06-175 Murphy-Duncan SFR.doc City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: May 25, 2006 TO: Bob Murphy rcm@murphybuilding.com FROM: Jenny Readwin, Plans Examiner RE: Plan Check # 06-175 Project: Murphy-Duncan SFR th Project Address: 19310 84 Ave W. During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator. 1)Show how island sink will be vented through the roof or with a loop vent as permitted by UPC 909.0.Air admittance valves are not permitted unless first approved by the Building Official under and alternate method per UPC 301.2. 2)Specify on the elevation views the grade slope away from the building. If minimum 6” within 10’ is not possible or habitable or useable space is below grade, foundation drainage is required. Provide footing drain detail on foundation sections complying with R405.1 and show required drain locations on the foundation plan. 3)Provide calculations to justify post size and footing at the intersection of B3, B4 and B5. 4)Revise calculations for B8 (4x10 at living room) to reflect span shown on the plans (11’ plans and 8’ in calculations). 5)Provide calculation to justify post size and footing between B11 and B12. 6)Provide calculations to justify that a single bolt is required for detail 1/L1. 7)R403.1.3 requires vertical rebar to have standard hook. Revise details on sheet G-1 to reflect. 8)Specify where detail 1/A-7 occurs and provide calculations. If this does not apply to this application cross off or remove from plans.