Loading...
07-1216 Plan Review Comments - Updated Review.pdf CE ITY OF DMONDS th • 1215 AN•E,WA98020 VENUEORTHDMONDS P: 425.771.0220 • F: 425.771.0221 • W:www.ci.edmonds.wa.us HONEAXEB DSD: P•E•B EVELOPMENT ERVICES EPARTMENTLANNINGNGINEERING UILDING December 23, 2008 Mr. Mike Johnson Email: mjhnsnwy@hotmail.com RE:REVISED PLAN REVIEW COMMENTS FOR PLAN CHECK # 2007-1216 SAFFOLD NEW RESIDENCE AT 8008 TALBOT ROAD Dear Mr. Johnson: In response to recent correspondence between the property owner and City staff regarding the proposed residence, I am revising the plan review comments I sent you on January 30, 2008. The following will need to be addressed before review by the Planning Division can continue: Site Plan: 1.It was noted that the upper floor projects over the main floor by approximately one foot on the northwestern side of the house. It is unclear if this is shown on the site plan. Therefore, Please show and label the outline of the portion of the upper floor that projects over the main floor on all copies of the site plan. Datum Point: 2.Please show and label the datum point used for your height calculations on all copies of your site plan. Height Calculations: 3.Per ECDC 21.40.030.B, the height rectangle used for your height calculations shall be the smallest rectangle that will enclose all of the building, excluding a maximum of 30 inches of eaves. It appears that the height rectangle used for your height calculations included some of the eaves. Additionally, it is unclear of the height rectangle includes the portion of the upper floor that cantilevers over the main floor on the northwestern side of the house. Therefore, please update your height rectangle to include the outermost walls of the residence, but exclude up to 30 inches of eaves. Additionally, please update the elevations of the four corners of the height rectangle, and update the height calculations shown on the site plan and building elevations accordingly. Fence: 4.Your site plan shows a 6’ cedar fence. Please label this fence as existing or proposed. SEPA Review: 5.The Engineering Division’s review of your proposal estimated the grading to be 490 cubic yards. Note that if grading exceeds 500 cubic yards, SEPA review will be required. Please contact the Planning Division for SEPA review procedures if you find that you will be exceeding 500 cubic yards of grading. “Future Wet Bar”: 6.Sheet A4 of your building plans indicate a “future wet bar” within the proposed recreation room. Do you plan to stub the plumbing to this area with the subject application? If so, please indicate this on your plans. If not, please remove the “future wet bar” from your plans since it is not a part of this application. Please note that a separate building permit will be necessary if you plan to add the wet bar in the future. Additionally, an Accessory Dwelling Unit (ADU) covenant may be required when you propose to add the wet bar to ensure that the lower floor will not be used as an ADU without the appropriate land use approvals. Please make all submittals to a Development Services Permit Coordinator, Monday through Friday between 8:00 am and 4:30 pm. If you have any questions, feel free to contact me at (425) 771-0220, ext. 1224. Sincerely, Development Services Department - Planning Division Jen Machuga, Planner