06-095 McCormick 635 Paradise 2.doc MEMORANDUM Date:June 15, 2006 Senior Permit Coordinator Marie Harrison To: From:Fire Marshal John J. Westfall 425.771.0213 Subject:PC06-095 Multi-use Office & Storage 635 Paradise Ln SECOND REVIEW The following project has been evaluated under the 2003 International Codes. 1. Show storage building and storage rack elevations. Pre-application roof height was approx. 12’. Current buildng exterior elevation is 23’ at ridge. High-piled combustible is defined where the top of storage is 12’ or greater. Show usable storage heights for each storage area. 2. Per Building comments and pre-application comment #5 provide shelving/floor plan with written description of storage items including MSDSs and group classifications of storage commodities. Also: a. Call out location and storage commodity classifications (IFC Section 2303 and NFPA 231C). b. Will public access storage building? c. Call out whether shelving is solid or slatted. If slatted callout specifications. d. How many tiers on shelving? e. Call out maximum pile volume for each storage array. f. Location of commodities that are banded or encapsulated. g. Dimension and location of transverse and longitudinal flue spaces. 3. I require the preceding information so I may continue fire review. Previous comments dtd 5/5/06 were not addressed, I am resending. Information and evaluation of #1 and #2 are important to establish the nature of the fire protection requirement for this project. 4. Sht A-1 General Note #12 add “…Additional fire extinguishers may be required for special hazard areas.” I will better comment to fire protection footprint following your responses here. City of Edmonds Fire Marshal  