05-355 Regal Homes SfR.doc
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 30, 2005
TO: Regal Homes
Fax (425)290-9941
FROM: Jenny Readwin, Plans Examiner
RE: Plan Check # 05-355
Project: Regal Homes SFR
th
Project Address: 22808 96 Pl W.
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed.
1)Show size and location of foundation vents on the foundation plan.
2)An additional smoke detector is required on the main floor. Note on plans.
3)Provide a letter from the Geotechnical Engineer of record stating that they’ve reviewed the final
construction plans and they are consistent with their report recommendations.
4)Special inspections are required for the following. Complete the enclosed special inspection
agreement signed by the owner, the general contractor and the special inspector and submit to
the City for approval prior to issuance.
Soil bearing verification
Proof rolling
Placement of fill and compaction
General site monitoring by Geotechnical Engineer of Record
Final report from Geotechnical Engineer of Record
5)See attached structural comments from city consultant. Respond to each item in writing.
Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a
written response to each of the above items to a Permit Coordinator.