Plan Review Corrections
Plan Check : Date:
# 2007-0471 August 22, 2007
nd
Project Name/Address:
Marques/505 2 Ave N
Contact Person/Address/Fax:
Ken Marques/PO Box 711 Manson, Wa 98831/Phone: 509-607-3736/e-mail:
ksmpa1@aol.com
Reviewer: Jaime HawkinsDivision:Engineering
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed:
6/4/2007 -
1. Show the minimum Temporary Erosion and Sediment Control in the site plan. Please refer to
City of Edmonds standard detail E1.1, and E1.2 You may find this detail by visiting the City of
www.ci.edmonds.wa.us
Edmonds web site at and clicking on City Government-Development Services-
Engineering Division and scroll down to handouts and forms. 8/22/2007 Please show the required
erosion control as previously requested. A minimum of a Filter Fabric Fence shall be installed along the
affected areas of the north, west and south property lines.
2.Is there a detention system in the property? Please show if one exists. If one does not exists, what are the
downspouts currently connected to?
6/4/2007 -
3.Provide grading calculations and quantity. 8/22/2007 Please show/provide your grading
calculation and quantities. Your calculation shall include the proposed addition, garage, and driveway
grading. I have calculated the grading quantities to be a minimum of 90-cu-yds
6/4/2007 -
4.Please revise the impervious surface calculation. The sum of the proposed impervious surface
is over two thousand square feet. All new impervious surface over two thousand square feet shall be
detained. Please refer to the City of Edmonds Engineering handout #E72. 8/22/2007 Please
provide/show either the existing or proposed detention system. Storm water quality control is required
on all new or redevelopment with more than 2,000 square feet of new impervious surface area. The
addition you are proposing exceeds 2,000 square feet.
Please resubmit 3 copies of the revised plans/documents to a Development Services Coordinator. Please
contact me at 425-771-0220 if you have specific questions regarding these plan corrections.
DATE FAXED/E-MAILED 8/22/2007 PAGE __1__ OF __1_