Plan Review Corrections
Plan Check : Date:
# 2007-0699 August 22, 2007
Project Name/Address:
Knutson/18720 Sound View Pl
th
Contact Person/Address/Fax:
Joe Molina/21911 76 Ave W, Ste: 210 Edmonds, WA 98026/Phone: 425-778-
1530/fax: 425-774-7803/e-mial: jmolina@tgbarchitects.com
Reviewer: Jaime HawkinsDivision:Engineering
During review of the subject submittal, it was found that the following information, corrections, or
clarifications would need to be addressed:
1.Show the minimum Temporary Erosion and Sediment Control in the site plan. Please refer to City of
Edmonds standard detail E1.1, and E1.2 You may find this detail by visiting the City of Edmonds web
www.ci.edmonds.wa.us
site at and clicking on City Government-Development Services-Engineering
Division and scroll down to handouts and forms. Please extend the proposed Filter Fabric Fence
eastward along the north and south property lines. Show the required Construction Entrance.
2.Please show the water service line from the meter to the house. If poly is used for the water service line
then, a 12-gauge tracer wire shall be taped to the line every 10-ft and it shall be grounded at the meter
and the house.
3.Provide grading calculations and quantity. If your grading is greater than 500-cyd please contact the
Planning Division for SEPA determination.
4.The existing sewer lateral is 4-in and in bad condition. Please show the new 6-in sewer lateral from the
sewer main to the easement line and provide a 6-in sanitary sewer clean out at the easement line. Install
per E6.4
5.Please show a 4-in sidesewer from the easement line to the house. Provide a 4-in cleanout 2-ft from the
building. Install per E6.2
6.Please provide a cross section of the proposed driveway.
7.Please provide a Drainage Plan. The proposed impervious surface exceeds 5,000 sq-ft; therefore, the
system must be designed and stamped by a licensed Engineer. See handout #E72.
Please resubmit 3 copies of the revised plans/documents to a Development Services Coordinator. Please
contact me at 425-771-0220 if you have specific questions regarding these plan corrections.