Loading...
07-0260 & 261 Plan Review Comments1.doc CE ITY OF DMONDS th • 1215 AN•E,WA98020 VENUE ORTH DMONDS P: 425.771.0220 • F: 425.771.0221 • W: www.ci.edmonds.wa.us HONEAXEB DSD: P•E•B EVELOPMENT ERVICES EPARTMENTLANNING NGINEERING UILDING April 2, 2007 Gasline Mechanical Inc. Kelly Crawford E-mail: kelly_gasline@hotmail.com PLAN CHECK # 2007-0260 & 2007-0261 RE: PLAN REVIEW COMMENTS FOR MECHANICAL EQUIPMENT AT POINT EDWARDS BUILDINGS 6 & 7 Dear Kelly, I have reviewed the above building permit applications for the Planning Division. The following information is needed to approve the application: Elevation View. 1. The elevation view for Building 6 shows the parapet at the elevation of 145.33’. However, the approved plans for the building show the parapet at the elevation of 149. Please clarify. Was the building actually constructed lower than originally planned? Screening for RTU-309/Building 7 2. . The rooftop plans indicate that RTU-309 will be located approximately 5 feet from the outer edge of the building. It appears that it will extend approximately 3 feet above the parapet on the east side of the building. This should not be a problem, but please provide a detail of what the actual screening will look like. Please make all submittals to a Development Services Permit Coordinator (Marie Harrison), Monday through Friday, 9:00 am to noon or 1:00 pm to 4:00 pm. Please submit two copies of the revised plans. If you have any questions, feel free to contact me at (425) 771-0220 ext 1330. I am in the office Mondays, Wednesdays, and until noon on Fridays. I look forward to working with you on this project. Sincerely, Development Services Department - Planning Division Kathleen Taylor, Associate Planner