - 13" MAX). SEE PLUMBING DESIGN.
EXHAUST FAN SCHEDULE
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
FAN PERFORMANCE ELECTRICAL DATA (60 HZ) 14
FLOW ESP FAN POWER FAN DRIVE MOTOR VOLTS PHASE FLA MOCP SOUND WEIGHT
TAG MANUFACTURER AND MODEL DESCRIPTION APPLICATION SERVING (CFM) (IN WG) (HP OR W) RPM (HP) (dBA) (LBS) NOTES:
EF-1 COOK FAN SQND-EC, #100SQN17DEC CENTRIFUGAL SQUARE INLINE TOILET RM EXHAUST RMS 168, 169, 170, 171 570 0.50 98W 1554 DIRECT 1/4 115 1 5.8 15 53 57 1, 2, 3, 5, 7, 8
EF-2 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM/CAFE EXHAUST RMS 104, 124, 125 370 0.50 73W 1406 DIRECT 1/4 115 1 5.8 15 55 22 1, 2, 3, 4, 5, 7, 8
EF-3 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM/JAN RM EXHAUST RMS 202, 203 100 0.50 31W 1241 DIRECT 1/4 115 1 5.8 15 51 22 1, 2, 3, 4, 5, 7, 8 (o
EF-4 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST TOILET RM EXHAUST RMS 207, 210, 211 370 0.50 73W 1406 DIRECT 1/4 115 1 5.8 15 55 22 1, 2, 3, 4, 5, 7, 8 2 416J
EF-5 COOK FAN ACE-B VFD, #490C11 B ROOFTOP DOWNBLAST SERVICE GARAGE EXHAUST RMS 140, 141, 142, 143, 161 18,750 0.50 3.61 HP 344 BELT 5 460 3 7.6 15 64 437 1, 2, 3, 4, 5, 6, 8, 9, 10 G CA
CA
EF-6 COOK FAN SQND-EC, #100SQN17DEC CENTRIFUGAL SQUARE INLINE ELEC/CO-GEN EXHAUST RM 181 600 0.50 105W 1586 DIRECT 1/4 115 1 5.8 15 52 57 1, 2, 3, 5, 7, 8 4)
EF-7 COOK FAN SQND-EC, #135SQN17DEC CENTRIFUGAL SQUARE INLINE NEW CAR DELIVERY EXHAUST RM 117 1040 0.50 166W 1091 DIRECT 3/4 115 1 13.8 20 51 95 1, 2, 3, 4, 5, 6, 8, 9, 11 I (o
EF-8 COOK FAN S ND -EC 90S N17DEC CENTRIFUGAL SQUARE INLINE COMPRESSOR LOBE RM EXH RM 180 200 0.50 47W 1462 DIRECT 1 6 115 1 4.4 15 50 95 1 2 3 5 7 80 >0 bm
'~
EF-9 COOK FAN ACED -EC, #10OC17DEC ROOFTOP DOWNBLAST MECHANICAL ROOM EXHAUST RM 231 470 0.50 96W 1508 DIRECT 1/4 115 1 5.8 15 56 22 1, 2, 3, 4, 5, 7, 8 0
Wo Z
NOTES:
1.
EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
2.
REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH, EMERGENCY POWER PROVISIONS AND CONVENIENCE OUTLET, AS APPLICABLE.
3.
EXHAUST
FANS
SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. ON/OFF SCHEDULING BY PROGRAMMABLE TIMER. TIME CLOCK WIRED BY ELECTRICIAN/PROVIDED
4.
PROVIDE
WITH
MANUFACTURER'S OPTIONAL 14" ROOF CURB, OUTLET GUARD AND/OR BIRD SCREEN.
5.
PROVIDE
WITH
CLASS 1A LOW LEAK MOTORIZED DAMPER (120V) AT BUILDING ENVELOPE EXHAUST DUCT PENETRATION AS REQUIRED PER 2015 WSEC SECTION C403.2.4.3.
6.
PROVIDE
WITH
MANUFACTURER'S PREMIUM EFFICIENCY VFD RATED MOTOR.
7.
EXHAUST
FAN
MOTORS SHALL BE PROVIDED WITH MANUFACTURER'S OPTIONAL SPEED CONTROLLER.
[:l'/L100]MTO101[i%1�
8. PROVIDE EXHAUST FAN WITH ELECTRONICALLY COMMUTATED (ECM) MOTORS AS REQUIRED BY 2015 WSEC SECTION C403.2.10.3 FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE 1 /12
HORSEPOWER AND LARGER.
9. CONTROL BY UL LISTED TOXIC GAS SENSORS FOR CARBON MONOXIDE AND NITROUS DIOXIDE, LOCATED AS SHOWN ON THE FLOOR PLANS (HONEYWELL E3POINT OR EQUAL). FAN SHALL RUN
CONTINUOUSLY DURING OCCUPIED HOURS AT 20 HZ MINIMUM SPEED OR 0.05 CFM/SF, WHICHEVER IS GREATER. DURING ALL OCCUPIED HOURS, FAN SHALL RUN AT 60 HZ (FULL SPEED) UPON
DETECTION OF GAS LEVELS AT OR ABOVE ACCEPTABLE LEVELS UNTIL LEVELS BELOW THE ACCEPTABLE LIMITS ARE REACHED OR FOR A MINIMUM RUN TIME OF 10 MINUTES. FULL SPEED
ACTIVATION SHALL BE BASED ON A CO LEVELS OF 35 PPM OR HIGHER AND ON NO2 LEVELS AS DICTATED BY THE 8 HOUR OSHA PERMISSIBLE EXPOSURE LIMIT OR HIGHER.
10. SERVICE GARAGE EXHAUST SYSTEM HAS BEEN SIZED IN ACCORDANCE WITH 2O15 IMC SECTION 404.2 AT 0.75 CFM/SF X 24,950 SF = 18,750 CFM MINIMUM EXHAUST AIRFLOW.
11. NEW CAR DELIVERY EXHAUST SYSTEM HAS BEEN SIZED IN ACCORDANCE WITH 2O15 IMC SECTION 404.2 AT 0.75 CFM/SF X 1,386 SF = 1,040 CFM MINIMUM EXHAUST AIRFLOW.
SUPPLY FAN SCHEDULE
TAG
COOK FAN SAND -EC, #100SQN17DEC
MANUFACTURER AND MODEL
DESCRIPTION
APPLICATION
SERVING
FAN PERFORMANCE
ELECTRICAL DATA (60 HZ)
SOUND
(dBA)
WEIGHT
(LBS)
NOTES:
FLOW
(CFM)
ESP
(IN WG)
FAN POWER
(HP OR W)
FAN
RPM
DRIVE
MOTOR
(HP)
VOLTS
PHASE
FLA
MOCP
SF-1
COOK FAN SQND-EC, #90SQN 17DEC
CENTRIFUGAL SQUARE INLINE
DEDICATED OUTSIDE VENT AIR
RMS 144, 145, 147, 148, 150, 151
130
0.375
24W
1221
DIRECT
1 /6
115
1
4.4
15
46
95
1, 2, 3, 4, 5, 6
SF-2
COOK FAN SQND-EC, #100SQN17DEC
CENTRIFUGAL SQUARE INLINE
DEDICATED OUTSIDE VENT AIR
RMS 168, 169, 170, 171
490
0.375
66W
1342
DIRECT
1/4
115
1
5.8
15
48
57
1, 2, 3, 4, 5, 6
NOTES:
1. EQUIPMENT MAY BE SUBSTITUTED FOR EQUAL OR BETTER MANUFACTURER. REFER TO SUBMITTALS FOR FINAL EQUIPMENT SELECTION AND OPTIONS.
1. REFER TO ELECTRICAL DRAWINGS FOR MOTOR STARTER, DISCONNECT SWITCH, EMERGENCY POWER PROVISIONS AND CONVENIENCE OUTLET, AS APPLICABLE.
2. SUPPLY FANS SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. ON/OFF SCHEDULING BY PROGRAMMABLE TIMER. TIME CLOCK WIRED BY ELECTRICIAN/PROVIDED BY MECHANICAL.
LEAK MOTORIZED DAMPER (120V) AT BUILDING ENVELOPE EXHAUST DUCT PENETRATION AS REQUIRED PER 2015 WSEC SECTION C403.2.4.3.
BE PROVIDED WITH MANUFACTURER'S OPTIONAL SPEED CONTROLLER.
LECTRONICALLY COMMUTATED (ECM) MOTORS AS REQUIRED BY 2015 WSEC SECTION C403.2.10.3 FOR FRACTIONAL HORSEPOWER FAN MOTORS THAT ARE 1 /12
K "i� /i► ' iIii►
z.,
n
o
0
W
N
W
m
fn �
N =
00
Q z
=) O
Y
N
O Q
O N
2 =)
M
co
OCn
o
u
W
w �
0_of
V
z>_
w W
fi
`� OLL
00
zm
0
U
fl-
00
SIGNED: 8/11 /2017
I :Z =kyI&A Cs]
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11 /2017
JOB NUMBER
117036
SHEET TITLE
MECHANICAL
EQUIPMENT
SCHEDULES
SHEET NUMBER
r System Sizingr T-
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AM
Air System Name - - -- - -- - - ---- --
- -- - -
-- - - - RTU-1
--- -
Equipment Class .._._._._ ._._._.__._._ ._.._.._._._.__.
PKG ROOF
Air System TYP e---------------- ----
-- ---- SZCAV
Sizing Calculation Information
Calculation Months _______________________
Jan to Dec
Sizing Data --- _ ------- - ----- _ _.. -_
_- _ Calculated
Central Cooling Coil Sizing Data
Total coil load . _ _ -- . ___ ---- -------------------
._ 12.3
Tons
Total coil load
147.3
MBH
Sensible coil load --------
141.8
MBH
Coil CFM at Oct 1300 __ __ __
__ 6104
CFM
Max block CFM ---------------- _.___ _---_--
-__. 6104
CFM
Sum of peak zone CFM _________________________
6104
CFM
Sensible heat ratio ---------------- --------------- __._.
__.___ 0.963
ft2/Ton------- -- ---- - ----- --------
----- -263.2
BTU/(hr•ft2) ......... ....__. ---------------
--------- 45.6
Water flow @ 10.0 OF rise ________________________
N/A
Central Heating Coil Sizing Data
Max coil load - ---------------------
72.7
MBH
Coil CFM at Des Htg _.__________ -...------..--
____.._.....--6104
CFM
Max coil CFM --- -- - - - - -----
---------6104
CFM
Water flow @ 20.0 OF drop - --------------------------
------------------- N/A
Supply Fan Sizing as
Actual max CFM------- --------------------------------------------------------
6104
CFM
Standard CFM
6022
CFM
ActualCFM/ft2max - --
-- 1 89
t2
CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM-----------------------_----------------------------
538
CFM
CFM/ft2 ____ _
0.17
CFM/ft2
Number of zones-------------------------------------1
Floor Area _.. -... --.... ----. -- --- 3232.0 ft2
Location ------------------------ Edmonds, Washington
Zone CFM Sizing __________ Sum of space airflow rates
Space CFM Sizing -------- Individual peak space loads
Load occurs at _.-------------------------------------------------------------
Oct 1300
OA DB / WB-----------
-75.6 / 60.3
OF
Entering DB / WB --....
_.. 76.4 160.5
°F
Leaving DB / WB - ____ _____
_______ 54.6 / 51.6
OF
Coil ADP ---------------- ------
------- 49.2
OF
Bypass Factor
0.198
Resulting RH --- --- ----- ----- -
------ ------------ 39
%
Design supply temp. --------- -- - --
- - - 55.0
OF
Zone T-stat Check _____
____.1 of 1
OK
Max zone temperature deviation _____________________
0.0
OF
Load occurs at----------------------------------
Des Htg
2
BTU/(h)aft-
-- - -- - - - 22.5
Ent. DB / Lvg DB - -
- - - - 67.4 / 78.5
OF
Fan motor BHP -----------------------------------------------------
1.00
BHP
Fan motor kW -
- - - 0.80
kW
Fan static -----------------------------------------------------
0.60
in wg
CFM/ erson---__-------__-------_---------_---------_---- 26.89 CFM/ erson
P P
RTU-1
Hourly Analysis Program v5.01 Page 1 of 15
Air System Sizingr
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AM
Air System Name _______________________________
RTU-4
Equipment Class .______ ____ ____.__.
PKG ROOF
Air System Type ------------ -- ----
-- ---- SZCAV
Sizing Calculation Information
Calculation Months ____ ____ __
__ Jan to Dec
Sizing Data ----- ----------- ------ _ _---__-
_-Calculated
Central Cooling Coil Sizing Data
Total coil load ---- _----------_--------------- ---------------------------------
5.8
Tons
Total coil load
69.3
MBH
Sensible coil load -------- _____
------ 60.3
MBH
Coil CFM at Jun 1500 _____
_ 2489
CFM
Max block CFM ------------ _._._. __.__
__.__. 2489
CFM
Sum of peak zone CFM _________________________
2489
CFM
Sensible heat ratio ____ -___-- -------
------ 0.870
ft2/Ton------- -- --
---------649.8
BTU/(hr•ft2)......... ------------- --- ----------------------------
--18.5
Water flow @ 10.0 OF rise ________________________
N/A
Central Heating Coil Sizing Data
Max coil load ----------------
39.3
MBH
Coil CFM at Des Htg ------ .--------- .--------------- .---------------
_._-. 2489
CFM
Max coil CFM - - - -
- - - - - - - 2489
CFM
Water flow @ 20.0 OF drop ---------------------------------------
N/A
Supply Fan Sizing Data
Actual max CFM------- --------------------------------------------------------
2489
CFM
Standard CFM
2456
CFM
Actual max CFM/ft2------------------------------------------------------------
0.66
CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM------------- -----------------------------------------------
626
CFM
CFM/ft2
0.17
CFM/ft2
Number of zones ----- --- ----- -- - - - - - - -- - - - - -1
Floor Area _.. -... ---... ---...----- ......_ 3751.0 ft2
Location ------------------------ Edmonds, Washington
Zone CFM Sizing _______ Sum of space airflow rates
Space CFM Sizing _- __. Individual peak space loads
Load occurs at----------------------------------------------------------------
Jun 1500
OADB/WB --
-----81.0/63.5
OF
Entering DB / WB _.._... _
77.5 / 63.1
OF
LeavingDB/WB--------------- - ----
- 54.8/53.3
OF
Coil ADP ----------------- ------
- -- - 51.9
OF
Bypass Factor
- - - - - - 0.112
Resulting RH ------ ----- ------
------- ----------- 48
%
Design supply temp. --------- -- - -
- - - - 55.0
OF
Zone T-stat Check .---------------------------------------------------------
.....1 of 1
OK
Max zone temperature deviation _____________________
0.0
OF
Load occurs at _________________________________ Des Htg
BTU/(hr-ft2) . --------- -------------- -------------- -------------------------- - 10.5
Ent. DB / Lvg DB - - 59.7 / 74.5 OF
Fan motor BHP -------------------------------------------
0.41
BHP
Fan motor kW - -
- - 0.32
kW
Fan static ----------------------------------------------------
0.60
in wg
CFM/person_.________.______________-_______-______
8.35
CFM/person
RTU-4
r System Sizingr
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AM
Air System Name - - -- - --- - --- - --- -
--- - -- --- RTU-2
Equipment Class _._._ _.
PKG ROOF
Air System Type ------------- -- ----
-- ---- SZCAV
Sizing Calculation Information
Calculation Months _______________________
Jan to Dec
Sizing Data_. ------- ------------ ___-_------
Calculated
Central Cooling Coil Sizing Data
Total coil load -_.__---------
_-.--_--------- 5.3
Tons
Total coil load
63.6
MBH
Sensible coil load -------- --------
57.1
MBH
Coil CFM at Jun 1400 ___ __
____- 2390
CFM
Max block CFM _.._--- _--_._ _..__.
____-- 2390
CFM
Sum of peak zone CFM _________________________
2390
CFM
Sensible heat ratio -_-- ___-- _.__._.
-------------.._-..0.897
ft2/Ton------- --- ---- - ----- --------
----- -594.9
BTU/(hr•ft2) - -------- - - --------------------------------------------
20.2
Water flow @ 10.0 OF rise ________________________
N/A
Central Heating Coil Sizing Data
Max coil load - - - - - -----------
--------- 27.7
MBH
Coil CFM at Des ____________ Htg .___._.-...-_---------
__.. 2390
CFM
Max coil CFM - - -
- - - - - - - - 2390
CFM
Water flow @ 20.0 OF drop -------------------------------------
N/A
Supply Fan Sizing Data
Actual max CFM----------------------------------------------
2390
CFM
Standard CFM
2358
CFM
Actual max CFM/ft2------------------------------------------------------------
0.76
CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM-----------------------_----------------------------
329
CFM
CFM/ft2
0.10
CFM/ft2
Number of zones - - -- - -- -- - -- - - -- - -- - -- --- -- --- ----- ---1
Floor Area .. _ .... ----- _ _. _-----------3154.0 ft2
Location _______________________Edmonds, Washington
Zone CFM Sizing _____ __ Sum of space airflow rates
Space CFM Sizing _____. Individual peak space loads
Load occurs at -. __--_- __.__----------
_._. ___---Jun 1400
OADB/WB
80.5/63.4
OF
Entering DB / WB ----
77.0 / 62.8
OF
Leaving DB / WB ____ ___
__ ___54.6 / 53.4
OF
Coil ADP ------ _--- -
---------- 52.3
OF
Bypass Factor -
0.092
ResultingRH _. -- .--------------- .--------- ._.-.-.------- ____.-----------
--_.--------47
%
Design supply temp. - - - - - - - -
- - - - - 55.0
OF
Zone T-stat Check ---------------------- ..--- _.._
_ _--- ._-1 of 1
OK
Max zone temperature deviation _____________________
0.0
OF
Load occurs at --- ------ ---------- ------ ---------- ------ ---------- ------ -- ------ Des Htg
BTU/ hrft2 - - - - - -.__ - __.. 8.8
Ent. DB / Lvg DB 65.2 / 76.1 OF
Fan motor BHP ------------------------------------------
0.39
BHP
Fan motor kW - - -
- - 0.31
kW
Fanstatic-----------------------------------------------------------------------------------
0.60
in wg
CFM/person------_------_--_------_--_------_--_------_--_-__
11.76
CFM/person
Hourly Analysis Program v5.01 Page 4 of 15
Air System Sizing
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AM
Air System Name _______________________________
RTU-5
Equipment Class _..__.. _-___.___
PKG ROOF
Air System Type ----------------------
---- SZCAV
Sizing Calculation Information
Calculation Months __ ____ ____
__ Jan to Dec
Sizing Data _.------- ------ ____.. -__-
_-Calculated
Central Cooling Coil Sizing Data
Total coil load _--- ------------- _--------------- ---------------------------------
6.5
Tons
Total coil load
77.5
MBH
Sensible coil load -------- __..__.. _.______
------ 73.4
MBH
Coil CFM at Jul 1600 ___________________________
3177
CFM
Max block CFM -------------------------------------------------------------
3177
CFM
Sum of peak zone CFM _________________________
3177
CFM
Sensible heat ratio -_-- ___-- _.__._.
-----------.__._.0.948
ft2/Ton------- -- ------
----- -671.0
BTU/(hr•ft2)------------------------- ---------------------------------------------
_ 17.9
Water flow @ 10.0 OF rise ________________________
N/A
Central Heating Coil Sizing Data
Max coil load - ----------------
35.5
MBH
Coil CFM at Des Htg ------ .--------- .--------------- .---------------
_._-. 3177
CFM
Max coil CFM - --
- ----- --3177
CFM
Water flow @ 20.0 OF drop ---------------------------------------
N/A
Supply Fan Sizing Data
Actual max CFM--------.---------------------------------------
3177
CFM
Standard CFM
3134
CFM
Actual max CFM/ft2------------------------------------------------------------
0.73
CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM------------- -----------------------------------------------
491
CFM
CFM/ft2
0.11
CFM/ft2
Number of zones __ ___ _ ___ 1
Floor Area - -_ .... _ _ ----------- 4332.0 ft2
Location _______________________Edmonds, Washington
Zone CFM Sizing ___ ___ Sum of space airflow rates
Space CFM Sizing ...... Individual peak space loads
Load occurs at ---------------------------------------------------------.
Jul 1600
OADB/WB
81.5/63.4
OF
Entering DB / WB ---- __-
--------------- 77.1 / 62.7
°F
LeavingDB/WB- -------------
-------55.4/54.2
OF
Coil ADP -- ---- _------------------
------- 53.2
OF
Bypass Factor
0.092
Resulting RH _. -- .--------------- . ---_-----------
------------47
%
Design supply temp.
- - - - - 55.0
OF
Zone T-stat Check --------------------- ------------
_._ --------------1 of 1
OK
Max zone temperature deviation _____________________
0.0
OF
r System Sizingfor T-
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AM
Air System Name - - -- - -- - ---- --- - --- -
--- - -- --- RTU-3
Equipment Class _.
PKG ROOF
Air System Type ---------------- ----
-- ---- SZCAV
Sizing Calculation Information
Calculation Months _______________________
Jan to Dec
Sizing Data -------- --------------- -._-_Calculated
Central Cooling Coil Sizing Data
Total coil load ------ -_- - ---- ___ -----------
_--- --.___ 3.5
Tons
Total coil load
42.5
MBH
Sensible coil load --- -------- ------
37.4
MBH
Coil CFM at Jun 1600 __ _
__ 1588
CFM
Max block CFM ___. _____. _._._.
_..___-- 1588
CFM
Sum of peak zone CFM _________________________
1588
CFM
Sensible heat ratio ---------------- ---------------
___-- 0.880
ft2/Ton------- -- ---- - ----- --------------
-737.5
BTU/(hr•ft2) __ __. -.__.
16.3
Water flow @ 10.0 OF rise ________________________
N/A
Central Heating Coil Sizing Data
Max coil load - - - - ---------------------
20.6
MBH
Coil CFM at Des Htg _.__________ -...------..--
____.._.....--1588
CFM
Max coil CFM - -
- 1588
CFM
Water flow @ 20.0 OF drop ------------------------------------
N/A
Supply Fan Sizing as
Actual max CFM----------------------------------------------1588
CFM
Standard CFM
1567
CFM
Actual max CFM/ft2------------------------------------------------------------
0.61
CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM-----------------------_----------------------------
343
CFM
CFM/ft2 . . --
- - 0.13
CFM/ft2
Number of zones--------------------------------------1
Floor Area ._ _ _ -- . ----.. ----.. ------------ -- 2615.0 ft2
Location ------------------------ Edmonds, Washington
Zone CFM Sizing __________ Sum of space airflow rates
Space CFM Sizing _. -- --- -------- Individual peak space loads
Load occurs at ------------------
-.-.-.-Jun 1600
OADB/WB
----80.5/63.4
OF
Entering DB / WB . -..-.- _....
.......... 77.2 / 62.6
OF
Leaving DB / WB ____ __ ____
_____55.1 / 53.1
OF
Coil ADP __._-.
OF
Bypass Factor
- - - - - 0.146
Resulting RH - ---_-- ----_ ---_--.
-------- ------- 46
%
Design supply temp. --------- -- - --
- - - 55.0
OF
Zone T-stat Check .
-______-1 of 1
OK
Max zone temperature deviation _____----
_------- _--- 0.0
OF
Load occurs at
BTU/ hrft2.._..._...
Ent. DB / Lvg DB
Des Htg
---------- 7.9
61.4 / 73.6 OF
Fan motor BHP -------------------------------------------------------
0.26
BHP
Fan motor kW - -
- 0.21
kW
Fan static ----------------------------------------------------
0.60
in wg
CFM/person----------- ------------ ---- ------------ ----
---- -------- ---- ------------ --- 13.72
CFM/person
RTU-3
Hourly Analysis Program v5.01 Page 7 of 15
Design Weather r
117036 Magic Toyota Edmonds 08/09/2017
Comfort Systems USA - Northwest 01:30PM
Design Parameters:
City Name
Edmonds
Location
Washington
Latitude_------------------------ .-------- --------- -
------ - - -------- _.-------- _ __ 47.8
Deg.
Longitude
122.3
Deg.
Elevation
377.0
ft
Summer Design Dry -Bulb
82.0
OF
Summer Coincident Wet -Bulb
63.5
OF
Summer Daily Range
16.0
OF
Winter Design Dry -Bulb
24.0
OF
Winter Design Wet -Bulb
20.0
OF
Atmospheric Clearness Number
1.05
Average Ground Reflectance
0.20
Soil Conductivity
0.800
BTU/(hr-ft•°F)
Local Time Zone (GMT +/- N hours)
8.0
hours
Consider Daylight Savings Time
No
Simulation Weather Data
N/A
Current Data is
User Modified
Design Cooling Months
January to December
DESIGN NOTES
1. HEATING AND COOLING LOAD SYSTEMS HAVE
BEEN SIZED IN ACCORDANCE WITH STANDARD
ENGINEERING PRACTICES ANS AS REQUIRED BY
THE 2015 WSEC SECTIONS C403.2.1 AND
C403.2.2 FOR CLIMATE ZONE 4C. OUTPUT
CAPACITIES OF ALL EQUIPMENT IS NOTED IN
THE EQUIPMENT SCHEDULES.
2. HVAC LOAD SUMMARY AND VENTILATION
CALCULATIONS SHOWN ON M004 AND M005.
3. CALCULATIONS USE THE FOLLOWING BUILDING
DESIGN TEMPERATURES AND THERMAL
INSULATION VALUES IN ACCORDANCE WITH
2015 WSEC AND THE ASHRAE RECOMMENDED
OUTDOOR DESIGN TEMPERATURES FOR
WASHINGTON STATE UNLESS NOTED
OTHERWISE:
SITE COORD:
LAT
N47.80
LON
W122.30
WEATHER DATA:
EDMONDS, WA (WSEC)
ELEVATION:
377
FT
SUMMER DESIGN OSA:
82°F
DB/63.5°F WB
WINTER DESIGN OSA:
24°F
DB
INDOOR DESIGN:
72°F
DB H/75°F DB C
SA HEATING:
95°F
MAX
SA COOLING:
58°F
MIN
ROOF U-VALUE:
0.026
WALLS U-VALUE:
0.047 & 0.064
DOORS U-VALUE:
0.200 & 0.580 GL
GLAZING
U-VALUE:
0.290
GLAZING
SHGC:
0.226
2. INTERIOR LIGHTING POWER ALLOWANCES PER
2015 WSEC TABLE C405.4.2(1) 0.66 TO 1.0
WATTS/SQ FT WERE USED IN THE HVAC
SYSTEM SIZING CALCULATIONS, UNLESS NOTED
OTHERWISE.
3. INTERIOR EQUIPMENT PLUG LOAD ALLOWANCES
PER 2015 WSEC TABLE B102 OF 1.0 TO 2.0
WATTS/SQ FT WERE USED IN THE HVAC
SYSTEM SIZING CALCULATIONS, UNLESS NOTED
OTHERWISE.
4. OUTSIDE AIR MECHANICAL VENTILATION BASED
ON 2015 IMC CHAPTER 4 W/ WA
AMENDMENTS. WHERE KNOWN, SPECIFIC
OCCUPANCIES UTILIZED THE ARCHITECTS
SEATING PLAN AND HEAD COUNT, EXCEPTION
TO IMC SECTION 403.2, OR ASHRAE 62.1,
LATEST EDITION.
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST') AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
TiC
N
00
Qo
Q
0
o z
0
O
CO
Irl-
N Li
LL1
O
o
�
LIJ
�
N
w
m
Cn CD
co
N =
I_i
C7,
d O
z
�
0
OI-
N
O Q
(D N
U_ W
��
co
0�
wQ co
w ;
ILL!
pvn
W
a�
w
U 1-
0
00 00
Qo
�
C 4
o
�IL
Srl-
U
�
ow
co
SIGNED: 8/11 /2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
Load occurs at --__---_--_--__---_-_--_____--_--_____--_-
Des Htg
BTU/(hr-ft2)
8.2
Ent. DB /Lvg DB __________________________ ______________________________
64.3 / 74.8
OF
HVAC LOAD SUMMARY
Fan motor BHP --------------------------------------
0.52
BHP
Fan motor kW - - -
- - 0.41
kW
Fanstatic-----------------------------------------------------------------------------------
0.60
in wg
DESIGNED
CSUSA NW / EE
CFM/person-__-__-______-__-__-___-_-_-___-_-_-___-__-__
17.52
CFM/person
RTU -5
' CHECKED '
CSUSA NW / SAL
08/11/2017
1 •,
SHEET TITLE
MECHANICAL
HVAC LOAD
CALCULATIONS
Ed01:4Ai:lI1611:40
11�
Hourly Analysis Program v5.01 Page 10 of 15
Hourly Analysis Program v5.01 Page 13 of 15
OUTSIDE AIR MECHANICAL VENTILATION CALCULATIONS
Ventilation i i r
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AN
1. Summary
Ventilation Sizing Method ____-
Design Ventilation Airflow Rate
Sum of Space OA Airflows
------- ------ -- --------- . 538 CFM
Zone Name / Space Name
Mult.
Floor
Area
ft2
Maximum
Occupants
Maximum
Supply Air
CFM
Required
Outdoor Air
(CFM/person
Required
Outdoor Air
CFM/ft2
Required
Outdoor Air
CFM
Required
> Outdoor Air
% of supply)
Uncorrected
Outdoor Air
(CFM)
Zone 1
101 - Display/Sales (1)
1
3232.0
20.0
6104.3
7.50
0.12
0.0
0.0
537.8
Totals (incl. Space Multipliers)
6104.3
537.8s
Ventilation i i for RTU-2
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AN
1. Summary
Ventilation Sizing Method ------------------------------------
Design Ventilation Airflow Rate
Sum of Space OA Airflows
------------------- 329 CFM
Zone Name / Space Name
Mult.
Floor
Area
ft2
>
Maximum
Occupants
Maximum
Supply Air
CFM
Required
Outdoor Air
CFM/person
Required
Outdoor Air
CFM/ft2 ;
Required
Outdoor Air
CFM)
Required
Outdoor Air
` % of suppl
'Uncorrected
Outdoor Air
CFM
Zone 1
133 - Service Work
1
135.0
1.0
81.9
5.00
0.06
0.0
0.0
13.1
103, 104, 131 -Multiple
1
2842.0
24.0
2190.4
5.00
0.06
0.0
0.0
290.5
106 - New Car Mgr
1
177.0
3.0
117.6
5.00
0.06
0.0
0.0
25.6
Totals (incl. Space Multipliers)
2389.9
1
329.2
Ventilation i
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AN
1. Summary
Ventilation Sizing Method ._...__._.
Design Ventilation Airflow Rate
Sum of Space OA Airflows
- -- - - - 343 CFM
Zone Name / Space Name
Mult.
Floor
Area
ft2
Maximum
Occupants
Maximum
Supply Air
CFM
Required
Outdoor Air
CFM/person
Required
Outdoor Air
CFM/W)
Required
Outdoor Air
CFM
Required
Outdoor Air
% of supply)
Uncorrected
Outdoor Air
(CFM)
Zone 1
112 - F&I
1
125.0
3.0
124.7
5.00
0.06
0.0
0.0
22.5
113 - F&I
1
125.0
3.0
124.7
5.00
0.06
0.0
0.0
22.5
114 - F&I
1
125.0
3.0
124.7
5.00
0.06
0.0
0.0
22.5
115 - F&I
1
125.0
3.0
124.7
5.00
0.06
0.0
0.0
22.5
116 - F&I
1
125.0
3.0
124.7
5.00
0.06
0.0
0.0
22.5
118 - Corridor
1
164.0
0.0
19.1
0.00
0.06
0.0
0.0
9.8
119 - Corridor
1
276.0
0.0
34.3
0.00
0.06
0.0
0.0
16.6
122 - Parts
1
1018.0
2.0
526.1
5.00
0.12
0.0
0.0
132.2
110 - F&I MGR
1
158.0
3.0
109.1
5.00
0.06
0.0
0.0
24.5
126, 127, 128 - Multiple
1
284.0
4.0
218.6
5.00
0.06
0.0
0.0
37.0
129 - Parts Mgr
1
90.0
1.0
57.5
5.00
0.06
0.0
0.0
10.4
Totals (Incl. Space Multipliers)
1588.1
343.0
Ventilation i i
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AN
1. Summary
Ventilation Sizing Method --------
Design Ventilation Airflow Rate ._
Sum of Space OA Airflows
_..------- __---------- - ------------ 626 CFM
Zone Name / Space Name
Mult.
Floor
Area
ft2
Maximum
Occupants
Maximum
;Supply Air
CFM
Required
Outdoor Air
(CFM/person
Required
Outdoor Air
CFM/ft2
Required
Outdoor Air
CFM
Required
Outdoor Air
% of supply)
Uncorrected
Outdoor Air
(CFM)
Zone 1
200 - File Storage
1
388.0
1.0
77.3
5.00
0.06
0.0
0.0
28.3
201 - Dealer
1
404.0
2.0
354.0
5.00
0.06
0.0
0.0
34.2
204 - Gen Mgr
1
410.0
2.0
378.7
5.00
0.06
0.0
0.0
34.6
205 - Waiting
1
691.0
20.0
320.2
5.00
0.06
0.0
0.0
141.5
208 - Conf/Training
1
773.0
44.0
1009.2
5.00
0.06
0.0
0.0
266.4
209 - Corridor
1
457.0
0.0
72.2
0.00
0.06
0.0
0.0
27.4
224 - Locker Rm
1
242.0
4.0
193.3
0.00
0.25
0.0
0.0
60.5
226 - Secure Files
1
158.0
1.0
36.6
5.00
0.06
0.0
0.0
14.5
227 - File Storage
1
228.0
1.0
47.9
5.00
0.06
0.0
0.0
18.7
Totals (incl. Space Multipliers)
2489.4
626.0
Ventilation i 1 r
Project Name: 117036 Magic Toyota Edmonds 08/11/2017
Prepared by: Comfort Systems USA - Northwest 06:21AN
1. Summary
Ventilation Sizing Method
Design Ventilation Airflow Rate
Sum of Space OA Airflows
491 CFM
Zone Name / Space Name
Mult.
Floor
Area
(ft2)
;
Maximum
'; Occupants
Maximum
Supply Air
(CFM)
Required
Outdoor Air
(CFM/person)
Required
Outdoor Air
(CFM/ft2)
Required
Outdoor Air
(CFM}
Required
Outdoor Air
(% of supply)
Uncorrected'
Outdoor Air
(CFM)'
Zone 1
213 - Generall Office
1
1122.0
10.0
825.2
5.00
0.06
0.0
0.0
117.3
214 - HR
1
181.0
2.0
184.0
5.00
0.06
0.0
0.0
20.9
215 - Office Mgr
1
175.0
2.0
221.7
5.00
0.06
0.0
0.0
20.5
216 - Corridor
1
181.0
0.0
29A
0.00
0.06
0.0
0.0
10.9
217 - IT Office
1
65.0
1.0
75.3
5.00
0.06
0.0
0.0
8.9
219 - Internet Sales
1
395.0
4.0
318.9
5.00
0.06
0.0
0.0
43.7
220 - Corridor
1
335.0
0.0
55.9
0.00
0.06
0.0
0.0
20.1
221 - Service Call Cntr
1
367.0
4.0
346.0
5.00
0.06
0.0
0.0
42.0
222 - Employee Lounge
1
316.0
4.0
440.3
5.00
0.12
0.0
0.0
57.9
225 - Parts
1
1195.0
1.0
680.6
5.00
0.12
0.0
0.0
148.4
Totals (incl. Space Multipliers)
3177.3
490.6
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
Mechanical Summary MECH-SUM
2015 Washington State Energy Code Corr oliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Project Information
Project Title: Magic Toyota Edmonds WA
Date 8/11/2017
Applicant Information. Provide contact information for individual who can respond to
For Building Dept. Use
inquiries about compliance form information provided.
Company Name: Comfort Systems USA NW
Company Address: 18702 North Creek Parkway Edmonds WA 98011
Applicant Name: Sonny Winter, Project Manager
Applicant Phone: (425) 883-9224
Project Description
[2]New Building Building Addition Tenant Improvement QSystem Retrofit E:[No System Changes
Briefly describe mechanical systems in
New mechanical HVAC systems to support construction of a 2 story structure consisting of a sales floor, generatl
the text box provided
office space, a parts deparment, service area and parking deck. Mechanical work includes the following: heating,
E Total Bldg Performance (TBP)
ventilation and air conditioning systems to serve the auto showroom and office spaces, exhaust systems for
restrooms breakrooms and service area ductless mini -split A/C units for small server and equipment rooms in
p
This path includes all mandatory
slab hot water (hydronic) radiant heating system in the service and new car delivery areas,. snow melt, all
provisions per C401.2 Option 2.
p
MECH-SUM, MECH-CHK; and C407
associated ductwork piping, rifles registers diffusers accessories and astand-alone controiss stems for a
' p p g' g g y
Energy Analysis forms required,
complete installation and equipment start-up, air balance and programming and owner triaining, O&M manuals.
Load calculation summary MECH-LOAD-CALC Form
Design Load Calculations
Provide design load calculations for all mechanical systems and equipment serving the building heating, cooling or
ventilating needs. If a load calculation summary is provided with the permit documents that includes all applicable
compliance information then the MECH-LOAD-CALC form is not required.
0. Mechanical Plans L MECH-EQ Forms (TBD)
Mechanical Schedules
Indicate location of equipment compliance information. if provided on plans then MECH-EQ forms are not required,
however, include on plans all applicable compliance information listed in MECH-EQ tables.
DOAS is required per C403.6 effective July 1, 2017 (office, retail, education, library and fire station occupancies)
All occupied, conditioned areas shall be served by a DOAS that delivers required ventilation air in a manner that does
not require space conditioning fan operation. Space conditioning fans cycled off when no heating or cooling is required.
Dedicated Outdoor Air
Ventilation provided via natural ventilation per 2015 IMC in lieu of DOAS (C403.6, Exception 1)
System Requirements and
Ventilation and space conditioning provided by a HEVAV system per C403.7 in lieu of DOAS (C403.6, Exception
)
High Efficiency VAV
DOAS included in project, although not required (occupancy not office, retail, education, library or fire station)
Alternate
DOAS related allowances included in project:
Prescriptive vertical fenestration maximum area allowance increased to 40% per C402.4,1.4 with 100% of
conditioned floor area in building served by DOAS.
E] Exception to air economizer per C403.3 Exception 1, include MECH-ECONO form.
Project includes HVAC air distribution systems that provide heating and/or cooling
If yes, provide a MECH-FANSYS -SUM form.
Fan Power
For one or more systems, the total fan motor nameplate hp of all fans in HVAC system exceeds Shp.
Ifyes, provide a separate MECH-FANSYS form for each HVAC system exceeding the 5 horsepower threshold.
Refer to Section C403.2.11 and MECH-FANSYS-DOC for requirements and exceptions.
Hydronic chilled water -] Water -loop heat pump No hydronic systems
HVAC Hydronic Systems
tt-----tt
Hydronic heating water L ,i Geothermal
[ C406.2 More efficient HVAC equipment and fan systems
Requires 90% of heating and cooling capacity to be equipment listed in tables C403.2.3(1)-(g) or air -to -wafer heat
pumps and heat recovery chillers. All equipment listed in tables C403.2.3(1)-(7) must be 15% more efficient than
minimum requirements. All stand alone supply, return, and exhaust fans over9hp must have FEQ>_ 71 and must be
C406 Additional Efficiency
selected within 10% of maximum total or static pressure.
C406.6 Dedicated outdoor air system (DOHS)
Options - Mechanical
Requires 90% of conditioned floor area to be served by a DOAS per C403.6 that delivers required ventilation air in a
manner that does not require space conditioning fan operation.
C406.7 Reduced energy in service water heating
Requires 90% of floor area be in occupancy types listed in C406.7:1 and that 60% of annual hot water energy use be
provided by heat pump, waste heat recovery or solar water -heating systems.
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1
Mechanical Summary, ••
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Equipment Type (s)
JZ Hot water heating tank(s) Instantaneous 0 No service water systems
Service Water Heating
Dedicated boiler Heat exchange from space heat boiler or
Systems
central hot water/steam
Distribution Type (s)
121 Circulation System On -demand
Commissioning
Commissioning is required for:
I.....it, Mechanical systems per C408.2 Service water heating systems per C408.4
If required, commissioning shall be performed for all applicable systems regardless of individual equipment capacity.
Exceptions to commissioning requirements:
Total output capacity of all mechanical space conditioning systems in the building do not exceed 240,000 Btu/h
cooling or 300,000 Btu/h heating. Mechanical systems commissioning not required.
Capacity of largest service water heating system in building does not exceed 200,000 Btu/h. Service water heating
systems commissioning not required.
Low Energy and Semi -Heated Spaces (Note 6 and 7)
Peak Space
Heating
Cooling
Conditioning
Space
Area Served,
Capacity, Btu/h
Capacity, Btu/h
Capacity,
Compliance
Type
Location in Plan(s)
Space(s) Served
square feet
(Note 4)
(Note 5)
Btu/6-sf
Check
Notes
Semi-
DOES NOT
Smallest
heated
Sheet M100
151 - Sprinkler Riser Room
110
1,706
0
15.51
COMPLY,
Manufactured
Unit Selected
Semi-
(TOES NOT
Smallest
heated
Sheet M100
100 - Entry Vestibule
60
1,706
0
28,43
COMPLY
Manufactured
Unit Selected
Semi-
DOES NOT
Smallest
heated
Sheet M101
102 - Entry Vestibule
60
1,706
0
28.43
COMPLY
Manufactured
Unit Selected
Note 4 - Provide total installed heating output capacity of systems serving Low Energy or Semi -Heated space(s) in btuh.
Note 5 - Provide total installed cooling capacity of system serving Low Energy space(s) in Btu/h. Not allowed for semi -heated spaces. Enter 0 if no cooling.
Note 6 - Refer to Section C402.1.1 Low Energy Building. lntalled peak space conditioning capacity, heating or cooling, may not exceed 3.4 Btu/h*sf.
Note 7 - Refer to Section C402.1.1.1 and Semi -Heated Space definition in Chapter 2. Total heating output capacity may not exceed 8 Btu/h*sf. Only systems without
electric resistance heating and no cooling are eligible for the wall insulation exception under semi -heated.
2015 WSEC MECH FORM,
N�9RP0RHI1
1. HEATING AND COOLING LOAD SYSTEMS HAVE
BEEN SIZED IN ACCORDANCE WITH STANDARD
ENGINEERING PRACTICES ANS AS REQUIRED BY
THE 2015 WSEC SECTIONS C403.2.1 AND
C403.2.2 FOR CLIMATE ZONE 4C. OUTPUT
CAPACITIES OF ALL EQUIPMENT IS NOTED IN
THE EQUIPMENT SCHEDULES.
#IJIMA 0 11 IRTA I
30
3. CALCULATIONS USE THE FOLLOWING BUILDING
DESIGN TEMPERATURES AND THERMAL
INSULATION VALUES IN ACCORDANCE WITH
2015 WSEC AND THE ASHRAE RECOMMENDED
OUTDOOR DESIGN TEMPERATURES FOR
WASHINGTON STATE, UNLESS NOTED
OTHERWISE:
SITE COORD: LAT N47.8*
LON W122.30
WEATHER DATA: EDMONDS, WA (WSEC)
ELEVATION: 377 FT
SUMMER
DESIGN OSA:827
/i • i
WINTER
1
/i
SA HEATING: 95°F MAX
SA COOLING: 58°F MIN
ROOF U-VALUE:
0.026
WALLS U-VALUE:
0.047 & 0.064
DOORS U-VALUE:
0.200 & 0.580 GL
GLAZING
U-VALUE:
0.290
GLAZING
SHGC:
0.226
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
2. INTERIOR LIGHTING POWER ALLOWANCES PER
2015 WSEC TABLE C405.4.2(1) 0.66 TO 1.0
WATTS/SQ FT WERE USED IN THE HVAC
SYSTEM SIZING CALCULATIONS, UNLESS NOTED L�
OTHERWISE. r
3. INTERIOR EQUIPMENT PLUG LOAD ALLOWANCES 0
PER 2015 WSEC TABLE 6102 OF 1.0 TO 2.0 LL W -4)Cn
WATTS/SQ FT WERE USED IN THE HVAC L
SYSTEM SIZING CALCULATIONS, UNLESS NOTED r
OTHERWISE. m i
4. OUTSIDE AIR MECHANICAL VENTILATION BASED
ON 2015 IMC CHAPTER 4 W/ WA
AMENDMENTS. WHERE KNOWN, SPECIFIC
OCCUPANCIES UTILIZED THE ARCHITECTS
SEATING PLAN AND HEAD COUNT, EXCEPTION
TO IMC SECTION 403.2, OR ASHRAE 62.1,
LATEST EDITION.
0
UJ
H
cf)CD
00
>-
Q O
Y N
Q z ,
= 0000
00
W � tf)
W N
� d-
U �
O O
zm
N
0
I`
00
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
tOB A11:1BER
1 •
SHEET TITLE
MECHANICAL
HVAC LOAD
CALCULATIONS
SHEET NUMBER
c L i' ' J
COPYRIGHT NOTICE
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 3 of 7 THIS LAYOUT/DESIGN IS A
Mechanical Permit Plans Checklist MECH-CHK Mechanical Permit Plans Checklist MECH-CHK Mechanical Permit Plans Checklist MECH-CHK COPYRIGHTED WORK OWNED BY
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST') AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
FM co
O
M
Q
>111111111111111
Q
o TT_
!!1�
N V `^
v )
Z 0
O
N n
Q W
O (�
W4�, , ll—
W C0
UJ
I on �o Co 3:
00 C\1 �
O
Q O � 0
H T O Q
" N � �
O
INN (O �e Cf) � O LU
W Q o0
.. W
W �j W 1--
and -J d- W Cn
0 N W �ry
0
0 ~ ¢ O
3 O LY] O
2(0CD 0
co
0> o �
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 4 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 5 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 6 of 7 U (0 Z
Mechanical ._ rmit . ._ rmit . ._
rmit Plans Checklist MECH-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
� A. L.�
WAS
F T
�tti� � �yy
` z
�11 38898 ST� ski
�SSj�NALGZ
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
JOB NUMBER
2015 WSEC MECH FORM
117036
SHEET TITLE
ENERGY CODE
COMPLIANCE
FORMS
SHEET NUMBER
M 006
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 -Page 1 of 7
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
Equipment -Sizing, Performance and Type
Identif e ui ment to be used in manufacturin industrial or commercial rocesses that do not
Y q p g, p
NA
C403.1
Exempt process equipment
provide space conditioning; identify provisions applicable to this equipment per C403.1
exception
Provide load calculations performed per ASHRAE Std 183 or equivalent, using design
M004,
Yes
C403.2.1
Load calculations
parameters per C302 and Appendix C; include load adjustments to account for energy
M005
recove
Ma is To ota Edmonds WA 8 li 2017 Project Title: g y Date
The followin information is necessa to check a ermit a lication for tom liance with the mechanical s stems and e ui ment re uirements of the
9 ry p pp p Y q p q
Washin ton State Ener Code Commercial Provisions.
9 9Y
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
For su I and return ductwork located in unconditioned s ace or outdoors indicate R-value
PPY P
of insulation on ductwork on plans; identify climate zone; note exceptions taken
M001
For supply ductwork located in conditioned space, identify if design supply temperature is <
C403.2.8.1
Yes
C403.2:8.2
Duct insulation
55°F or > 105°F and indicate R-value of insulation on this ductwork on plans;. note exception
taken
M001
For OSA ductwork, shafts and plenums, indicate R-value of insulation on these elements on
plans per Table C402.1.3 for steel -framed walls; note. exception taken
M001
Piping Systems
Yes
C403.2.9
Pi in insulation
P g
Indicate design temperature range of fluid conveyed in piping and thickness of insulation (in
inches) on hydronic piping plans; or exception taken
M001
Yes
C403.2.9.1
Piping insulation exposed to
Indicate method of protection of pipe insulation from damage /degradation on hydronic piping
weather
plans
M001
Economizers
Identify in equipment schedules on plans or in MECH-EO forms all cooling systems requiring
M002,
air economizer controls
M003
Yes
C403.3
Air economizer required
Provide MECH-ECONO form indicating systems utilizing air economizer exceptions, including
those with water -side economizer in lieu of air economizer; indicate on plans eligible
M002,
exceptions) taken and measures to comply with exceptions)
M003
Yes
C403.3.1
Integrated economizer
Indicate air and water -side economizers are configured for partial cooling operation even
M001,
M002,
operation -air and water
where additional mechanical cooling is required to meet the load
M003
Yes
C403.3.2
Economizer heating system
Verify control method of HVAC systems with economizers does not increase building heating
M001,
M002,
impact - airand water
energy usage during Normal operation
M003
Yes
C403.3.3.1
Air economizer capacity
Indicate modulating OSA and return air dampers are configured to provide up to 100% OSA
M001,
M002,
for cooling
M003
Verify mechanical cooling controls are interlocked with air economizer controls so the outside
M001,
air damper remains in 100% openposition when mechanical cooling is also required to meet
M002,
C403.3.1
the cooling load, until the leaving air temperature is < 45°F
M003
Yes
C403.3.3.2
Integrated air economizer
M001,
For systems with cooling capacity >_ 65,000 Btu/h, verify that control of economizer dampers is
M002,
not based only on mixed air temperature; or exception taken
M003
Yes
C403.3.3.3
Air economizer high limit
controls
Indicate high limit shut-off control method and required high limit per Table C403.3.3.3
M003
For eligible systems where water -side economizer may be provided in lieu of air economizer,
NA
C403.3.4.1
Water economizer capacity
indicate system is capable of 100%design cooling capacity at 50°F db / 45°F wb OSA
temperatures
NA
C403.3.4.2
Water economizer
Indicate pressure drop across precooling coils and heat exchangers in water economizer
maximum pressure. drop
system do not exceed pressure drop limit
Yes
C403.3.1
DX air handling equipment
For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, refer to HVAC
M001,
M002,
control
System Controls for requirements
M003
DX equipment economizer
For DX air handlers with economizer and cooling capacity ? 54,000 Btu/h, provide a fault
M001,
Yes
C403.2.4.7
fault detection and
detection and diagnostics (FDD) system to monitor economizer system operation and report
M002,
diagnostics.
faults
M003
Systems Requiring Energy
Recovery
For systems with design OSA > 5,000 cfm, or design supply air cfm and % OSA exceeding the
values in Tables C403:5.1(1) or (2), indicate exhaust air ER method; or exception taken with
su ortin calculations
Pp g
Ener recover ER -
gY Y( )
For rooms served by multiple systems with aggregate design OSA > 5,000 cfm, or aggregate
NA
C403.5.1
ventilation /exhaust.
systems
design supply air cfm and % OSA exceeding the values in Tables C403.5.1(1) or (2), indicate
exhaust air ER method; or exception taken with supporting calculations
Indicate ER rated effectiveness that increases OSA enthalpy by >_ 50% based on delta
between OSA and return air enthalpies at design conditions
Laboratory exhaust systems
For buildings with total lab exhaust > 5,000 cfm, indicate method of energy recovery used to
NA
C403.2.7.2
(energy recovery)
pre -condition laboratory make-up air; ER effectiveness (min 25°F); or alternative. method per
exception (VAV exhaust, semi -conditioned makeup, or GERM calculation)
For buildings with pools or spas with water surface area > 200 sf, indicate exhaust air ER
C404.10.4
Pools and permanent spas
method and use of waste heat (preheat ventilation air, pool water or service hot water); or
NA
(under
exhaust systems
exception taken
C404.11)
(energy recovery)
Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air
temperature at design conditions by >_ 36°F
Energy recovery -
For buildings with on -site steam heating systems, indicate condensate water ER
For buildings that use off -site generated steam where condensate is not returned to the
NA
C403.5.2
steam condensate systems
source, indicate on -site condensate water ER
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessa
Ma is To ota Edmonds WA 8 li 2017 Project Title: Date
J 9 Y
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
A licable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Buildin De artment
es,no,na
Documents
Notes
For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote
refrigeration capacity for coolers /freezers, indicate condenser ER and use of captured energy
(service water heating, space heating, or dehumidification reheating)
NA
C403.5.3
Energy recovery -
For buildings with >_ 40,000 sf conditioned floor area and with ? 1,000,000 Btu/h of remote
cooler /freezer condensers
refrigeration capacity for coolers /freezers,. indicate condenser ER and use of captured energy
for service water heating and also for space heating, or dehumidification reheating
For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and
NA
C403.5.4
Energy recovery -
design service hot water load. > 250,000 Btu/h, indicate condenser ER to pre -heat service
condenser systems
water; or exception taken. Provide calculations showing the amount of Yecovered heatthat is
utilized (60% of peak heat rejection load or pre-heatservice water to 85°F).
Hydronic System
Controls
For hydronic system pump motors >_ 7.5 hp, indicate method of variable flow control (VSD or
C403.2.13
Variable flow control -
equivalent method that requires>_ 30%design wattage at 50%design fluid flow}; note
NA
C403.4.2.7
hydronicsystem pumps
exception taken
Identify whether hydronic coils have DDC controls and associated manner of pump speed
control (differential pressure, zone. hydronic demand, etc)
For boilers that provide building heating, indicate controls that provide heating water
temperature setback based on outdoor temperature
M303
For heating and chilled water systems > 300,000 Btu/h, indicate systems are configured to
C403.2.5
H dronic s stem setback
automatically reset supply water temperature based upon demand; or exceptiontaken.
Yes
If system pump motor hp >_ 3 hp, also indicate controls automatically reduce flow by >_ 50%.
M303
C403.4.2.4
and part load controls
For chilled water systems (>_ 300,000 Btu/h, pump motor hp >_ 3 hp}that serve water-cooled
unitary air conditioners, indicate VSD or staged pumps in chilled water system and heat
rejection loop that reduce pump flow so that one control valve. is nearly wide open, or to
maintain a minimum differential pressure; or exception taken
M303
Yes
C403.4.2
Boiler sequencing
Indicate automatic controls that sequence operation of multiple boilers
M303
NA
C403.4.6
Hot gas bypass limitation
For cooling equipment with hot gas bypass, provide either multiple step unloading or
continuous capacity modulation; indicate bypass capacity per Table C403.4.6
NA
C403.4.2.2
Two -pipe changeover
Indicate changeover deadband (min 15°F), heating /cooling mode scheduling and
systems
changeover temperature range (limit 30°F)
NA
C403.4.2.6
Chiller /boiler plant pump
Indicate controls are configured to automatically reduce overall plant flow and shut-off flow
isolation
through individual chillers and .boilers when not in use
For cooling towers with fan motors >_ 7.5 hp, indicate VSD and method to adjust fan speed
C403.2.13.1.1
Heat rejection equipment -(
ad'usted based on leavin fluid tem erature or condenser tem erature ressure of heat
J g P P / P
NA
C403.4.3.1.1
C403.4.3.1.2
variable flow control
rejection device)
For multiple -cell heat rejection equipment with VSD, indicate controls that ramp all fans in
unison
NA
C403.4.3.3
Heat rejection equipment -
Indicate open -circuit cooling towers with multiple pumps or VSD control are designed so all
cooling tower flow turndown
cells can be run in parallel
NA
C403.4.2.3.1
Water loop heat pump -
Indicate capability of central equipment to provide minimum 20°F water supply temperature
deadband
deadband between heat rejection and Beat addition modes; or exception taken
Water loop heat pump -
Indicate type of cooling tower (open- or closed-circuit) in equipment schedule; indicate method
NA
C403.4.2.3.2.1
heat rejection equipment,
used to limit system heat loss when heat rejection is not needed
Zone 4
Water loop heat pump -
For open- or closed-circuit cooling towers, provide a heat exchanger that separates the cooling
NA
C403.4.2.3.2.
heat rejection equipment,
tower and heat um loo
P P P
Zone 5
NA
C403.4.2.3.3
Water too heat um
P P P
For h dronic heat um s stems with totals stem ower 10 h indicate 2-wa isolation
Y P P Y Y P P' Y
isolation valves
valves on each heat pump and variable flow system control
Dedicated Outdoor Air Systems (DOAS) -Optional through 6/30J16, Prescriptive 7J1/2016
For buildings with office, retail, education, library and fire station spaces, identify these spaces
Yes
C403.6
Dedicated outdoor air
on plans; indicate that ventilation air in each occupied space is provided via a DOAS system;
C403.6.3
systems
or documentcompliance with C403.6:3 Impracticality; or exception taken (buildings complying
with C402.4.1.4 or C406.6 may not utilize exceptions)
M003
Energy recovery ventilation
For all DOAS systems, indicate exhaust air ER method; or exception taken with supporting
NA
C403.6.1
with DOAS
calculations. Indicate ER rated effectiveness that increases OSA enthal b > 50% based on
PY y "
delta between OSA and return air enthalpies at design conditions.
Indicate equipment associated with the delivery of zone level heating and cooling (fans,
Heating /cooling system
hydronic pumps, primary air dampers, etc) are configured to shut off, and central equipment is
NA
C403.6.2
controls with DOAS
configured to turn down, when there is no call for heating or cooling in the zone they serve
If applying Exception to heating /cooling fans used for air mixing in the space during deadband
periods, include fan watts per cfm in equipment schedule
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
C403.2.4.10
Group R2 / R3 dwelling
For primary space conditioning system, indicate 5-2 programmable thermostats capable of two
NA
C403.2.4.11
units, Group R2 sleeping
setback periods per day; for all thermostats indicate purpose (heating only, cooling only, or
units
both), required temperature range and at minimum a 10°F deadband; or exception taken
M002,
Indicate method of ventilation air delivery (natural or mechanical) for each zone
M003
C403.2.6
If mechanically delivered, indicate that systems are configured to provide not more than 150%
M004,
Yes
C403.2.11.4
Ventilation
of, but at least the minimum required volume of outdoor air to each zone per IMC, ASHRAE
M005
62.1 or other applicable code (WAG, OSHA, etc); or exception taken
If delivered via natural ventilation, identify required elements per IMC including minimum
NIA
openable area to the outdoors or qualifying adjoining spaces
Identify spaces > 500 sf with occupant load > 25 people/1,000 sf per IMC; for each space
Demand controlled
indicate whether it is served by an HVAC system with total design OSA > 3,000 cfm, and / or
NA
C403.2.6.2
ventilation
the system has airside economizer or automatic modulating OSA damper; indicate OSA
controls are configured to provide demand controlled ventilation or provide supporting
documentation fora lied exce tion
PP P
For gyms, classrooms, auditoriums and conference rooms > 500 sf, indicate occupancy -based
NA
C403.2.6.3
Occupancy sensors
OSA control when space is unoccupied and method (closes OSA damper or shuts -off
equipment); or alternate means provided toautomatically reduce OSA when space is partially
occupied
C403.2.6.4
Enclosed loading dock
For enclosed loading docks, indicate ventilation /exhaust system method of activation (gas
NA
C403.2.6.4,1
ventilation
detection system for CO and NO2, or occupancy sensors), and control method (staged or
modulatin g)
M002
Yes
C403.2.6.4
Enclosed parking garage
For enclosed parking garages, indicate ventilation !exhaust system activated by gas detection
M003
C403.2.6.4.2
ventilation
system for CO and NO2, and control method (staged or modulating); or exception taken
Provide calculations that show a balanced accounting of total kitchen exhaust (include all
hoods) with % ofsupply air, transfer air from adjacent spaces, and make-up air;. if applicable,
indicate that direct make-up air to each hood does not exceed 10% df hood exhaust
NA
C403.2.7.1
Kitchen exhaust hoods
For kitchens with total hood exhaust exceeding 2,000 cfm, indicate exhaust air rate per Table
C403.2.7.1 and compliance method (DCV, energy recovery, or transfer air that would
otherwise be exhausted)
NA
C403.2.7.2
Laboratory exhaust systems
Refer to Systems Requiring Energy Recovery for requirements
Variable flow capacity -
For HVAC fan motors >_ 7.5 hp, indicate method of variable flow control (VSD, or equivalent
NA
C403.2.13
HVAC system fans
control method that reduces design air volume by 50% at 1/3 static design pressure); note
exception taken
For DX air handlers with economizer and cooling capacity >_ 65,000 Btu/h, indicate number of
cooling stages provided and method (multiple compressors and / or variable speed
M002,
DX air handler variable
compressors}; indicate minimum displacement (capacity reduction) as % of full load
M003
M001,
Yes
C403.3.1
cooling control
(Under Integrated
M002,
Economizer)
Indicate control method (cooling capacity controlled in response to space temperature, space
M003,
temperature controlled by modulating supply airflow, or both)
M004,
M005
>
For DX air handling units with cooling capacty_ 65,000 Btu/h and evaporatroe and chilled
water air handling units with fan >_ 0.25 hp, indicate whether system is single zone or multiple
zone and related control method coolin ca acit controlled in res onse to s ace
( 9 P Y P P
temperature, space temperature is controlled by modulating supplyairflow, or both)
NIA
For mechanical cooling systems (includes DX and chilled water coifs) that control cooling
capacity in response tospace temperature - Provide a minimum of two stages of fan control;
Yes
C403.2.11.5
Fan airtlow control
indicate minimum fanspeed is <_B6% of full speed drawing <_ 40% of full speed fan power
M002,
during periods of low cooling or ventilation only
M003
For other mechanical cooling systems (includes DX and chilled water coils) that control space
tem erature b modulatin airflow in lieu of or in addition to controllin ca acit in res onse
P Y 9 ( , � 9 P Y P
to s ace tem erature -Provide fan controls for modulatin su I airflow indicate minimum
P P ) 9 PPY
fan speed is s 50% of full speed drawing <_ 30% of full speed fan power during periods of low
cooling or ventilation only; or exception taken
N(A
Provide central and zone level DDC controls as required based on system application,
No
C403.2.4.12
DDC system capabilities
capacity or size thresholds and other qualification per Table C403:2.4.12.1
Identify all DDC system input! output control points; indicate capability for trending and
raphical displa
Ducting Systems
C403.2.8.1
Indicate on plans that all ductwork is constructed and sealed per IMC
M001
For OSA ductwork, also indicate on plans that ductwork meets air leakage requirements per
Yes
C403.2.8:3
Duct construction
C402:5and vapor retarder requirements per the IBC
M001
Yes
C403.2.8.3
Duct pressure
classifications.
Identif location of low medium and hi h ressure ductwork on fans
Y g P P
M001
NA
C403.2.8.3.3
High pressure duct leakage
Indicate high pressure duct leakage testing requirements on plans; provide test results to
test
jurisdiction when completed
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
C402.4.1.4
Increased prescriptive
NA
C403.6
maximum vertical
Indicate that all occupied, conditioned spaces are served by a DOAS per C403.6
fenestration area with DOAS
Additional Efficiency Package Option, Dedicated Outside Air Systems (DOAS)
NA
C406.6
Building provided with
To comply with additional efficiency package option, indicate that 90% or more of all occupied,
DOAS
conditioned spaces are served bya DOHS per C403.6
Multiple Zone Air Systems
Air systems serving multiple
Identify supply air systems serving multiple zones and the zones they serve on plans; indicate
NA
C403.4.4
whether system is VAV and method of primary air control; or provide supporting
zones
documentation for applied exception to VAV
Provide equipment schedules on plans or MECH-EO form that list all VAV air terminals and
types
For each air terminal include: maximum airflow rates for primary supply air during zone peak
VAV systems serving
NA
C403.4.4
multiple zones
heating and zone peak cooling; maximum airflow during reheating, retooling or mixing;
minimum airflow rate to maintain required ventilation, and the basis for these values; if IMC or
ASHRAE 62.1 multiple zone equation is basis for minimum flow rates, provide calculation on
plans
NA
C403.4.4.1
Single duct VAV terminal
Indicate single duct terminal units are configured to reduce primary supply air before reheating
units
or retooling
NA
C403.4.4.2
Dual duct systems -terminal
For systems with separate warm air and cool air ducts, indicate terminal units are configured to
units
reduce the flow from one duct to minimum before mixing with air from the other duct
Indicate locations of duct static pressure sensors on plans; include at least one sensor per
major duct branch; verify controller Setpoint pressure at each sensor is <_ 1.2 inch w.g.
For systems with zone level DDC, indicate controls are configured to monitor zone damper
NA
C403.4.1.1
VAV system static
C403:4,1.2
pressure sensors -
and DDC
Positions and reset static pressure Setpoint based on the zone requiring most pressure;
sensors set points
include control logic that automatically detects and generates an alarm if any zone excessively
drives reset logic, and allows building operators to exclude zones from reset logic
Multiple -zone VAV system
For systems with zone level DDC controls, indicate controls are configured to automatically
NA
C403.4.4.3
ventilation optimization
reduce outdoor airflow in response to changes in system ventilation efficiency; or exception
controls
taken
NA
C403.4.4.4
VAV system supply air reset
Indicate controls automatically reset supply air temperature in response to building loads or
outdoor air temperature; or exception taken
Multiple Zone HVAC Systems, High Efficiency VAV -Required for systems utilizing C403.6 DOAS Exception 2, must comply with all 16 provisions
NA
C403.7,
Air economizer
Indicate system is configured for 100% air economizer operation and complies with all related
Item 1
economizer requirements per C403.3 (without economizer exceptions)
NA
C403.7,
Direct digital controls (DDC)
Provide DDC controls for all components of system; identify all DDC system input /output
Item 2
control points; indicate capability for trending and graphical display
For systems with minimum OSA > 2,500 cfm, indicate outdoor airflow monitoring station that
NA
C403.7,
Outdoor airflow
measures OSA intake under all load conditions; indicate control sequence that increases or
Item 3
measurement and reduction
reduces system OSA cfm based on VAV terminal feedback of ventilation efficiency (per
C403:4.4.3 without exceptions) or DCV (per C403:2.6.2)
NA
C403.7,
Supply airflow measurement
For systems with minimum OSA > 2,500 cfm, indicate supply airflow monitoring station
Item 4
capable of measuring supply air delivered to VAV terminals under all load conditions
C403.7,
Zone isolation and
Verify maximum area served by a single HEVAV system is <_ 50,000 sf, or one entire floor,
NA
Item 5
maximum area served
whichever is greater; in addition if a system serves > 25,000 sf, that includes areas that are
expected to be occupied non -simultaneously, indicate zone isolation controls per C403.2.4.4
C403.7,
Interior /exterior zone
Verify that VAV terminals serving interior cooling driven loads are sized per design supply air
NA
Item 6
design supply air
temperature that is 5°F higher than VAV terminals serving exterior zones
temperature
C403.7,
Maximum air terminal inlet
Identify air terminals with minimum primary airflow setpoints > 50% of maximum setpoint in
NA
Item 7
velocity
equipment schedule or MECH-EO form; indicate air terminal inlet velocity does not exceed 900
fpm
NA
C403.7,
Sequence of operation
Indicate DDC system sequences of operation are designed and configured per ASHRAE GPC
Item 8
36
NA
C403.7,
Maximum allowable system
Verify fan system bhp is <_ 90% of the bhp limit per Option 2 equation in Table C403.2.11.1(1),
Item 9
brake horsepower
provide MECH-FANSYS form for each system
Indicate all series and parallel terminal fans have electronically commutated motors; indicate
NA
C403.7,
Fan -powered terminal unit
DDC control system is configured to vary air terminal fan speed as a function of the load;
Item 10
motor and control
indicate fan speed during periods of low heating, low cooling, or ventilation only is <_ 66% of
peak design air flow or provide supporting documentation for applied exception
COPYRIGHT NOTICE
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 7 of 7 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 - Page 2 of 2 THIS LAYOUT/DESIGN IS A
Mechanical Permit Plans Checklist MECH-CHK Service Water Heating Permit Plans Checklist SWH-CHK COPYRIGHTED WORK OWNED BY
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017 COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST') AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
O0
Q
O T�T
!!1�
V
Z 0
p z
l� 0 0
r
N �
W
O
O 0
I.-:
N
W
m
fn ( N =
H
O
Q Z O
Y OF— N O Q
O
_ 0 �
W Q o0
W �4 W H
.4 Z�-
p W U
W a� 0
00
1—LL
om �o
S o U
(0 fl-
ow 0
0� o
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 U (0 Z
Power echanical Fan System ' •
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
ls A• L
OF WA
tiR V
� z
.p 38898 p w�
�� ��'GIST$4�' Ct�'
�SSjCNAL��
SIGNED: 8/11 /2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11 /2017
JOB NUMBER
2015 WSEC MECH FORM, 117036
SHEET TITLE
ENERGY CODE
COMPLIANCE
FORMS
SHEET NUMBER
M007
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
C403.7,
Application of single duct
Indicate VAV terminal types on plans; verify fan -powered terminal units only serve perimeter
NA
Item 11
and fan -powered terminal
zones with envelope loads;. verify all other zones are served by single duct terminal units
units
C403.7,
Fan -powered terminal unit
Indicate DDC controls are configured to automatically reset the primary supply air cfm setpoint
NA
Item 12
primary air reset
of all fan -powered terminal units to the minimum required to maintain ventilation during
occupied heating or deadband, based. upon the VAV air handling unit OSA ventilation fraction
For spaces > 150 sf with occupant density >_ 25 people ! 1000 sf, indicate space is served by a
NA
C403.7,
High occupancy space
dedicated terminal unit with DCV control that resets terminal unit ventilation setpoint; also
Item 13
controls.
indicate occupancy sensor control that automatically reduces minimum ventilation to zero and
sets back room heating and cooling setpoints by >_ 5°F
For server, electronic equipment, telecom or similar spaces with cooling loads > 5 W/sf,
NA
C403.7,
Dedicated HVAC systems
indicate spaces are served by independent HVAC systems that are separate from HPVAV
Item 14
systems serving rest of building; indicate dedicated HVAC systems have air economizer
controls or energy recovery per C403:3 Exception 9
Indicate whether systems are served by a high efficiency heating water plant, or a high
efficiency chilled water plant
If complying via high efficiency heating water plant: Indicate all VAV terminals have hydronic
heating coils served. by heating water system with either gas -fired boiler(s) with thermal
NA
C403.7,
Central plant efficiency
efficiency >_ 90%, air -to -water heat pumps, or heat recovery chillers
If complying via high efficiency chilled water plant: Indicate all VAV air handlers have cooling
Item 15
coils se
Project Title: Magic Toyota Edmonds WA
Date 8/11/2017
For Building Dept. Use
HVAC Air Distribution System Schedule
List all HVAC systems that have the capability to provide heating and/or cooling to the spaces they serve.
System or
Primary Supply
Fan ID
Speed Control
(Note 1)
Description
(Note 2)
System Total '
Nameplate HP '
{Note 3}
Fan Power
Calculation i
Required
(Note 4)
RTU-1
CV
PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING
3
No
RTU-2
CV
PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING
2
No
RTU-3
CV
PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING
1
No
RTU-4
CV
PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING
1
No
RTU-5
CV
PACKAGED ROOFTOP UNIT DX COOLING GAS HEATING
2
No
Note 1 -Constant Volume (CV), Variable Air Volume (VAV), or Hospital/Lab CV system that qualifies for VAV budget per C403.2.11.1 Exception 1.
Single zone VAV systems shall comply as CV.
Note 2 =Describe system type and list all fans (or groups of fans) associated with the delivery and removal of conditioned air by the system.. Include
all supply, return/relief, exhaust and exhaust hoods (>1 hp), make-up air, dedicated outside air (DOHS), booster fans, and series fah -powered
terminals: VAV parallel fan -powered terminals and economizer relief fans do not need to be included if the fans do not operate at peak
conditions.
Note 3 = Enter the total nameplate hp of all fans associated with the delivery and removal of conditioned air by the system.
Note 4 -This form automatically identifies whether aMECH-FANSYS form is required to demonstrate compliance with the fan power allowance (Yes),
or this information is not required because the system has a combined total nameplate motor hp that is 5 hp or less (No)
MECH-FANSYS.: Forms
A MECH-FANSYS farm shall be provided for each system with total nameplate hp greater than 5 hp. Select (Add Fan
System Form): to generate an additional form, Added forms can be deleted with button in cell E32 of he added form.
2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 -Page 1 of 2
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2 & R3 over 3 stories and all R1 Revised January 2017
Project Title: Magic Toyota Edmonds WA Date 8/11/2017
The following information is necessary to check a permit application for compliance with the mechanicial systems and equipment requirements of the
Washington State Energy Code, Commercial Provisions.
Applicable
Code Section
Code Provision
Information Required - Must be in permit documents
Location in
Building Department
es,no,na
Documents
Notes
Equipment -Sizing, Performance and Type
Yes
C404.2
SWH equipment type and
Provide equipment schedule on plans indicating type and capacity; indicate efficiency complies
efficiency
with required federal standard
P002, P003
For individual SWH equipment serving an entire building with >_ 1,000,000 Btu/h capacity,
indicate thermal efficiency ? 90%; or exception taken
For buildings with aggregate capacity of all SHW equipment >_ 1,000,000 Btu/h (exclude <
High input -rated SWH
NA
C404.2.1
systems
100,000 Btu/h equipment from threshold calculation), indicate average capacity weighted
thermal efficiency >_ 90%; or exception taken
If applying Exception 1 for site -solar or site -recovered energy, provide calculations and source
of annual service water heating energy use estimate
Yes
C404.4
Heat traps
Indicate piping connected to equipment have heat traps on supply and discharge
P001
Yes
C404.5
Insulation under electric
For electric water heaters located in unconditioned spaces or on concrete floors, indicate R-10
water heater
insulation under equipment
P001
Piping Systems
Indicate thickness of piping insulation on plans per Table C403.2.9; verify insulation is provided
Yes
C404.6
Insulation of piping
-from the water heater to the final fixture in a line, from the inlet /outlet piping at water heater
to heat trap (up to 8 feet), and on piping that is heat traced; note exceptions taken
p001
Indicate method of compliance on tans for all runs connecting service hot water source
p piping 9
Yes
C404.3
Efficient SWH supply piping
to hot water fixture (maximum pipe length or maximum pipe volume method per Table.
C404:3.T � provide calculations for all runs documenting the total length and / or volume )� P piping 9
P001
Service Water Heating System Controls
For circulation systems with dedicated return piping, indicate controls are configured to
automatically start pump based on demand for hot water and shut-off pump when there is no
demand and when the desired water temperature is met
P001
Yes
C404.7.1
Heated -water circulating
C404.8
systems
For circulation systems with cold water supply serving as the return indicate controls
piping 9
are configured to automatically start based on demand for hot water and shut-off um
Y pump pump
when there is no demand, or when temperature of water entering the cold water supply pipe is
>_ 104°F
P001
For heat trace systems provided to maintain temperature of service hot water in
P piping,
NA
C404.7.2
Heat trace system controls
indicate controls are configured to de -energize system when there is no demand for hot water
Y
and when the desired water temperature is met
NA
C404.7.3
Controls for hot water
Forsystems with separate water heater and storage tank indicate controls are configured to
9
storage
limit operation time of pump after end of heating cycle to <_ 5 minutes
For SWH, pool /spa and pressure boosting pump motors >_ 7.5 hp, indicate method of variable
0
flow control VSD ore equivalent method that requires _ 30 /o design wattage at 50%desi n
( q 9
NA
C403.2.13
Variable flow control -
fluid flow); note exception taken
C403.4.2.7
pumps
Identify basis of pump speed control (differential or static pressure setpoint, pressure, zone
load demand, etc
Pools and Permanent Spas -Equipment and Controls (Sections are under C404.11}
Pool heating equipment
Provide equipment schedule on plans indicating type and capacity for all pool heating
NA
C404.10.1
efficiency
equipment; indicate efficiency complies with required federal standard; for heat pump water
heaters indicate COP >_ 4
NA
C403.2.13
Variable flow control -
Refer to Service Water Heating System Controls
NA
C404.10.1
Pool heater on /off controls
Indicate automatic on /off control based on scheduling and readily accessible on /off switch
C404.10.2
on heater that operates independent of thermostat setting; note exceptions taken
For all pools and in -ground permanent spas, indicate a vapor retardant cover on plans
NA
C404.10.3
Pool covers
For all pools and in -ground spas heated to > 90°F, indicate cover shall include insulation >_ R-
12
NA
C404.10.3
Pool assembly insulation
For all pools and in -ground spas heated to > 90°F, Indicate on plans. that sides and bottom are
provided with insulation >_ R-12
NA C404.12 Energy consumption of Indicate portable spa complies with Association of Pool and Spa Professionals APSP-14
portable spas
Energy Recovery (ER) Systems -Service Water Heating and Pool Systems
C404.10.4
For buildings with pools or permanent spas with water surface area > 200 sf, indicate exhaust
(Section
Pools and permanent spas
air ER method and use of waste heat (preheat ventilation air, pool water or service hot water);
NA
under
exhaust systems
or exception taken
Indicate ER system has the rated effectiveness and is configured to decrease the exhaust air
C404.11)
(energy recovery)
temperature at design conditions by >_ 36°F
For buildings with food service, meat or deli departments that have >_ 500,000 Btu/h of remote
refrigeration capacity for coolers /freezers, indicate if condenser ER will be used to pre -heat.
NA
C403.5.3
Energy recovery -
service water
For buildings with >_ 40,000 sf conditioned floor area and with >_ 1,000,000 Btu/h of remote
cooler /freezer condensers
refrigeration. capacity for coolers /freezers,. indicate if condenser ER will be used to pre -heat
service water
For buildings with 24-hour operation and > 1,500,000 Btu/h of heat rejection capacity and
NA
C403.5.4
Energy recovery -
design SWH load > 250,000 Btu/h, indicate condenser ER to pre -heat service water; or
condenser systems
exception taken. Provide calculations showing the amount of recovered heat that is utilized
(60% of peak heat rejection load or pre -heat service water to 85°F).
NA
C404.10
Drain water heat recovery
For systems incorporating drain water ER, indicate system design complies with CSA 655.2
units.
(or CSA 55.1 for Group R); indicate potable waterside pressure loss at design flow is < 10 psi
Service Water Heating Energy Use Metering
NA
C404.9
SWH energy usage in
For Group R-2 multi -family buildings with central SWH systems, provide metering of hot water
dwelling units
energy usage per dwelling unit;. indicate metering and data reporting method
SWH equipment energy use
For new buildings 5Q,000 sf and building additions 25,000 sf, with total SWH equipment
NA
C409.3.2
metering
capacity >_ 50 kW (>_ 170,600 Btu/h), verfiy energy use metering of all SWH equipment will be
provided per C409
Additional Efficiency Package Option, Reduced Energy Use In Service Water Heating -Must comply with both provisions to be eligible
To comply with additional efficiency package option, verify that >_ 90 % of the conditioned floor
NA
C406.7.1
Eligible building type
area of the building is one or more of the occupancies identified in this section OR;
g P
Provide whole building energy analysis per C407 that demonstrates the SWH load in the
> 0
building is _ 10 /o of total building energy loads
To comply with additional efficiency option, provide documentation that verifies
package P
0
_ 60 /° of building annual SWH ever is provided b high efficiency sources heat water
9 9Y p Y Y ( pump
heater with COP >_ 3, waste heat recovery, solar water -heating system);
NA
C406.7.2
C403.5.4
Load fraction
For buildings with 24-hour operation and with > 1,500,000 Btu/h of heat rejection capacity and
design service hot water load > 250,000 Btu/h (per C403.5.4); provide documentation that
0
verifies >_ 100 /o of building annual SWH energy is provided by condenser energy recovery or
other high efficiency source
Documentation and Specific System Requirements to Supporting Commissioning
Indicate that all SWH equipment and controls for which the WSEC requires control functions
q
Scope of service water
and / or configuration to perform specific functions are required to be commissioned;+D7
P101
For buildings where the largest SWH system has ? 200,000 Btu/h total output capacity,
Yes
C408.4
heating systems
commissioning
indicate that all SWH systems regardless of individual capacity are required to be
commissioned.
Indicate that all pool and permanent spa water heating systems regardless of individual
capacity are required to be commissioned
q '
Scope of pool and
Indicate that energy recovery equipment that heats pool water regardless of capacity is
NA
C408.4.1.3
permanent spa systems
required to be commissioned;
commissioning
Identify all pool heating and energy recovery equipment and controls that the WSEC defines
as being capable of and / or configured to perform specific functions.
Indicate in plans and specifications that Cx per C408 is required for all applicable service water
heating systems;
P001
Include general summary with at a minimum of Items 1 thru 4 of the Cx plan per C408.1.2
C404.13
C408.1.1
Commissioning
including: narrative description of activites, responsibilities of the Cx team, schedule of
Yes
C408.1.2
requirements in construction
activities including verification of project close out documentation per C103:6, and conflict of
C408.1.4.2
documents
interest plan (if required);
P001
C103,6
Include in general summary that a Cx project report or Compliance Checklist (Figure
C408.1.4.2) shall be completed by the Certified Cx Professional and provided to the owner
prior to the final mechanical inspection.
P001
Yes
C408.4.1
Functional performance
Identify in plans and specifications the intended operation of all equipment and controls during
testing criteria
all modes of operation, including inte
M-ECHANICAL FIRST FLOOR -PLAN ---NORTH,
i
GENERAL NOTES:
1. AREAS IN WHICH STATIONARY MOTOR VEHICLES ARE
OPERATED SHALL BE PROVIDED WITH A SOURCE
CAPTURE SYSTEM THAT CONNECTS DIRECTLY TO THE
MOTOR VEHICLE EXHAUST SYSTEM PER IMC 502.14,
TO BE PROVIDED BY OTHERS.
2. THE VEHICLE EXHAUST SYSTEM SHALL BE
ENGINEERED BY OTHERS WITH DESIGN BY A
REGISTERED DESIGN PROFESSIONAL OR SHALL BE
FACTORY BUILT EQUIPMENT DESIGNED AND SIZED
FOR THE PURPOSE.
3. THIS PROJECT UTILIZES A RETURN AIR PLENUM
ABOVE CEILING SPACES AND A SUCH ALL MATERIALS
IN THIS PLENUM SHALL MEET THE REQUIREMENTS
OF IMC 602.2.1.
4. LOUVERS REPRESENT FLOW THROUGH NET FREE
AREA AND MUST BE COORDINATED
WITH THE ARCHITECT FOR INSTALLATION INTO THE
TILT UP STRUCTURE.
5. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN
ROUTING AND REFERENCE ONLY, SEE THE M-300
SERIES DRAWINGS FOR RADIANT PIPING DETAILS.
RADIANT HEAT ZONE REFERENCE:
250 CFM I I I /L _.._.__ _ ! INTERIOR:
----- _ - - ---------- -
r
- v 1 + _`
"1200I_ _ J �I
T
0 GG„ __' __ _ , RZ B: 9.24 GPM ACROSS 17 CIRCUITS AND 2 MANIFOLDS
l/ _________
- L-1 - C01-25 - 'r lT _ ; RG-1 RZ-C: 5.58 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD
RZ-D: 8.27 GPM ACROSS 15 CIRCUITS AND 2 MANIFOLDS
IF
f .;'�``W." �`' RZ-E: 1.81 GPM ACROSS 5 CIRCUITS AND 1 MANIFOLD
4--
4-
Co2-12 C
T C, " ..
- _ a
6 0 i�
8"0 ------------� - I \ -- ----- -
CD1 25
E,�� EWH-6 � \ r — �
-- - 4 688 CFM
r
aLsl
�_�PAEG2-175
F z z _ - �9 "�, , \ 4,688 CFM i �
1 mm124x24 SCREENED �,E ��`, t���„ i 2r4x24 SCREENED OPENINGI
-
1 I �I I \ I I (OPENING
, RZ D1
i--------------------- ' -----
i
} _ _ - _ 1 �: _ __v_ _-- -- -
' I / C� EF-5 VFD RZ-D
i - -
( Jp{ L - - -_--- - L------ ------ ---------------------`--
r �
--------------------
.............
RZ-F - --- -- - - - -- %� -- -----
21
RADIANT ZONE C
_.
0 CO
L.. - '
�, _ / — ' —
1 T�.v�l� �o ... i
t
' F
'I I--r -J I F I F r
J L J88x36 L I �
gy-m,
_ L----J L----J
11.0 SQ. FT. NFA
5,680 CFM I _ ,
T !-ir
- -- I. RZ-C
RADIANT PIPING MAIN
L,---1--------►--------------- -----1------- --------------
�_______IL -11
��.
T
1 2
/ T/Ct, c, I a,
T EF-6
L-x: 2004"
L-x: 20"x14" / 1.95 SQ. FT. NFA
12
~} 1.95 SQ. FT. NFA i` / 1050 CFM
_ ' \, l 1050 CFM
-J�
EXTERIOR:
RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD
RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS
KEY NOTES:
0 EXTERIOR ZONE (SNOW MELT)
2Q INTERIOR ZONE (COMFORT HEATING)
3Q SEE SHEET M303 FOR RADIANT PIPE SIZING
A
1A
t1
N
7
S
H
H
1
7 1
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
•
•
0 J
0
z.:
N
a� 00
Q�
= p
O z
O p
CO
lir-
N p
L1J
O
o
w
tz
U)
w
m
co
N =
co
-�
O
Q z
�
Y
N
O Q
LL Co
INS110
�
o0�
Lu
W
w �
co
00
pco
W
�w
��
oo
zm
o
QLL
��
1(0
o
U
bm
&
CO
SIGNED: 8/11 /2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
08/11 /2017
tOB A 1 -:
11 .,
SHEET TITLE
MECHANICAL
FIRST FLOOR PLAN
- NORTH
Ed01:4Ai,Ill 611Ail
4 1 1
- - -_ -- - - - ---------- ---- ------ -
f .,
GENERAL NOTES:
1. AREAS IN WHICH STATIONARY MOTOR VEHICLES ARE
OPERATED SHALL BE PROVIDED WITH A SOURCE
CAPTURE SYSTEM THAT CONNECTS DIRECTLY TO THE
MOTOR VEHICLE EXHAUST SYSTEM PER IMC 502.14,
TO BE PROVIDED BY OTHERS.
2. THE VEHICLE EXHAUST SYSTEM SHALL BE
ENGINEERED BY OTHERS WITH DESIGN BY A
REGISTERED DESIGN PROFESSIONAL OR SHALL BE
FACTORY BUILT EQUIPMENT DESIGNED AND SIZED
FOR THE PURPOSE.
3. THIS PROJECT UTILIZES A RETURN AIR PLENUM
ABOVE CEILING SPACES AND A SUCH ALL MATERIALS
IN THIS PLENUM SHALL MEET THE REQUIREMENTS
OF IMC 602.2.1.
4. LOUVERS REPRESENT FLOW THROUGH NET FREE
AREA AND MUST BE COORDINATED
WITH THE ARCHITECT FOR INSTALLATION INTO THE
TILT UP STRUCTURE.
5. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN
ROUTING AND REFERENCE ONLY, SEE THE M-300
SERIES DRAWINGS FOR RADIANT PIPING DETAILS.
RADIANT HEAT ZONE REFERENCE:
INTERIOR:
RZ-A:
11.23
GPM
ACROSS
19 CIRCUITS AND
2 MANIFOLDS
RZ-B:
9.24
GPM
ACROSS
17 CIRCUITS AND
2 MANIFOLDS
RZ-C:
5.58
GPM
ACROSS
10 CIRCUITS AND
1 MANIFOLD
RZ-D:
8.27
GPM
ACROSS
15 CIRCUITS AND
2 MANIFOLDS
RZ-E:
1.81
GPM
ACROSS
5 CIRCUITS AND 1
MANIFOLD
EXTERIOR:
RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD
RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS
KEY NOTES:
(1) SEE SHEET M303 FOR RADIANT PIPE SIZING
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
•
•
0
z.:
N
a� 00
Q�
Uj
= p
O z
O p
co
III
N p
L1J
O
o
�
w
U)
W
m
Cn co
N =
O
Q z
�
Y OF-
N
O Q
0 N
LL Co
F
LL Co
co
0
0000
W ¢
LU
75;
Lu
W F—
p
W
o0
��
oo
zm
o
QLL
��
J
o
U
�
I
co
;t
( I CD1-1 A � �'� o -- _ � � � �WAsh�'
ti
_,
� � � EG2-150 a ` � � g;,�
:D OPENINGI / I -= \
RG1 �
-- ------`i
% I` =,� --P3889E8�oG2-150
� � D2-GIST
TO RTU-3 sioxL 2"C
L----------------- -- ---------------- ---
a
t
I
I
i
SIGNED: 8 11 2017
.Ea .-. -.S-- - ----- "-8"0
-
REVISIONS
z - CD2-150 �1
12 0. ISSUE FOR PERMIT 8/11/2017
`i~%
L-2
20"x14"
1.95 SQ. FT. NFA
1050 CFM
�
o
0
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11 /2017
JOB NUMBER
117036
SHEET TITLE
MECHANICAL
FIRST FLOOR PLAN
- SOUTH
Ed01:4AClII1611:40
1'I ■ 1�1J
MECHANICAL FIRST FLOOR PLAN - SOUTH �_�;_�.1 �_,� ��_�;- �,__,1.
ISCALE: 1 /8" = V-0"
GENERAL NOTES:
1. THIS PROJECT UTILIZES A RETURN AIR PLENUM
ABOVE CEILING SPACES AND A SUCH ALL MATERIALS
IN THIS PLENUM SHALL MEET THE REQUIREMENTS
OF IMC 602.2.1.
2. RADIANT HEATING SHOWN ON THIS SHEET FOR MAIN
ROUTING AND REFERENCE ONLY, SEE THE M-300
SERIES DRAWINGS FOR RADIANT PIPING DETAILS.
RADIANT HEAT ZONE REFERENCE:
INTERIOR:
RZ-A: 11.23 GPM ACROSS 19 CIRCUITS AND 2 MANIFOLDS
RZ-B: 9.24 GPM ACROSS 17 CIRCUITS AND 2 MANIFOLDS
RZ-C: 5.58 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD
RZ-D: 8.27 GPM ACROSS 15 CIRCUITS AND 2 MANIFOLDS
RZ-E: 1.81 GPM ACROSS 5 CIRCUITS AND 1 MANIFOLD
EXTERIOR:
RZ-F: 24.14 GPM ACROSS 10 CIRCUITS AND 1 MANIFOLD
RZ-G: 24.99 GPM ACROSS 10 CIRCUITS AND 2 MANIFOLDS
KEY NOTES:
1� RADIANT PIPING TO MECH ROOM, SEE M303.
A
1
N
7 1
A
S
H
H
1
7 1
KEY PLAN
MECHANICAL SECOND FLOOR PLAN - NORTH
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
•
•
0
z.:
N
a� 00
Q�
Uj
= p
O z
O p
co
lir-
N p
L1J
O
o
�
W%,m,
w
�
U)
W
m
Cn co
N =
~
d00
Q z
:D O
Y OF-
N
O Q
0 N
LL Co
F
LL Co
co
0
0000
W ¢
LU
75;
Lu
W F-
pcnW
�0
��
oo
zm
o
QLL
��
J
o
U
�
&
co
SIGNED: 8/11 /2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11 /2017
JOB NUMBER
117036
SHEET TITLE
MECHANICAL
SECOND FLOOR
PLAN - NORTH
Ed01:4AClII161140
ISCALE: 1 /8" = V-0"
5
--------------------------------------------------------
-- -------------- --- -------------- -- -----------
-:I-
E
L.
7-7-
0 IJ
0 2
CD2-200
UP TO
EF-3
- -------------
-
3
1-70 EG
6"0
CD1-100
CD2-200
------------
8"0
gjorRG1
EG1 -70 RG1
LE 0 "AG E 2 U
RG1
rl2xlO, 04
1200:
ic,41
\-12x10
RG1
ic,41
CD1 -90:
CD1-90
36xl:2
28x14 UP TO
P TO AHU: 4
%HU-4
(sF 'CURE CI ES 22,,
C-80
2 \j. 5)
-------------------- ---------- —
LDl -475
CD2-200
LD1-425 —12"0
1604
-8"o
XCD2-200
1,80 LDl -425 12"0-\ 2"0
"
i
CD1 -90
0
Q-1 - XR 20U
20xl 6
2000
24x 16 � 1
2"0
2"0
2"0
t IbIN
2406
............. Fill
lo"o
lo"o
C0111T T -)09:
-----------
-
CD3-250
CD3-250 R
12xl2
CD1-100
\ -6"0
UP TO
EF-2
G2-2000
- —
-------------- -------
------------ 7 ---------------- ---------- T
I
---------- - - -----
r 20xl 6
RG1'---
----------------
T
EG 'AIOMIN T
I Tal
------------------- I
1604-
UP TO
EF-4
RG1
L
8"o
CD2-150
2"0
00
2"0
A GENERALNOTES:
1 THIS PROJECT UTILIZES A RETURN AIR PLENUM
ABOVE CEILING SPACES AND A SUCH ALL
MATERIALS IN THIS PLENUM SHALL MEET THE
REQUIREMENTS OF IMC 602.2.1.
B
-LDl -475
-LDl -425
i I M P401
m
1-425
14425
LDl -425 �/- -`1
---------- --------- ---- ------------------ D
ilmlyzip
OMNI$
LDl -425
E
1-425
1-425
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
2w-C
0
CD
ui
t::
U)
U-1
m 3:
:D
co co
-C-,,Jj -r
co
d
00
:D 0
0
F- c"I
0 <
LL Co
0 co
0000
w
Lu
0 75;
Lu
0
cf) U)
Lu U)
p
cn
=
W
oo
2: cn
0
LL
2i
C\l
0
0
AM&
co
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
w
--------------------------- -
DESIGNED
p -- - ------------ - - -------- -- -- --------
--- - ------------- �,�: r -----------------------
----------- - -- — ------
G
36xl2�. c --- --
CSUSA NW EE
28x14 r i i UP TO 01! CE
UP TO i i AHU-5 CD2- 00 CHECKED
!AHU-5
CD2-250 CSUSA NW SAL
D2-150 c
N71
CD2-150 "0
............... 8"0 RG1
0 0 8 0—�
---------------
CD2-15 08/11/2017
-4
L4
--------------------------------------------------- --
8"0 12*� CDx-150
RG1
JOB NUMBER
10"o
r
lo"o - -- ---
-10"o i Cc 117036
"o 1
8"0
2"0
CD1-50 _0
8"0 6"0 CD3-250 CD3-225 SHEET TITLE
CD2-20 RG1
CD3-250 CD3-250 A
A MECHANICAL
r
. .............
RG1 SECOND FLOOR
------- — -- - -----
H PLAN - SOUTH
N s
SHEET NUMBER
KEY PLAN M 1 0 3
zi 3
ISCALE: 1/8" = V-0"
12 1
11
1 1
9 ?
`1 < ��
i
�1
! i
-
I
- _
-
- -
-
I
--
—I - -
'*
I �.
I
�
I
I
z
ti
�
I W
- -
- -
-
i�
-_
\
- _
t
i
i'
I
,
ft
1 j
(80
CU-3
LBS
(80 LBS)
(80,/LBS)
CU-7
(801BS)
I
4
/F
/f (80 LBS)
} (578 LBS)
,
f
,F
r
j
---------
--------- --- --
I
------------------------------------------N-
----------
/
I
1
f`
f
--------------- ---
\
-----------------------------
-----------------------------------
/
/
I
I
,
'
4 \
I
--------------
------
---- - _
_ _ ---
i
-----------
I
I
I
EF-9
(95 LBS)
I
1'
�11 j
10
_________ -
(�
MECHANICAL_ R00 PLAN - NORTH
_ -
--_____ ___ ___ ___
SCALE: 1 /8" = 1 '-0"
GENERAL NOTES:
1. PROJECT STRUCTURAL ENGINEER TO PROVIDE
ENGINEERING CALCULATIONS FOR SEISMIC
ANCHORAGE OF THE ROOF TOP UNITS AND ANY
OTHER ROOF TOP EQUIPMENT IN EXCESS OF 400
POUNDS.
2. PROJECT STRUCTURAL ENGINEER TO SPECIFY THE
REQUIREMENTS FOR CONNECTION OF THE ROOF TOP
UNITS TO THE CURBS AND THE CONNECTION
METHOD OF THE CURBS TO THE ROOF STRUCTURE.
A
t1
N
7 1
A
S
H
H
1
7 1
KEY PLAN
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
z.,
G
O
r
W
r
M
fn 0000
N _
Q z
=) O
Y
N
O Q
N
� =)
(o
LLCM0
O :u� �JE
cn
W Lf�
W I—
p
N
W
Z
U �-
W
00
O m
Qo
O
o
U
00
SIGNED: 8 11 2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
JOB NUMBER
117036
SHEET TITLE
MECHANICAL
ROOF PLAN -
NORTH
s
l:144AZ0161A4:1
7 6 5 J 2
--------------- — --------------------
----
------------- ---- ---- — I
- -------------- - -- - ----- -------- --- - -------------- - --- --------------- --- - -------------- - --- --------------- ---- ---------- -- - -- - -------------- - --- --------------- ---- --------------- --- -- - ----------------- - --- ------------------- --- - ------------------
A
GENERAL NOTES:
--------------
- - - ---------
1 PROJECT STRUCTURAL ENGINEER TO PROVIDE
-------------- -------- ---------
ENGINEERING CALCULATIONS FOR SEISMIC
ANCHORAGE OF THE ROOF TOP UNITS AND ANY
(90 LBS) OTHER ROOF TOP EQUIPMENT IN EXCESS OF 400
POUNDS.
2. PROJECT STRUCTURAL ENGINEER TO SPECIFY THE
REQUIREMENTS FOR CONNECTION OF THE ROOF TOP
UNITS TO THE CURBS AND THE CONNECTION
V. METHOD OF THE CURBS TO THE ROOF STRUCTURE.
- ----------
_J
---- ------------------- --- ------------------- ---- _,tip
------------------- ---- ------------------- --- ------------------ t ,, E
L
L
00,
1
KEY PLAN
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
90-11
0
:5
0
mfn
ZD
co
j --r
c\j
ob
QCy)
:z
=) 0
CN
0 <
C�
LL U)
� =)
c")
cc)
0 U)
c) 7--
U) cc)
ui
LLJ LO
LLJ
F—
W
p
of C\j
U)
-�7 >
Lu W
W
F-
IL
F
3
00
2: cn
0
LL
2i
c\j
0
C)
U
00
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
JOB NUMBER
1 117036
SHEET TITLE
MECHANICAL
ROOF PLAN -
SOUTH
s E i m 14 4 A Z L11 6 1 A 4 :1
M105
[.IMIECHANICAL ROOF PLAN SOUTH
SCALE:
CALE: 1/8" = 1'-0"
7
GENERAL NOTES:
------- - ------ --------
�'l
-- ------- -
IT
1. RADIANT ZONE OUTLINES ARE SHOWN ON
--------------------------------------------
................................................................................
M102 AND M103.
:A
2. THIS SHEET SHOWN THE SUB SLAB RADIANT
+
PIPING AS IT WILL LAY OUT IN THE SPACE
- --------------------------------------------
FROM THE MANIFOLDS, DETAILS OF THE
...............................................
INSTALLATION SHALL BE PROVIDED IN SHOP
------ �/ - ----------------------------------------------------------------
---
►- -----
- ------------------------------------------ DRAWINGS.
_j
IF
3. HYDRONIC PIPING MAINS FROM THE BOILER TO
- -------
- --
- --- ------
-------
--------------------------
----- - -- -------------- THE MANIFOLDS ARE SHOWN ON M102 AND
M103.
............ ..........
.......
------------- ----------------------
4. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM
- - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
IS SHOWN ON M303.
---------------------
-----------------
KEY NOTES:
(D MANIFOLD FOR EXTERIOR RAMP (SNOW MELT)
(Z MANIFOLD FOR EXTERIOR SERVICE DRIVE
..............
(SNOW MELT)
A R—Z --A-21
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
0
:5
0
fn co
co
=) 0
0
cn 7;7
F—
0 <
LL Cn
0 U)
75;
U) ccoo
UJ
w
ui
co w
p
j
ui
��
um FLL
00
2: cn
0
2i
C14
0
C)
0
4w
00
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
�4
---- -- -------- -- -------- - --------- - --------- --
— -- --- ---------------- --- - -- ----------------- ----- -------------------- -- ------
El
- - ----- - ------------------------------------- -
- ----- DESIGNED
------------------
- ------------
CSUSA NW EE
F` f
CHECKED
CSUSA NW / SAL
DATE
08/11/2017
JOB NUMBER
1 117036
-------------
- -------------------
SHEET TITLE
----------------- ----- - - -------------------------
RADIANT PIPING
LAYOUT - NORTH
N s
SHEET NUMBER
KEY PLAN M 300
z
7i
RADIANT PIPING LAYOUT - SOUTH
4 5 3
r 4 B
------ ---- ----------------------
---- -----------------
---- ----------------- E
------ --- ---------------------- �`
-----------------
GENERAL NOTES:
1. RADIANT ZONE OUTLINES ARE SHOWN ON
M102AND M103.
2. THIS SHEET SHOWS THE SUB SLAB RADIANT
PIPING AS IT WILL LAY OUT IN THE SPACE
FROM THE MANIFOLDS, DETAILS OF THE
INSTALLATION SHALL BE PROVIDED IN SHOP
DRAWINGS.
3. HYDRONIC PIPING MAINS FROM THE BOILER TO
THE MANIFOLDS ARE SHOWN ON M102 AND
M103.
4. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM
IS SHOWN ON M303.
o�
�
o
0
�.o
MENc�
--
o
0
KEY PLAN
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
0
2W-C
CN
C)
00
Q<
�
r 'S
0 C6
m n
C:) 7'
c) 0
co
IT-
C,q
LLJ
0
Lu
U)
U-1
m 3:
co 00
-C-,,Jj -r
�—
cy)
-�t
00 Of
=) 0
0—
�C-4
0 <
C)f 0 (14
LL C0
2: CP
E M
2 =)
0U)
U) 0000
ujQ
Lu
Lu
6i 1_
CQ
U) U)
Lu U)
p0
= Ld
��
IL
oo
2:
0
LL
C\l
0
CD
0
00
SIGNED: 8/11/2017
REVISIONS
0. ISSUE FOR PERMIT
DESIGNED
CSUSA NW / EE
8/11/2017
CHECKED
CSUSA NW / SAL
08/11/2017
JOB NUMBER
117036
SHEET TITLE
RADIANT PIPING
LAYOUT - SOUTH
SHEET NUMBER
[K I
ills
SCALE: 1/8" = l'-O"
Lea%
(
�.r----------------
GENERAL NOTES:
1. RADIANT ZONE OUTLINE FOR THE EXTERIOR
RAMP IS SHOWN ON SHEET M304 AND THE
MANIFOLD SUPPORTING IT IS SHOWN ON
SHEET M102.
2. RADIANT ZONE OUTLINE FOR THE EXTERIOR
SERVICE ENTRY/EXIT IS SHOWN ON SHEET
C-1.1 AND THE MANIFOLD SUPPORTING IT IS
SHOWN ON SHEET M102.
3. THIS SHEET SHOWS THE SUB SLAB RADIANT
PIPING AS IT WILL LAY OUT IN THE SPACE
FROM THE MANIFOLDS, DETAILS OF THE
INSTALLATION SHALL BE PROVIDED IN SHOP
DRAWINGS.
4. HYDRONIC PIPING MAINS FROM THE BOILER TO
THE MANIFOLDS ARE SHOWN ON M102 AND
M 103.
5. SCHEMATIC DESIGN OF THE HYDRONIC SYSTEM
IS SHOWN ON M303.
A
1
N
7 1
A
S
H
H
1
7 1
KEY PLAN
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
•
•
0
z.,
N
00
Q�
0 Uj
= n
O z
O p
M
IT-
N o
W
O
o
�
w
U)
W
m
co co
N =
~
Oo
d
00
Q z
� O
Y
N
O Q
O N
LL Co
F
2 =)
0
0000
W Q
W
75;
Lu
W 1—
ui U)
p
��
oo
zm
o
QLL
�0
o
co
e
SIGNED: 8/11 /2017
REVISIONS
0. ISSUE FOR PERMIT
DESIGNED
CSUSA NW / EE
8/11/2017
CHECKED
CSUSA NW / SAL
08/11 /2017
JOB NUMBER
117036
SHEET TITLE
RADIANT PIPING
LAYOUT -
EXTERIOR
SHEET NUMBER
3" (88.75 GPM)
2" (49.13 GPM)
2" (39.62 GPM)
I
Y Y
I
B-1 I B-2
399 MBH I 399 MBH
J LJ
C o ■ :
I=
P-2 vFD
-1-
W
HX-1
W
CO-GEN----------------------I
BASIS OF DESIGN:
1. BOILERS TO BE STAGED NATURAL GAS COMBUSTION IN COMPLIANCE WITH WSEC C403.2.4.8.
2. DUAL BOILERS TO BE STAGED PER LOAD REQUIREMENTS AND OPERATE LEAD LAG WITH TURN DOWN CAPABILITY.
3. SNOW MELT SYSTEM SHALL BE DISABLED WHEN OUTSIDE AIR TEMPERATURE IS GREATER THAN 49 F.
4. INDOOR DESIGN TEMPERATURE IN SERVICE AREA = 65'F.
5. FLOOR TEMPERATURE RANGE = 74-75°F, NOT TO EXCEED 80°F.
6. FLOOR SURFACE IS SLAB ON GRADE WITH NO COVERING.
MAIN PIPING LOOP FROM BOILERS TO MANIFOLDS TO BE SCH 10 STEEL.
7. RADIANT PIPING FROM MANIFOLD TO BE I" REHAU RAUPEX O2 BARRIER PIPE.
8. SYSTEM TO CONTAIN PROPYLENE GLYCOL AS REQUIRED FOR PROTECTION OF PIPE IN SNOW MELT APPLICATIONS.
9. RADIANT SUPPLY TEMPERATURE CALCULATED TO BE 100°F.
10. RADIANT SUPPLY/RETURN TEMPERATURE DIFFERENTIAL TO BE 20°F.
11. MANIFOLD FLOW BE REGULATED BY CONTROL VALVE WITH FEEDBACK FROM SLAB SENSOR.
12. SERVICE AREA CALCULATION IS 12 BTUH/SQUARE FOOT.
13. SNOW MELT APPLICATION IS 17.6 BUTH/SQUARE FOOT.
14. PIPE SPACING BASED ON 10".
15. BOILERS TO BE NATURAL GAS AND BACKUP TO A CO-GEN SYSTEM UTILIZING WASTE HEAT.
16. MAIN PUMPS TO BE ON VFD'S CONTROLLED BY DIFFERENTIAL PRESSURE.
i���iP►I�111�I��1��il�l[�I�I\��I�J��I7I►[eIiP►i[i��1>��'������������I���I:ZiI:ZiI►��1�/1��:[�I��I:7\'�91►[e��
SNOW MELT LOOP
[I�IZ1Z11 6141
" (39.62 GPM) /-2" (34.04 GPM)
" (28.70 GPM)
1j" (19.43 GPM)
---------I----<---2 I �---------T--------q I � ---------T-----------�
9 UNDER SLAB CIRCUITS 9 UNDER SLAB CIRCUITS
1i" (13.85 GPM)
TO SLAB
SENSOR
I
I
I
I
r-- - - - - - - I
r
5.58 GPM i i 8.27 GPM
T I I I
SERVICE ENTRY
SNOW MELT
TO SLAB
SENSOR
I�
I
RZ-C /� T
4.43 GPM RZ-D1 3.84 GPM RZ-D2
'I
i
10 UNDER SLAB CIRCUITS
8 UNDER SLAB CIRCUITS 9 UNDER SLAB CIRCUITS
- - - - - - - - - - - -------->--------J
I
L--
T
I
TO SLAB
SENSOR
I
tGPM
5
T
10 UNDER SLAB CIRCUITS
1" (5.58 GPM)
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS A
COPYRIGHTED WORK OWNED BY
COMFORT SYSTEMS USA
(NORTHWEST), INC. ("COMFORT
SYSTEMS NORTHWEST") AND
COMFORT SYSTEMS NORTHWEST
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
COPYING, PUBLICATION OR USE
OF THIS LAYOUT/DESIGN AND TO
OBTAIN DAMAGES THEREFORE.
0
cn
W
U) o
00
Q 0
U' N
Q Z r
W < G
W N
v � �
r H
00
77 N
0
ti
00
SIGNED: 8/11 /2017
0
0
H
U)
W
m 3:
j=
N H
00 O�
::) 0
O Q
LL (n
0 U)
U 2
Lu U)
w H
U ry
O
LL
'S 7-5
0
0
REVISIONS
0. ISSUE FOR PERMIT 8/11/2017
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
DATE
08/11 /2017
tOB A11:111BER
i •
SHEET NUMBER
., ,IM MWN MMINOWMAINKORWAAMOMI
SCALE: NTS
10' MIN FROM ANY EA
INSULATED REFRIGERANT PIPING TO/FROM
COPYRIGHT NOTICE
FRESH AIR INTAKES
OUTDOOR CONDENSING UNIT
THIS LAYOUT/DESIGN IS A
COORDINATE WITH
COPYRIGHTED WORK OWNED BY
ROOF PLANS
COMFORT SYSTEMS USA
OUTDOOR UNIT
(NORTHWEST), INC. ("COMFORT
TOP - - ---------
CEILING
FINISHED LI M MANUFACTURER'S WALL
CU-x (SEE SCHEDULE)
SYSTEMS NORTHWEST") AND
RETURN AIRFLOW MOUNTING PLATE
INSULATED REFRIGERANT
PIPING TO/FROM INDOOR
COMFORT SYSTEMS NORTHWEST
DUCTLESS WALL UNIT
BOLTED STEEL
FAN COIL (AH) UNIT
HEREBY RESERVES ITS RIGHT TO
PREVENT UNAUTHORIZED
FASTEN MOUNTING PLATE
MOUNTING BRACKETS
COPYING, PUBLICATION OR USE
o TO WALL PER MANUFACTURER'S
OF THIS LAYOUT/DESIGN AND TO
DOWNBLAST CENTRIFUGAL
SUPPLY AIRFLOW_.. -__`INSTALLATION INSTRUCTIONS
OBTAIN DAMAGES THEREFORE.
EXHAUST VENTILATOR, ALUMINUM
AIRFLOW
ROOF MOUNTED, DIRECT DRIVE
INDOOR FAN COIL UNIT
92#
ELECTRONICALLY COMMUTATED
= WOOD, METAL STUD OR
u-
0 LL CMU WALL, SEE ARCH PLANS
VARI-FLOW MOTOR
:�i <
0 FOR SPECIFIC WALL TYPE.
EQUIPMENT RAILS
LOW LEAK CLASS 1A RATED
co
0 +
ANCHOR BOLT TO
CONC SLAB AT GRADE
FASTEN DUCT TO CURB tEA EA MOTORIZED DAMPER IN TRAY
'' INSULATION, 3# DENSITY
ROOF CURB FLASHING00
ROOF CURB, 18 GA GALV STEEL
FLOOR LINE
CO
C)
FINISHED ROOF
ROOF PER 12- SLOPE)
(11
f
NOTES:
NOTES:
1. SEE EQUIPMENT SCHEDULE
FOR AH-3/HP-3
MFG SYSTEM MODEL NUMBERS, POWER
EXH DUI
1. AH-3/HP-3 SYSTEM SERVES ELEVATOR EQUIPMENT ROOM COOLING/HEATING LOADS ON
REQUIREMENTS AND INCLUDED
CONTROLS AND
ACCESSORIES.
FIRST FLOOR PER ARCH PLANS AND ELEVATOR SUBMITTALS.
0
2. SEE EQUIPMENT SCHEDULE FOR AH-3/HP-3 MFG SYSTEM MODEL NUMBERS, POWER
= p
NOTES:
REQUIREMENTS AND INCLUDED CONTROLS AND ACCESSORIES.
p 77
1. SEE EXHAUST FAN SCHEDULE FOR MFG MODEL NUMBERS AND INCLUDED CURB
3. INDOOR UNIT AH-3 IS POWERED FROM OUTDOOR UNIT HP-3.
O 0
ACCESSORIES. FAN AND CURB BY SAME MANUFACTURER.
N75;
'Q �'
EXH FAN DETAIL EF-1, 2
K4WALL FAN COIL UNIT DETAIL AH-3
KTN
CONDENSING
UNIT DETAIL
SCALE: NONE
M4.1 SCALE: NONE
NMl- ji
SCALE: NONE
SYSTEM POWER SUPPLY
208-230V/60HZ/1PH
10' MIN FROM ANY
OSA INTAKE
CD 0 0
V,
FRESH AIR INTAKES
Lu W
OUTDOOR HIP UNIT
COORDINATE WITH
uj
CARRIER 38MAQB09R--3
PLUMBING PLANS
W 00
HP-3 (0.75T) HP-x
> 00 ry
< z 0
0 U)
PACKAGED ROOFTOP UNIT (RTU)
C-4 0 <
o N u- w
M 0 cQ
co
C
ui
ui 3: co cn
ry
EXTERIOR
/D
Lu U)
cn ui ry
p
LAG BOLTS, SEE
4)
- - -------------------------------- -
STRUCTURAL FOR SIZES
RTU, AHU OR ROOF
- ry 0
0 m u-
75;
INTERIOR
AND SPACING
INTAKE HOOD
C\j 0
CD
INSULATED REFER TUBING
INDOOR UNIT POWERED
FLASHING
L
0
FROM OUTDOOR UNIT.
LINE VOLTAGE BY ELEC CONTRACTOR
- - R�l INSULATED ROOF CURB, BY MC.
TYPICAL PLUMBING
VENT
>0
0
FACTORY RTU CURB = ROOF CURB AND RTU BY SAME MANUFACTURER
ROOFING (BY GC)
FINISHED ROOF
A.
AH-x
W F. A
DUCTLESS WALL UNIT AH-x
- - --------------------------------------------------------------------------------
---
---------------------------------------------------------------------------------------
E-q c,
........... .......... j,
NOTES:
ILACD-1
1. SEE EQUIPMENT SCHEDULE FOR AH-x/CU-x MFG SYSTEM MODEL NUMBERS, POWER
REQUIREMENTS AND INCLUDED CONTROLS AND ACCESSORIES.
NOTES:
38898
GIST
1. SEE RTU SCHEDULES FOR MFG MODEL NUMBERS AND INCLUDED CURB ACCESSORIES. FAN
SIGNAL
AND CURB BY SAME MANUFACTURER (14- ROOF CURB OPTION).
SIGNED: 8/11/2017
HEAT PUMP SYSTEM SCHEMATIC HP-3
K'6-'ROOFTOP UNIT MOUNTING DETAIL
K'lo'
OUTSIDE
AIR INTAKE DETAIL
SCALE: NONE
M4.1 SCALE: NONE
M4.1
SCALE: NONE
REVISIONS
0. ISSUE FOR PERMIT 8/11/20171
MIN 1-1/2" WIDE
HANGER BAND
DESIGNED
CSUSA NW / EE
CHECKED
CSUSA NW / SAL
FLEX DUCT
DATE
MIN RADIUS IS
1 X DIAMETER CLAMP
08/11/2017
ATTACH W/METAL CLIPS
OR SCREWS
JOB NUMBER
---------------------------------------------------------------------------
117036
SHEET TITLE
CEILING
MECHANICAL
DIFFUSER
DETAILS
SHEET NUMBER
M400
K'9-'CEILING DIFFUSER DETAIL
M4.1 SCALE: NONE