074219.001-1 Insulated Metal Panel Backup Wall Assemblies REVISED_NBBJ-PAAN.pdfCONTRACTOR SUBMITTAL ISSUE TO NBBJ
DATE ISSUED Apr 30, 2015
COMPANY NBBJ
223 Yale Avenue North
Seattle, WA 98109
PHONE / FAX (206) 223-5555
PROJECT NUMBER 100822.06
PROJECT NAME SMC Edmonds ACC
ATTENTION: Barb Gipple
NBBJ Submittal
Number 169-074219-1
GC Submittal
Number 169-074219001-1
SPEC. PARAGRAPH:
SPEC. DESCRIPTION:Insulated Metal Panel Backup
Wall Assemblies
SPECIFIC ITEM:Insulated Metal Panel Backup
Wall Assemblies
CONTRACTOR ISSUED
ON:Apr 30, 2015
DATE REQUESTED
BACK:May 15, 2015
DATE RECEIVED @
NBBJ:May 1, 2015
DATE DUE BACK TO
CONTRACTOR:May 14, 2015
DATE RETURNED BY
NBBJ:
ITEMS TRANSMITTED
SENT VIA
REVIEW ACTION Partially approved as noted
REVIEW NOTE
COPIES
GC REMARKS
NBBJ COMPOSITE RESPONSE
Entered By: Andris Lapins
Entered Date: Wednesday, May 13, 2015 7:43 AM
Approved as noted per attached comments. Please provide the following:
Confirmation letter from the manufacturer stating that the installers deviations from recommended details are acceptable
and will not adversely affect system performance or warranty.
PLEASE NOTE: Previously reviewed information not reviewed with this submittal.
ISSUED BY Joe Eagle
PHONE / FAX: (206) 682-7770
CONSULTANTS REPRESENTED
Page 1 of 2
5/13/2015https://secure1.nbbj.com/CATools/Data/SubForm.aspx?SubmittalID=130456&Msg=save
05/13/15
EMAIL: JOE.EAGLE@SELLEN.COM
COPY TO: Dan Schnebele
Mark Bucek
Scott Solberg
NBBJ Amy Frerker
NBBJ Andris Lapins
NBBJ Michael Howatt
ELECTRONIC ATTACHMENTS
Page 2 of 2
5/13/2015https://secure1.nbbj.com/CATools/Data/SubForm.aspx?SubmittalID=130456&Msg=save
SUBMITTAL FOR APPROVAL
7039. - SWEDISH/EDMONDS-AMBULATORY CARE
CENTER
1 | Page
Submittal #: 169 -074219.001
Rev#: 1
Priority: HOT
Date: 04/30/2015
To: MICHAEL HOWATT From: JOE EAGLE
NBBJ SELLEN CONSTRUCTION CO., INC.
223 Yale Ave 227 WESTLAKE AVE N
Seattle, 98109 SEATTLE, WA 98109
Originator: NORTHSHORE SHEET METAL INC
Description: Insulated Metal Panel Backup Wall Assemblies
We are transmitting the following Submittal Package item(s) for your review in accordance with the
contract specifications.
Please review and respond to: JOE EAGLE, by: 5/15/2015.
Additional Notes:
Item Number Spec Section Description Details Notes
169.002. 074219 Insulated Metal Panel Backup
Wall Assebmlies
Product Data, Shop
Drawings, Coursing Layout,
Performance Data, Panel to
Panel joint detail,
cc:
REVIEWED
WITH CORRECTIONS NOTED. THIS REVIEW DOES
NOT RELIEVE THE SUBCONTRACTOR OR MATERIAL
SUPPLIER FROM RESPONSIBILITY FOR ERRORS OR
DEVIATIONS FROM DRAWINGS & SPECIFICATIONS.
SELLEN CONSTRUCTION CO.
GENERAL CONTRACTOR
Submittal: 074219001-1 Insulated Metal Panel Bac
By: joee Date: 04/30/2015
KarrierPanel™
Insulated Roof
& Wall Panels
Universal Barrier
Wall Solution
074219 Insulated Metal
Wall Panels
KarrierPanel™
2
Is a cost effective universal barrier wall alternative solution to
traditional multi-component wall systems. Comprising of a KS Series
panel and integrated rail, KarrierPanel™is the ideal barrier wall to
support secondary rainscreens systems such as metal or brick
façades.
KarrierPanel™is suitable for all building types in any climate, and
combines the thermal benefits of lightweight insulated metal panels
with the aesthetics of multiple façades.
KarrierPanel™offers a simple more time efficient alternative to
traditional multi-part façades, allowing the structure to be quickly
insulated to ensure air and watertightness as soon as possible. Once
installed the system provides 100% building envelope performance.
For more information or to request a sample, email
karrier@kingspanpanels.com.
To view an animation of the
KarrierPanel™ wall system, visit our
YouTube Channel, Kingspan TV.
Contents
3
KarrierPanel™Product Details 4
Design Flexibility 5
Build Speed 6
Thermal Performance 7
Sustainability 8
Testing and Approvals 10
Kingspan Service and Support 11
KarrierPanel™Projects 12
Construction Details 14
4
KarrierPanel™
Product Details
Product Specification
Cover Widths: 24” 30” 36” 42” (Standard)
Panel Thickness: 2” 2
1/2” 3” 4” 5” 6”
R-value: 7.5 per inch
Panel Lengths: 6’-0” to 52’-0”
Panel Joint: Double tongue and groove interlocking
rainscreen joint
Reveal Choice:3/8 reveal
Exterior Face: 26, 24 or 22 Ga. Shadowline profiled
embossed Galvalume®pre-painted steel
Interior Face: 26, 24 or 22 Ga. Shadowline profiled
embossed Galvalume®pre-painted steel
Application: Vertical and horizontal
Rail: Custom Kingspan KarrierRail
™
5
Design Flexibility
KarrierPanel™
can support a
range of
rainscreen
finishes to
compliment any
architectural
scheme.
Unique KarrierRail™
KarrierPanel™utilizes a Kingspan designed unique rail. This stable and
secure structural rail safely transmits positive loads from the multiple
façades to the structural supports behind the insulated panels.
Similarly, expansion fasteners (fab-loks) secure the exposed rail edge,
ensuring that the system safely handles negative loads as well.
The rail has been developed to fully integrate with Kingspan’s KS series
panel joint. This rail system does not penetrate the air vapor barrier and
enables multiple types of rain screens to be attached to the
KarrierPanel™rail such as brick, single skin metal, and various other
systems.
Brick Rainscreen
on KarrierPanel™
Metal Rainscreen
on KarrierPanel™
Installation is quick, simple
and easy, as the rail is
installed during normal panel
installation, and is secured
using standard panel
fasteners in a one step
procedure.
The standard rail configuration is 16 gauge Galvalume®,
50 KSI steel. Available in various lengths with a 1, 2 and
3 inch bearing surface.
Build Speed
6
Build Speed
KarrierPanel™as a single component system increases speed
of build, minimizes delays and the need for multiple trades.
Typical multi-part façade system KarrierPanel
™System
with Metal Single
Element Rainscreen
Single
Component
KarrierPanel™
Wall System
Vs
1
■Faster close-in and dry-in for reduced building costs.
■The single component system results in less labor time on-site and construction waste.
■Reduces delays in construction experienced with scheduling multiple trades.
■Increase in build speed allows faster project completion and reduces business disruption.
Thermal Performance
7
Vs
The insulated panel provides excellent thermal performance with high R-value and airtightness with an air,
water and vapor barrier.
Benefits of the KarrierPanel™Wall System Vs
Traditional Built-up Construction:
■The single component KarrierPanel™wall system combines the
superior thermal performance of IMPs with an air, water and vapor
barrier.
■More uniform temperature distribution throughout the wall ensures
moisture control.
■Eliminates energy losses associated with thermal-bridging cavity
insulation.
■Eliminates concerns over UV exposure as compared to
conventional rainscreen components.
■Eliminates the potential for compromising the Air, Vapor Barrier
(AVB) and allows for visual inspection and testing of the AVB.
■Results in quicker ROI.
Kingspan
KarrierPanel™Wall System
Direction of heat flowSteel-framed,
Built-up Wall System
Direction of heat flow
8
Path to NetZero™
Kingspan’s long-term mission will see all our facilities achieve
NetZero energy consumption by 2020. NetZero Energy buildings,
in the simplest terms, produce as much energy as they consume.
Our insulated metal panels are a cost effective step to this high
performance goal, offering a building envelope with functionality
and design possibility.
Our Path to NetZero™app is a unique tool for the building industry that
simulates the process of achieving high performance and NetZero energy
buildings. Results indicate estimated energy cost savings, CO2, ROI and
contributions to LEED®points gained by using Kingspan Insulated
Panels.
Building professionals and owners today share a newfound enthusiasm for building envelope performance.
Driving this focus are mandates for green building, a focus on energy efficiency and recognized ROI.
EnvelopeFirst™
Kingspan’s EnvelopeFirst™is a design strategy for optimizing a
building’s performance and the first step towards NetZero energy.
The EnvelopeFirst™approach to design focuses on enclosure
performance, including durability, airtightness, and better moisture
and thermal control.
Testing and field results show that insulated metal panels (IMPs)
contribute to ROI and energy efficiency.
Start with the…
LEED®Credits
Kingspan is committed to supporting green rating systems such as
LEED®and Green Globes. Specification of effective systems and
materials is key to achieving these certifications. With this in mind,
Kingspan provides a LEED®credits guide to assist the building team
on how IMPs contribute to overall building performance and ratings
criteria.
Visit www.kingspanpanels.us/sustainability/leedinformation to
download Kingspan’s LEED®statement for project submittals.
Sustainability
Energy &
Atmosphere
Materials &
Resources
Innovation
In Design
Indoor
Environmental
Quality
Sustainable
Sites
9
Goal of an EPD
An EPD’s goal is transparency. Knowing what’s in the product you
chose and its environmental impact. An important aspect of an EPD
is to provide the basis of a fair comparison of products and services
by its environmental performance. EPDs can reflect the continuous
environmental improvement of products and services over time and
are able to communicate and add up relevant environmental
information along a product’s supply chain.
UL Certified
To add credibility to our findings, we engaged UL Environment to verify
the results of our EPD. UL has been impartially assessing products
since 1894 for safety and viability and have conducted numerous
environmental evaluations. UL certified EPDs are based on ISO
compliant standards.
Our EPD indicates that raw materials are the dominant impact
across our products life cycle, therefore we are consciously working
with our suppliers to improve this.
This data confirms our company policy of utilizing more recycled
and less virgin resources whenever possible.
To learn about our sustainability
journey and download the EPD or
App, visit:
www.pathtonetzero.com
EPD (Environmental Product Declaration)
Kingspan Insulated Panels North America,
has been awarded the first of its
kind UL certified ISO compliant
Environmental Product Declaration
(EPD). The EPD describes environmental
manufacturing footprints from cradle to
grave based on an ISO compliant Life
Cycle Assessment (LCA).
What is an EPD
An EPD is a third party verified, internationally recognized disclosure
of a product’s environmental impact, from cradle to grave based on
an ISO compliant Life Cycle Assessment (LCA).
Kingspan’s LCA calculates the environmental footprint at each stage
of the supply chain, manufacturing processes, product use and
end of life. All the significant environmental impacts associated with
the product, including the impact on water, air, land and climate
change are reported based on ISO LCA standards.
Testing and Services
10
Performance Requirements and Product Listings:
Kingspan insulated panels meet specific building envelope performance criteria and requirements stipulated by US
and Canadian building codes. Panels are tested in accordance with UL, ULC, FM and ASTM approval standards,
testing methods and procedures. Kingspan insulated panels are listed by FM Global and Warnock Hersey.
Test Procedure Results
Fire FM-4880 Passed: Class 1 Fire Rating of Insulated Wall or Wall and Roof / Ceiling
Panels, Interior Finish Materials or Coatings, and Exterior Wall Systems
ASTM E84 Flame spread <25, smoke developed <450
CAN/ULC-S101 Fire endurance tests: 10 min and 15 min stayed in place
CAN/ULC-S102 Flame spread: 20, Smoke developed: 350 for panel with facings
CAN/ULC-S127 Flame spread <500 for foam core
CAN/ULC-S134 Passed: Standard method of test for fire of exterior wall assemblies
ULC/ORD-C376 Passed: Fire growth of foamed plastic insulated building panels
in a full scale room configuration
NFPA 259 Tested for potential heat of building materials
NFPA 268 Passed: Standard test method for determining ignitability of exterior wall
assemblies using a radiant heat energy source
NFPA 285 Passed: Standard Fire Test Method for Evaluation of Fire Propagation
Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing
Combustible Components.
Structural FM-4881 Passed: Class +110/-154 Zone H Class
+100/-140 Zone HM – LM
ASTM E72 Vacuum chamber tested. Panel load / span and deflection
tables are available
Thermal Performance ASTM C518 R-value per inch = 7.5 h
.ft2.°F/Btu.in
Air Infiltration ASTM E283 0.003 CFM/ft
2 of Panel Area at 6.24 psf
Water ASTM E331 No uncontrolled water penetration at 20 psf differential pressure
AAMA 501.1 Dynamic water pressure testing – no sign of water
leakage at 15 psf
Fatigue Tests Cyclic test to positive and negative The panels exceeded 2 million alternate cycles
wind loading to ± L/180 deflection without failure or damage
Bond Strength ASTM D1623 Panels tested for tensile bond strength of metal to foam
Sample placed in an autoclave device and pressurized to
2 PSI at 212 °F for 21/2 hours
No skin delamination with direct pull off pressure up to 1188 psf
The above tests were conducted on various Kingspan products, and not all products may comply with the tests shown. If you have any questions on a specific product and/or test, please ask a
representative of Kingspan Technical Services. Kingspan does not assure compliance with any plans or specifications and it remains the responsibility of the customer to confirm compliance of
the product with applicable local, state and national codes and other laws or regulations.
Kingspan Service
and Support
11
Sales Team
Our regionally based sales team can provide assistance
on any project from the design stage through to site
installation.
Find your local sales rep on our website.
Canada - www.kingspanpanels.ca/findasalesrep
USA - www.kingspanpanels.us/findasalesrep
Email us:
Technical and Energy Services:
technicalservice@kingspanpanels.com
Installation:
installation@kingspanpanels.com
Marketing:
marketingdept@kingspanpanels.com
Samples:
samplesdept@kingspanpanels.com
Follow Kingspan on:
Langley, BC
Modesto, CA
Caledon, ON
Columbus, OH
Deland, FL
Technical Service
Kingspan provides a comprehensive technical advisory service to
assist architects, engineers, specifiers and installation contractors
with building design, product application and site work installation
training and challenges.
Energy Service
Kingspan offers a performance energy modeling service on select
projects to help design teams understand scenarios contributing to
optimizing the energy efficiency of insulated metal panel assemblies
based on meeting or exceeding ASHRAE 90.1 requirements.
Customer Service
Our dedicated team provides focused customer service for all pre and
post-order administration, delivery scheduling, and installer support,
ensuring a seamless coordinated customer experience.
Marketing Support
Our marketing team aims to provide a fast turnaround on standard
sample and literature requests, eliminating delays with planning and
client approval of material, so that your project begins on time.
Additional marketing support is provided through the use of project
case studies.
Field Service Support
Kingspan’s Field Service Engineering Team offer customers free
contractor training on the installation of new and existing products,
site inspection services as well as advice on mechanical handling
solutions.
KarrierPanel™Projects
12
13
Construction Details KarrierPanel™with Metal
14
Base at Overhang – Horizontal IMP Vertical Rainscreen
Single skin panel (installed vertically)
Hat channel – as required
Set hat channel in butyl sealant
at fastener locations
Continuous butyl sealant
Continuous butyl sealant both sides of trim
1/4” – 14 hex head fasteners with washer
Base channel set in sealant (not by Kingspan)
Fastener to concrete (not by Kingspan)
Vertical supports (not by Kingspan)
Single skin panel base flashing
Construction Details KarrierPanel™with Metal
15
Intermediate Support – Horizontal IMP Vertical Rainscreen
1/4” – 14 hex head fasteners with washer
Single skin panel (installed vertically)
Continuous KarrierRail™(KarrierRail™
available in 1”, 2” & 3” faces)
Expansion fastener as required
Set KarrierRail™in butyl sealant at fastener locations
Vertical support at 16” O.C. (not by Kingspan)
1”
Continuous butyl sealant
Continuous butyl sealant (optional)
Male
joint
Wall panel
installation
direction
Female
joint
Construction Details KarrierPanel™with Metal
16
Parapet Detail – Horizontal IMP Vertical Rainscreen
FIP insulation – as required
Single skin panel parapet assembly Continuous butyl sealant
Fastener to parapet backer
(not by Kingspan)
Membrane roof and parapet
backer (not by Kingspan)
Parapet blocking (not by Kingspan)
Wrap membrane over panel face
(not by Kingspan)
Set hat channel in butyl sealant
at fastener locations
Single skin panel (installed vertically)
Hat channel – as required
1/4” – 14 hex head fasteners with washer
Construction Details KarrierPanel™with Metal
17
Base Detail - Vertical IMP Horizontal Rainscreen
Single skin panel (installed horizontally)
Expansion fastener – as required
1/4” – 14 hex head fasteners with washer
Continuous butyl sealant both sides of trim
with marriage bead to vertical panel joint
Set KarrierRail™in butyl sealant at fastener locations
Continuous KarrierRail™(KarrierRail™available in 1”, 2” & 3” faces)
Single skin panel continuous
starter / flashing
Single skin panel base flashing
Continuous butyl sealant
Base angle with min. 3” vert. leg for panel attachment
set in sealant (not by kingspan)
Construction Details KarrierPanel™with Metal
18
Intermediate Support – Vertical IMP Horizontal Rainscreen
1/4” – 14 hex head fasteners with washer Horizontal support (not by Kingspan)
Expansion fastener as required Continuous butyl sealant (optional)
Continuous KarrierRail™(KarrierRail™
available in 1”, 2” & 3” faces)
Single skin panel (installed horizontally)
Set KarrierRail™in butyl sealant at fastener locations Continuous butyl sealant
Wall panel
installation direction
1”
Male
joint
Female
joint
Construction Details KarrierPanel™with Metal
19
Low Eave Detail – Vertical IMP
Horizontal Rainscreen
Expansion fastener – as required
FIP insulation – as required
Refer to 900/1000 series roof panel
details for additional information
1/4” – 14 hex head fasteners
with washer
Continuous butyl sealant with marriage
bead to vertical panel joint
Eave strut (not by Kingspan)
Continuous KarrierRail™(KarrierRail™available in 1”, 2” & 3” faces)
Single skin panel (installed horizontally)
Construction Details KarrierPanel™with Brick
20
Base Detail – Horizontal IMP
1/4” – 14 through fasteners with 1
1/8” bonded washer (as required for wind load)
Vertical metal stud wall (not by Kingspan)
Face brick (not by Kingspan)
Brick
Air
gapStud wall
Panel
thickness
Set panel in continuous butyl sealant
Waterproofing membrane below grade (not by Kingspan)
Flexible membrane flashing (not by Kingspan)
Masonry drainage and venting (not by Kingspan)
Mortar net (not by Kingspan)
Brick tie – HB wing nut with pintle (spacing to be determined by the engineer of record)
Construction Details KarrierPanel™with Brick
21
Engaged Panel Detail – Horizontal IMP
1/4” – 14 hex head fasteners without washer
12 Ga. stainless steel hidden fastener clip (1 per panel,
per support) set clip in butyl sealant
Face brick (not by Kingspan)
Brick
Air
gap Stud wall
Panel
thickness
Continuous butyl sealant at interior panel joint
Continuous butyl sealant at exterior panel joint
Vertical metal stud (not by Kingspan)
Brick tie – HB wing nut with pintle (spacing to be
determined by the engineer of record)
Brick tie – HB wing nut with pintle (spacing to be
determined by the engineer of record)
Construction Details KarrierPanel™with Brick
22
Framed Opening – Horizontal IMP
1/4” – 14 pancake through fasteners
with 1 1/8” bonded washer
(as required for wind load)
Face brick (not by Kingspan)
Masonry drainage and venting
(not by Kingspan)
Shelf angle (not by Kingspan)
Metal flashing with drip edge
set in sealant (by mason)
Backer rod and sealant (not by Kingspan)
Window system (not by Kingspan)
Self-adhering vapor barrier at window
rough opening (not by Kingspan)
Mortar net (not by Kingspan)
Vertical metal stud wall
(not by kingspan)
Membrane termination bar, fasteners
and sealant (by mason)
Set panel in continuous butyl sealant
Self-adhering membrane with up turned
ends to form end dams (by mason)
Brick tie – HB wing nut with pintle
(spacing to be determined by the
engineer of record)
Construction Details KarrierPanel™with Brick
23
Framed Opening – Horizontal IMP
Face brick (not by Kingspan)
8” hollow concrete block (not by Kingspan)
Slip sheet to protect panels (not by Kingspan)
Set panel in continuous butyl sealant
Self-adhering vapor barrier (not by Kingspan)
Wrap roof membrane over panel face
(not by Kingspan)
Masonry fastener (as required for
wind load) (not by Kingspan)
Parapet cap and metal flashing cap,
sealant and weather tightness
(not by Kingspan)
Brick tie – HB wing nut with pintle to masonry
(spacing to be determined by the engineer of record)
06/2014
Kingspan USA Kingspan Canada
Deland, FL : 386-626-6789 Caledon, ON : 905-951-5600
Modesto, CA : 209-531-9091 Langley, BC : 604-607-1101
www.kingspanpanels.us www.kingspanpanels.ca
For the product offering in other markets please contact your local sales representative or visit www.kingspanpanels.com
Care has been taken to ensure that the contents of this publication are accurate, but Kingspan Limited and its subsidiary companies do not accept responsibility for errors or for
information that is found to be misleading. Suggestions for, or description of, the end use or application of products or methods of working are for information only and
Kingspan Limited and its subsidiaries accept no liability in respect thereof.
Follow Kingspan on:
REVISION: 04/26/13
Henry Company 999 N. Sepulveda, Ste 800, El Segundo CA 90245-2754
Technical Services- Phone (800) 486-1278 – Email: techservices@henry.com
www.henry.com
TECHNICAL DATA SHEET
Blueskin SA
Self-Adhesive Air/Vapor Barrier Membrane
Typical Physical Properties
-Color
-Thickness
-Application Temp
-Service Temp
-Elongation
(ASTM D412-modified)
-Tensile Strength
(Membrane)
(ASTM D412- modified)
-Tensile Strength (Film)
(ASTM D882)
-Minimum Puncture
Resistance – Membrane
(ASTM E154)
-Watertightness
(CAN/CGSB-37.58-M86)
-Nail Sealability
(ASTM D1970)
Blue
40 mils (1.0 mm)
41ºF minimum
Minus 40°F to 158°F
200% minimum
500 psi minimum
5000 psi minimum
40 lbf.
Pass
Pass
-Low Temperature Flexibility
@ -22°F (CGSB 37-GP-56M)
-Water Vapor Transmission
(ASTM E96 water method)
(ASTM E96 desiccant method)
-Lap Peel Strength @ 39°F
(ASTM D903 180° bend)
-Water Absorption
(ASTM D570)
-Air Leakage @ 75 Pa
(ASTM E2178)
-Air Leakage After 3000 Pa Test
(ASTM E330-90)
-Assembly Air Leakage
@ 75 Pa (ASTM E2357)
-Crack Cycling
(ASTM C836)
Pass
0.86 perms
(49 ng/Pa.s.m2)
0.03 perms
(2 ng/Pa.s.m²)
25.0 lbf/in
(> 4378.4 N/m)
0.1%
0.0001 cfm/ft2
(0.0005 L/s.m.²)
No change
0.001 cfm/ft2
(0.005 L/s.m.²)
Pass
Packaging
-Roll length
-Roll width
-Top Surface
-Bottom Surface
75 ft.
48”, 36”, 18”, 12”, 9”, 6”, 4”
Blue Film
Siliconized Release Film
-Gross Coverage (Net Coverage*)
36”
18”
*Based on 2” laps
225 ft2 (212 ft2)
112.5 ft2 (100 ft2)
(Side and end laps)
Description
Blueskin SA is a self-adhering membrane consisting of an SBS rubberized asphalt compound, which is integrally laminated to a blue
engineered thermoplastic film. The membrane is specifically designed to be self-adhered to a prepared substrate, providing an
air/vapor/water barrier in full wall applications or as penetration/flashing membrane with other air barrier systems. Blueskin SA, in
assemblies with primer and BES Sealant meet ASTM E-2357 – reference guide specification for details.
Features
• SBS modified membrane, flexible at low temperatures
• Impermeable to air, moisture vapor and water
• Assemblies of Blueskin SA, primer and sealant meet ASTM E-2357 air barrier performance standard.
• Excellent adhesion to prepared substrates of concrete, concrete block, primed steel, aluminum mill finish, anodized
aluminum, galvanized metal, gypsum board and plywood
• Compatible with Henry Air-Bloc liquid air barrier membranes
• Membrane is self-gasketing when penetrated and under compression with self-tapping screws
REVISION: 04/26/13
Henry Company 999 N. Sepulveda, Ste 800, El Segundo CA 90245-2754
Technical Services- Phone (800) 486-1278 – Email: techservices@henry.com
www.henry.com
Blueskin SA Self-Adhesive Air/Vapor Barrier Membrane
Storage
Store rolls on end, on original pallets or elevated platform. Protect from weather or store in an enclosed area not subject to heat over
120°F.
Limitations
Not designed for permanent exposure to weather - protect as soon as possible, however can be exposed up to 30 days if necessary to
accommodate construction scheduling. Not to be used in direct contact with flexible PVC/vinyl membranes or gaskets.
Uses
Blueskin SA is designed for use as a self-adhered sheet air, vapor and rain barrier. Its principal application is on walls of either
masonry, concrete or gypsum board. It can also be used as a transition sheet in conjunction with Henry Liquid Membranes where
greater movement is anticipated, due to its high strength. Blueskin SA is also used for tying into metal on curtain walls, windows and
doorframes.
Surface Preparation
Acceptable substrates are precast concrete, cast-in place concrete, concrete block, primed steel, aluminum mill finish, anodized
aluminum, galvanized metal, gypsum board including Dens Glass Gold. All surfaces to receive Blueskin SA must be clean of oil,
dust and excess mortar. Strike masonry joints flush. Concrete surfaces must be smooth and without large voids, spalled areas or
sharp protrusions. Concrete must be cured a minimum of 14 days and must be dry before Blueskin SA is applied. Where curing
compounds are used, they must be clear resin based, without oil, wax or pigments.
All surfaces to receive Blueskin SA require an application of Blueskin Adhesive or Spray Prep, applied by lambs wool roller,
brush or spray at the rate of 85 to 250 ft2/gallon depending on porosity and texture of surface and allowed to dry for 30 minutes before
Blueskin SA is applied. Ensure that all surfaces receive Blueskin SA in the same day. Alternatively, apply Aquatac by roller at a
rate up to 500 ft2/gallon. Allow to dry to a tacky film.
Application
Refer to Blueskin SA Guide Specification for detailed application information.
Blueskin SA must be lapped a minimum of 2” on both sides and end laps. Position membrane for alignment; remove protective film
and press firmly in place. When membrane is entirely in place, roll membrane including seams with a counter top roller to ensure full
contact. When using membrane with brick ties, position membrane, press in place and cut for ties or projections. Seal around any
openings and at leading edge at the end of the days work with Henry #925 BES Sealant, Polybitume, Air-Bloc 21, or Air-Bloc 21
FR. Membrane applied to the underside of the substrate (i.e. ceilings) requires mechanical fastening through treated wood or
galvanized metal strapping, or have insulation mechanically fastened. Fastening must take place immediately after installation of
membrane. Space strapping on 18” centers, running perpendicular to the side laps.
Detail work must be carefully carried out to ensure continuous air tightness of the membrane. It is recommended that mechanical
attachment be made to all window and doorframes, or a properly designed sealant joint be provided.
Insulation Application over Membrane
Insulation Clips: Insulation clips should be mechanically fastened through the membrane into the substrate with a self-tapping screw.
Apply number of insulation clips as recommended by the insulation manufacturer.
Insulation Adhesive: Henry Air-Bloc 21 –where permitted by local VOC regulations - should be applied to insulation boards in a
serpentine pattern to restrict movement of air behind the insulation. Alternatively, a full coat notched trowel application of Henry Air-
Bloc 21 may be applied to the back of the board. Press insulation firmly in place.
REVISION: 04/26/13
Henry Company 999 N. Sepulveda, Ste 800, El Segundo CA 90245-2754
Technical Services- Phone (800) 486-1278 – Email: techservices@henry.com
www.henry.com
Blueskin SA Self-Adhesive Air/Vapor Barrier Membrane
Limited Warranty
We, the manufacturer, warranty only that this product is free of defects, since many factors which affect the results obtained from this
product - such as weather, workmanship, equipment utilized and prior condition of the substrate - are all beyond our control. We will
replace at no charge any product proved to be defective within 12 months of purchase, provided it has been applied in accordance with
our written directions for uses we recommended as suitable for this product. Proof of purchase must be provided. DISCLAIMER OF
WARRANTIES: The Limited Warranty is IN LIEU OF any other warranties express or implied including but not limited to any implied
warranty of MERCHANTABILITY or fitness for a particular purpose, and we, the manufacturer, shall have no further liability of any kind
including liability for consequential or incidental damages resulting from any defects or any delays caused by replacement or otherwise.
STATEMENT OF RESPONSIBILITY
The technical and application information herein is based on the present state of our best scientific and practical knowledge. As the
information herein is of a general nature, no assumption can be made as to a product’s suitability for a particular use or application and
no warranty as to its accuracy, reliability or completeness either expressed or implied is given other than those required by law. The
user is responsible for checking the suitability of products for their intended use. Henry Company data sheets are updated on a regular
basis; it is the user’s responsibility to obtain and to confirm the most recent version. Information contained in this data sheet may
change without notice.
Henry Company, 999 N. Sepulveda, Ste. 800 El Segundo CA 90245 REV: 04/24/14
Tel: 800-486-1278 Email: techservices@henry.com
www.henry.com
TECHNICAL DATA SHEET
FOILSKIN
Self-Adhesive Weather Barrier Membrane
Physical Properties
-Color
-Thickness
-Application Temp
-Service Temp
-Elongation
(ASTM D412-modified)
-Tensile Strength Membrane
(ASTM D412- modified)
-Tensile Strength (Foil)
(ASTM C1136)
Mold Resistance
(ASTM C665)
Aluminum
40 mils (1.0 mm)
Minimum 20F (-7°C)
Minus -40F to 140F
40% minimum
900 psi (6.2 mPa)
2812 psi (19.4 mPa)
1875 psi (12.9 mPa)
No growth
-Minimum Puncture
Resistance – Membrane
(ASTM E154)
-Low Temperature Flexibility
@ -22F
(CGSB 37-GP-56M)
-Water Vapor Permeance
(ASTM E96)
-Lap Peel Strength @ 40F
(ASTM D903 180 bend)
40 lbf
(178 N)
Pass
2.8 ng/Pa.s.m²
(0.05 perms)
(15 lbs/ inch)
2600 N/m width
Packaging
-Thickness
-Roll length
-Roll width
-Gross Coverage
40 mils
33.3’
36”
100 sq. ft.
-Top Surface
-Bottom Surface
Foil Scrim
Siliconized Release Paper
Description
FOILSKIN® is a self-adhering membrane consisting of an SBS rubberized asphalt compound, integrally laminated
to a glass scrim reinforced aluminum foil. The membrane is specifically designed to be self-adhered to a prepared
substrate, providing a weather barrier.
Features
SBS modified membrane, flexible at low temperatures
Impermeable to air, moisture vapor and water
No flame or adhesive required for installation
Thickness controlled at point of manufacture
Excellent adhesion to prepared insulation substrates
Membrane is self-sealing when penetrated with self-tapping screws
Self-adhesive membrane bond strengthens over time
Does not promote mould growth
Ultra-violet light resistant
Uses
FOILSKIN® is designed for use as a transition membrane with Air-Bloc 33 Air Barrier System. See Air-Bloc 33
Guide Specification.
Storage
Store FOILSKIN® rolls on end, on original pallets or elevated platform. Protect unused portion of membrane by
storing in original box to maintain self-adhesive quality. Protect from weather elements or store in an enclosed
area not subject to heat over 120F. Double stacked pallets are not recommended. If double stacking is
necessary, use a plywood sheet to distribute the load.
Henry Company, 999 N. Sepulveda, Ste. 800 El Segundo CA 90245 REV: 04/24/14
Tel: 800-486-1278 Email: techservices@henry.com
www.henry.com
FOILSKIN® Self-Adhesive Weather Barrier Membrane
Limitations
FOILSKIN® is not to be used in direct contact with flexible/highly plasticized PVC/vinyl membranes or gaskets.
Some sealants may discolor if in contact with the asphalt compound or may soften the asphalt compound. Contact
sealant manufacturer for more information.
Surface Preparation
Acceptable substrates are precast concrete, cast-in place concrete, concrete block, primed steel, aluminum mill
finish, anodized aluminum, galvanized metal, gypsum board including Dens Glass Gold. All surfaces to receive
Foilskin must be clean of oil, dust and excess mortar. Strike masonry joints flush. Concrete surfaces must be
smooth and without large voids, spalled areas or sharp protrusions. Concrete must be cured a minimum of 14
days and must be dry before Foilskin® is applied. Where curing compounds are used, they must be clear resin
based, without oil, wax or pigments.
All surfaces to receive Foilskin® require an application of Blueskin® Primer applied by lambs wool roller or
brush at the rate of 85 to 250 sq. ft./gallon depending on porosity and texture of surface and allowed to dry for 30
minutes before Foilskin® is applied. Ensure that all surfaces receive Foilskin® in the same day. Alternatively,
apply Aquatac™ Primer by roller at a rate up to 500 sq. ft/gallon. Allow to dry to a tacky film.
Application
Refer to Air-Bloc 33 Guide Specification and details for further application information. Foilskin® must be
lapped a minimum of 2” on both sides and end laps. Position membrane for alignment, remove protective film and
press firmly in place. When membrane is entirely in place, roll membrane including seams with a counter top roller
to ensure full contact. When using membrane with brick ties, position membrane, press in place and cut for ties or
projections. Seal around any openings and at leading edge at the end of the days work with Air-Bloc 33.
Membrane applied to the underside of the substrate (i.e. ceilings) requires mechanical fastening through treated
wood, galvanized metal strapping, or have insulation mechanically fastened. Fastening must take place
immediately after installation of membrane. Space strapping on 18” centers, running perpendicular to the side
laps.
Detail work must be carefully carried out to ensure continuous air tightness of the membrane. It is recommended
that mechanical attachment be made to all window and doorframes, or a properly designed sealant joint be
provided.
Caution
FOILSKIN® is highly reflective to sunlight. It is strongly recommended to use sunglasses to prevent eye damage
when working with the membrane.
Limited Warranty
We, the manufacturer, warranty only that this product is free of defects, since many factors which affect the results obtaine d from
this product - such as weather, workmanship, equipment utilized and prior condition of the substrate - are all beyond our control.
We will replace at no charge any product proved to be defective within 12 months of purchase, provided it has been applied in
accordance with our written directions for uses we recommended as suitable for this product. Proof of purchase must be provided.
DISCLAIMER OF WARRANTIES: The Limited Warranty is IN LIEU OF any other warranties express or implied including but not
limited to any implied warranty of MERCHANTABILITY or fitness for a particular purpose, and we, the manufacturer, shall have no
further liability of any kind including liability for consequential or incidental damages resulting from any defects or any delays caused
by replacement or otherwise. <>
Northshore, please clarify FIP
insulation
by Northshore
Vertical support is
responsibility of Northshore
where panel ends do not land
on stud.
NBBJ, please confirm 'Vertical
Support' must conform to
074219 2.5 A Misc Metal
Subframing
NBBJ: CONFIRMED, DETAIL BELOW OR DETAIL
3/KIP601 AS APPROPRIATE TO SUPPORT
PANEL EDGES & TRANSFER LOADS PER
MANUFACTURER'S RECOMMENDATIONS.
36"KS36KPEXTERIOR FACEINTERIOR FACE3"KIP 101SWEDISH EDMONDSAMBULATORY CARE CENTEREDMONDS, WASHINGTONa. Non-exposed sealant shall be field applied gun grade non-skinning butyl.b. Exposed sealant shall be field applied gun grade urethane or silicone sealant. (Not By KINGSPAN INSULATED PANELS)c. KINGSPAN INSULATED PANELS is not responsible for field installed vapor seal at joints and junctures.d. KINGSPAN INSULATED PANELS is not responsible for vapor leaks caused by penetration throughthe panels.a. All trim shall be fabricated from G90 or AZ50 in gauge and finish to match panel face.b. All trim is fastened at 12" o.c. unless otherwise noted in the details.a.Holes in panels for other trades to be cut, sealed and flashed by the trade concerned unless otherwise noted on these drawings.b. Openings which would reduce the structural strength of the panel are to be adequately reinforced byothers.a.The face of all steel must be free of bolt and rivet heads, built up welds or other obstruction which might interfere with bearing of panels on girts or purlins.b. Girts for support of panels must extend to outer extremities of elevations and across face of columnsto which panels are applied.c. All panels supports are to be true and plumb prior to erectingpanels. Recommended wall tolerance is 14" in any 20' direction. Recommend roof tolerance is 0" outward, 12" inward from plane.The following specifications appear on shop drawings prepared by KINGSPAN INSULATED PANELS.They are intended to be a guide for minimum acceptable installation procedures and to indicate thequantity, size and materials specification of products furnished by KINGSPAN INSULATED PANELS, forthe described project. They should not be used to replace or supplant specifications or notes on structuraldrawings. Materials shown on these drawings and specifications have been approved by KINGSPANINSULATED PANELS for the purpose shown.Exercise care to maintain uniform side joints on all panels at each elevation.GENERAL NOTES:SEALANTS:TRIM:WORK OF OTHER TRADES:SUPPORTING STEEL AND GIRT SYSTEMS:MODULE RETENTION:FIELD-CUT PANELS:a.Field cutting shall be performed in accordance with current Kingspan installation guides.b.Field-cut panels where required at openings as shown on drawings. Cut edges are to be covered with trim.c.Field-cut panels to slope at endwalls.d.Some field cutting may be required.TOUCH UP:Use matching color touch up on material where damage consists of small chips, abrasions and field cutedges. Touch up paint may be obtained by contacting Kingspan customer service. For larger area paintrepairs, consult the Kingspan Maintenance Manual for instructions. Each panel shall be covered until justprior to erection. Care should be taken not to allow panel facings to come in contact with dirt, oil, grease,standing water or any other material which could stain exposed surfaces. Carefully follow storage andhandling instructions included with shipping documents.ON-SITE STORAGE:Panels and accessories are to be adequately protected from traffic and weather to ensure againstphysical damage or discoloration. Each panel shall be covered until just prior to erection. Care should betaken not to allow panel facings to come in contact with dirt, oil, grease, standing water or any othermaterial which could stain exposed surfaces. Carefully follow storage and handling instructions includedwith shipping documents.SHEET INDEXPAGE #DESCRIPTIONGENERAL INFORMATION, CALCULATIONSFLOOR PLANSKIP 101-102KIP 201-202LEGEND:ABBREVIATIONS:NOT ALL ABBREVIATIONS MAY BE USED ON THIS PROJECTAFF B.O.P.BLDG. CBCCMUF.F.F.O.GA.GALV.HORIZ.IBCNTS O/O PPH SIM.T.O.T.O.P.T.O.S.TYP.UBCUREW/ W/OWSHRSS ABOVE FINISH FLOORBOTTOM OF PANELBUILDINGCALIFORNIA BUILDING CODECONCRETE MASONRY UNITFINISH FLOORFRAMED OPENINGGAUGEGALVANIZEDHORIZONTALINTERNATIONAL BUILDING CODENOT TO SCALEON CENTEROUT TO OUTPHILIPS PANHEADSIMILARTOP OFTOP OF PANELTOP OF STEELTYPICALUNIFORM BUILDING CODEURETHANEWITHWITH OUTWASHERSTANDING SEAMO.C. OR O/CDISCLAIMER:CUSTOMER REVIEW CHECKLIST:Panel Information:ƑPanel type and thicknessƑGauge and color of the exterior/interior skinsƑ,IFRORULV³7REHGHWHUPLQHG´SOHDVHPDUNXSWKHGUDZLQJVZLWKWKHFKRVHQFRORUDQGFRQWDFWyour project coordinator to confirm the color selectionFloor Plans:ƑGrid lines on the plans are correctƑDimensions shown on the floor plan are correct with the latest structural/steel drawingsƑFloor plans are representative of where Kingspan materials are to be providedƑIf there are panel areas missing or not clearly shown, please mark up the drawings andcontact your project coordinator to reviewRoof Plans: (If applicable)ƑRoof dimensions are accurateƑRoof panel lengths are correct with the latest structural/steel drawingsƑEndlaps (if present) are lined up with a roof purlinƑOverhangs (if present) are properly shownƑCanopy areas (if present) are properly shownƑIf there are missing panels, overlaps needed that are not shown, or wrong dimensionsplease mark up the drawings and contact your project coordinatorElevations:ƑElevation tags show the correct location of the bottom of panel and top of panel/parapet/steelƑFramed opening sizes, locations, and quantities are correctƑWall length dimensions are correct and match the floor planƑWall panel lengths are correct at each elevation shownƑDetail called out corresponds to the correct condition at that locationƑQuantity and length of panels called out in panel lists correspond with that shown for each elevationƑIf multiple panel types, verify that the proper panel types are being used in the proper locationƑIf panel areas are missing or not clearly shown, please identify on the drawings and contact your project coordinator to reviewDetails:Please review each detail shown thoroughly, with special attention to the following:ƑBase condition(s) correct (flush mount or overhung?)ƑSlab edge shown is correct, matches concrete condition (squared off or keyway?)ƑWindow details and flashings drawn correctlyƑOverhead door details and flashings drawn correctlyƑTrims necessary for proper installation shown in details (special attention should be paid to those PDUNHG³1RWE\.LQJVSDQ´ƑLocation and type of structural members shown in details reflect actual structural members presentQRWHSOHDVHLQGLFDWHRQWKHGUDZLQJVLIWKHUHDUHDQ\ORFDWLRQVXWLOL]LQJVWHHOWKLFNHUWKDQó´VRWKDWproper fasteners may be designated)ƑIf any detail conditions are omitted or are incorrect, please clearly identify on the drawingsTrims:ƑTrims to be provided as shownƑGauge and color of each trim piece is correctly identifiedƑShapes and dimensions of each trim are correctƑIf a different trim shape/dimension or color is desired, please mark up the drawings as neededAFTER COMPLETING THIS CHECKLIST, PLEASE CHECK THE APPROPRIATE BOX LOCATED IN7+(³)25$33529$/´6(&7,212)7+(7,7/(%/2&.7+(16,*1$1'5(78517+(DRAWINGS TO YOUR KINGSPAN PROJECT COORDINATOR.This checklist is provided as a guide when reviewing Kingspan shop drawings. Please take amoment to verify that the following information presented in these drawings is correct:Wall Sections:ƑWall construction/materials/panel thicknesses are correctƑElevations of support members are correctƑWall panel lengths are correctKIP 401-407WALL ELEVATIONSKIP 601-604DETAILSA2GRID LINE DESTINATIONELEVATIONDETAIL DESTINATIONELEVATION VIEW2GRID LINE DESTINATION2CROSS SECTION2DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEET AFGABOVE FINISH GRADEB.F.F.BELOW FINISH FLOORƑAPPROVED AS SUBMITTEDƑAPPROVED AS NOTEDƑREVISE / RESUBMITThese Approval Drawings are submitted for the above referenced project. Please review, sign, and return the Drawings marked either:"Approved as Submitted" (if there are no corrections),"Approved as noted" (with correction(s) clearly noted on the returned Drawing set), or"Revise / Resubmit" (with correction(s) clearly noted on the returned Drawing set).All dimensions, details and trims require approval/verification.All "clouded areas" must be reviewed and addressed to the satisfaction of Kingspan, before materials will be released for Fabrication and/orProduction Drawings will be issued.Approval of the Kingspan Drawings and panel analysis indicates that Kingspan has correctly interpreted the project requirements, and thedesigns thereof. This approval constitutes the acceptance of Kingspan dimensions, layouts, materials, and designs unless clearly notedotherwise.Kingspan is not responsible for checking the material and/or design compatibility of components that are not supplied by Kingspan.APPROVAL SIGNATURE DATE:PRINTED NAME & COMPANY OF SIGNATURE DATE:THESE DRAWING ARE ISSUED FOR
KINGSPAN PRODUCT
APPROVAL/VERIFICATION ONLY AND
SHOULD NOT BE USED FOR
INSTALLATION PURPOSES - "FOR
PRODUCTION" DRAWINGS SHALL BE
ISSUED AFTER APPROVED DRAWINGS
HAVE BEEN RECIEVED AND PROCESSEDKIP 701-702TRIMSCustomer to verify that the provided steel and/or architectural drawings upon which the Panel layoutand designs are based, are correct and accurately reflect the conditions necessary for design of allmaterials supplied by KINGSPAN. Customer must also verify that the project field conditions arerepresentative of the drawings submitted, OR that any and all necessary revised conditions that mayimpact design, have been submitted to and confirmed by KINGSPAN, prior to the release ofKINGSPAN Panel drawings or calculations.KINGSPAN is not responsible or liable for incorrect Panel lengths as a result of changes made aftersigned approved shop drawings are returned.Drawings furnished by KINGSPAN show Panel layouts, wall elevations, and fastening details only;they do not replace structural drawings. It is the project engineers or project architect's responsibilityto determine if allowable Panel and fastener loads meet the project design loads.KINGSPAN is only responsible for showing items that are furnished by KINGSPAN. Referencedimensions shown on these drawings have been taken from steel / architectural drawings providedby the customer, and have not been independently verified by KINGSPAN.Items not included in KINGSPAN material bid package may be shown in the drawings / details forinformational purposes only. KINGSPAN will supply only those items specifically included in theOrder Acknowledgement. It is the customer's (or the authorized agent's) responsibility to verifyKINGSPAN'S scope.Optional engineering seal provided by KINGSPAN on these drawings indicates Panel spans andconnections have been verified and approved for use as drawn. This approval pertains solely to thematerials being supplied by KINGSPAN, and does NOT apply to the structural supports or any othercomponents which may be shown on the drawings (for clarification purposes only). These items mustbe reviewed and approved by the project engineer of record.WALL PANEL CONFIGURATION: 3"36"UrethaneEXTERIOR FACEKS36KPCoverageProfileMaterialTextureGaugeFinishColorCore ThicknessCore MaterialPanel TypeAZ50ShadowlineMP26Stucco EmbossedINTERIOR FACEMP26AZ50Stucco EmbossedShadowlineImperial WhiteImperial WhiteKIP 501SOFFIT PLAN3/31/2015 3:15:27 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
KIP 102DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:29 PM
363'-0"1NMLKJHGFEDCBA2344.85XAYA1'132'-0"14311/16" = 1'-0"LEVEL ONE FLOOR PLAN /23241256KIP 201DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:35 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
1LKJHGFEDCBA2344.85XAYAX12X10X9X7X6X5X4X7.4X8101/16" = 1'-0"LEVEL TWO FLOOR PLAN /303'-6"132'-0"132324121298741311EW2EW1KIP 202DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:36 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
1PANELS QUANTITY --GRID LINE 1'1/8" = 1'-0"128'-4" O/O PANEL10482TYPT.O.P.15'-0"LEVEL 10'-0"69'-9" O/O PANEL3TYP2828B.O.P.0'-6"T.O.P.24'-0"143'-3" O/O PANEL16723'-3"23'-3"23'-3"32'-1"32'-1"32'-1"32'-1"3PANELS QUANTITY --GRID LINE A1/8" = 1'-0"114LEVEL 10'-0"B.O.P.0'-6"T.O.P.56'-0"126'-1014" O/O PANEL281025'-512"25'-512"25'-512"25'-512"25'-014"8'-212"15112TYP3TYP2821SIMKIP 401DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:37 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
2PANELS QUANTITY --GRID LINE 11/8" = 1'-0"166'-1034" O/O PANEL4LEVEL 10'-0"28B.O.P.0'-6"T.O.P.41'-0"161010931'-734"31'-734"27'-234"25'-512"25'-512"25'-512"3TYP3TYP1076'-434" O/O PANEL281025'-512"25'-534"25'-512"2GRID LINE 1 - CONTINUED1/8" = 1'-0"LEVEL 10'-0"B.O.P.0'-6"T.O.P.56'-0"2TYPKIP 402DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:38 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
4PANELS QUANTITY --GRID LINE XA1/8" = 1'-0"4LEVEL 10'-0"B.O.P.0'-6"11233284'-714" O/O PANEL28'-238"T.O.P.41'-0"LEVEL 222'-0"B.O.P.31'-0"T.O.P.56'-0"76'-7" O/O PANEL20'-218"45'-6" O/O PANEL43'-514" O/O PANEL21'-858"21'-858"28'-238"28'-212"2228'-212"28'-238"22'-9"22'-9"28281112132042TYP3TYP212811'-478"SIM5PANELS QUANTITY --ELEVATION 51/8" = 1'-0"4LEVEL 10'-0"B.O.P.0'-6"16103218'-838" O/O PANEL6PANELS QUANTITY --ELEVATION 61/8" = 1'-0"4LEVEL 10'-0"B.O.P.0'-6"10203274'-434" O/O PANELT.O.P.11'-0"T.O.P.11'-0"18'-534"32'-0"23'-11"222TYP2323KIP 403DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:39 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
7PANELS QUANTITY --GRID LINE XA1/8" = 1'-0"B.O.P.31'-0"T.O.P.41'-0"145'-012" O/O PANEL21'-714"25'-512"25'-512"25'-512"25'-512"1228421'-714"173TYP8PANELS QUANTITY --GRID LINE X8 - CONNECTOR1/8" = 1'-0"B.O.P.19'-0"PENTHOUSE38'-0"66'-712" O/O PANEL25'-512"25'-512"172815'-812"LEVEL 222'-0"6B.O.P.31'-0"T.O.P.25'-0"312'-5"9PANELS QUANTITY --GRID LINE X7.4 - CONNECTOR1/8" = 1'-0"B.O.P.19'-0"T.O.P.41'-0"97'-10" O/O PANEL25'-512"25'-512"182816'-514"LEVEL 222'-0"6PENTHOUSE38'-0"312'-5"30'-534"6'-11"B.O.P.23'-6"52TYP2TYP3TYP3TYPSIMSIMKIP 404DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:40 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
10PANELS QUANTITY --GRID LINE J1/8" = 1'-0"T.O.P.41'-0"108'-1118" O/O PANEL25'-512"25'-512"102832'-658"LEVEL 222'-0"18PENTHOUSE38'-0"525'-512"B.O.P.23'-6"2TYP2TYP3TYP11PANELS QUANTITY --GRID LINE YA1/8" = 1'-0"145'-112" O/O PANEL24'-214"24'-214"102824'-214"LEVEL 222'-0"10524'-214"T.O.P.24'-0"B.O.P.15'-0"165514'-278" O/O PANEL10283224'-214"24'-214"18'-1134"10'-278"26'-812"5'-038"2'-0" O/O PANEL19192TYP3TYP2811PANELS QUANTITY --GRID LINE YA - CONTINUED1/8" = 1'-0"59'-312" O/O PANEL29'-734"1428LEVEL 222'-0"529'-734"T.O.P.24'-0"B.O.P.15'-0"16102852TYP3TYPKIP 405DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:41 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
12PANELS QUANTITY --PENTHOUSE1/8" = 1'-0"134LEVEL 10'-0"T.O.P.56'-0"132'-134" O/O PANEL281025'-512"25'-512"30'-9"25'-512"25'-014"8'-212"PENTHOUSE38'-0"2TYP3TYPEW2PANELS QUANTITY --EXHAUST WELL1/8" = 1'-0"164T.O.P.56'-0"59'-212" O/O PANEL281929'-714"29'-714"PENTHOUSE38'-0"EW1PANELS QUANTITY --EXHAUST WELL1/8" = 1'-0"194T.O.P.56'-0"22'-534" O/O PANEL2816PENTHOUSE38'-0"KIP 406DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:22242323@ STOREFRONT252626@ DOOR3/31/2015 3:15:43 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
13PANELS QUANTITY --CANOPY1/8" = 1'-0"LEVEL 10'-0"250'-1112" O/O PANELLEVEL 222'-0"33'-0"34'-5"28'-5"19'-6"19'-6"19'-6"28152TYP3TYP250'-1112" O/O PANEL13'-814"19'-6"19'-6"19'-6"33'-214"19'-6"19'-6"27'-612"4'-0"B.O.P.13'-0"1031311013PANELS QUANTITY --CANOPY - CONTINUED1/8" = 1'-0"3114'-234"321027SIMSIMKIP 407DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:3/31/2015 3:15:44 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
4.85XAX12X10X9X7X7.4X8YA1/16" = 1'-0"SOFFIT PLAN 13'-2
"
12'-5
"
11'-8
"
10'-1
1
"
10'-2
"
9'-5"
8'-8"
7'-11
"
7'-2"
6'-5"
5'-8"
4'-11
"
4'-2"
3'-5"
3'-0"
14'-8
"
13'-1
1
"
15'-5
"
16'-2
"
16'-1
1
"
17'-8
"
18'-5
"
19'-2
"
19'-1
1
"
20'-8
"
21'-5
"
22'-2
"
22'-9
"
20'-0
"
10'-9
"
6'-6"
7'-6"
8'-6"
9'-6"
10'-5
"
11'-5
"
13'-4
"
12'-5
"
15'-4
"
14'-4
"
16'-4
"
17'-3
"
17'-9"19'-2"3131323232323218'-3
"
19'-3
"
20'-2
"
21'-2
"
22'-2
"
23'-1
"
24'-1
"
25'-1
"
26'-1
"
27'-0
"
28'-0
"
28'-2
"
27'-1
0
"
27'-5
"
27'-0
"
26'-7
"
26'-2
"
25'-9
"
25'-4
"
24'-1
1
"
24'-6
"
24'-0
"
23'-7
"
24'-6
"
22'-9
"
22'-4
"
21'-1
1
"
21'-6
"
21'-1
"
20'-8
"
20'-3
"
19'-1
0
"
19'-5
"
19'-0
"
18'-7
"
18'-2
"
17'-9
"
17'-4
"
16'-1
1
"
16'-5
"71'-11"247'-0 1/2"313232SIMSIM14'-83
8"KIP 501DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:ALL DIMENSIONS AREO/O OF PANELSREQUIRE VERIFICATION--NOT BY KINGSPAN.ALL DIMENSIONS AND PANEL LENGTHSNOTE:3/31/2015 3:15:45 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.NBBJ: REQUESTED DETAIL @ CURTAINWALLHEAD NOT PROVIDED. REFERENCE 13 &14/A8.04. CONTINUITY OF WEATHER, AIR &THERMAL BARRIER PAST HEAD SUPPORTINGCHANNEL TO CURTAINWALL HEAD SHALL BEMAINTAINED. GC TO VERIFY & COORDINATE.
27356894SECTION VIEWPANEL JOINT SCALE: N.T.S.PLAN VIEWINTERMEDIATE SUPPORT SCALE: N.T.S.1VERTICAL JOINT PLAN VIEWSCALE: N.T.S.SECTION VIEWBASESCALE: N.T.S.FIELD CUT PANEL AS REQ'D(NOT BY KINGSPAN)CONTINUOUS BUTYL SEALANTAT PANEL JOINTS&217,18286.$55,(55$,/(1) 14" - 14 x 4" TEK 3FASTENERS w/ WASHERAT EVERY OTHER STUD6(7.$55,(55$,/,1%87</SEALANT AT FASTENERLOCATIONSFEMALE JOINTMALE JOINT
WALL PANEL INSTALLATION DIRECTION
VERTICAL SUPPORT(NOT BY KINGSPAN)METAL PANEL(NOT BY KINGSPAN)MP-1 CONTINUOUS MENDINGPLATE w/ POP RIVETS @ 12" O/CATTACHED TO STUD FRAMINGPRIOR TO PANEL INSTALLATIONCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTFILL GAPS 14" OR LARGERWITH F.I.P. INSULATION(NOT BY KINGSPAN)VERTICAL SUPPORT(NOT BY KINGSPAN)&217,18286.$55,(55$,/6(7.$55,(55$,/,1%87</SEALANT AT FASTENERLOCATIONS5" MIN.5" MIN.OPTIONAL FRAMINGTRIPLE STUD(2) 14" - 14 x 4" TEK 3FASTENERS w/o WASHERMETAL PANEL SYSTEM(NOT BY KINGSPAN)&217,1286.$55,(55$,/SINGLE SKIN PANEL(NOT BY KINGSPAN)(2) 14" - 14 x 4" TEK 3FASTENERS w/ WASHERAT EVERY OTHER STUDVERTICAL SUPPORTAT 16" O.C.(NOT BY KINGSPAN)6(7.$55,(55$,/,1%87</SEALANT AT FASTENERLOCATIONSMETAL PANEL(NOT BY KINGSPAN)4" DP3 FASTENER@ 12" O.C.BUTYL SEALANTMETAL STUD FRMGBY OTHERSFLEXIBLE FLASHING(NOT BY KINGSPAN)SCALE: N.T.S.SECTION VIEWBASE @ ROOFBUILT UP ROOF(NOT BY KINGSPAN)14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.MEMBRANE FLASHING(NOT BY KINGSPAN)CONTINUOUSBUTYL SEALANTSECTION VIEWBASESCALE: N.T.S.METAL PANEL(NOT BY KINGSPAN)BUTYL SEALANTMETAL STUD FRMGBY OTHERSFLEXIBLE FLASHING(NOT BY KINGSPAN)JC-1 "J" CLIP w/1" DP3 @ 12" O.C.w/ SEALANT IN BASEFILL GAPS 14" OR LARGERWITH F.I.P. INSULATION(NOT BY KINGSPAN)SCALE: N.T.S.PLAN VIEWPANEL @ EXPANSION JOINTCT-3 CAP TRIMCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)FASTENER(NOT BY KINGSPAN)SUB FRAMING AS REQUIRED(NOT BY KINGSPAN)EXPANSION JOINT(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCT-3 CAP TRIMVERTICAL SUPPORT(NOT BY KINGSPAN)CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)EXPANSION JOINT(NOT BY KINGSPAN)CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTSCALE: N.T.S.PLAN VIEWPANEL @ EXPANSION JOINTSCALE: N.T.S.PLAN VIEWPANEL @ EXPANSION JOINT(2) 14" - 14 x 4" TEK 3FASTENERS w/o WASHERMETAL PANEL(NOT BY KINGSPAN)SUB FRAMING AS REQUIRED(NOT BY KINGSPAN)EXPANSION JOINT(NOT BY KINGSPAN)14" - 14 x 4" TEK 3FASTENERS w/ WASHERAT EVERY OTHER STUD(1) 14" - 14 x 4" TEK 3FASTENERS w/ WASHERAT EVERY OTHER STUD&217,18286.$55,(55$,/(2) 14" - 14 x 4" TEK 3FASTENERS w/o WASHERPER SUPPORTKIP 601DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:46 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
111612101415171813SCALE: N.T.S.PLAN VIEWOUTSIDE CORNER SCALE: N.T.S.PLAN VIEWINSIDE CORNER SCALE: N.T.S.PLAN VIEWINSIDE CORNER (2) 14"-14 x 4" TEK 3 w/WASHER, PER SUPPORTOC-7 OUTSIDE TRIMw/ #10 x 34" PPH @ 12" O.C.CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)6(7.$55,(5&/,3,1BUTYL SEALANT ATFASTENER LOCATIONS.$55,(55$,/IC-7 INSIDE CORNER TRIMw/ POP RIVETS @ 12" O.C.(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTIC-1 INSIDE CORNER TRIMVERTICAL SUPPORT(NOT BY KINGSPAN)FIELD MITER CUTPANELSCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)OC-1 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.F.I.P. INSULATIONAS REQUIRED(BY OTHERS)SUB FRAMING AS REQUIRED(NOT BY KINGSPAN)OUTSIDE CORNER OUTSIDE CORNER PLAN VIEWSCALE: N.T.S.IC-2 INSIDE CORNER TRIMSCALE: N.T.S.OUTSIDE CORNER PLAN VIEWSCALE: N.T.S.PLAN VIEWSCALE: N.T.S.PLAN VIEWOUTSIDE CORNER SUB FRAMING(NOT BY KINGSPAN)METAL PANEL(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTOC-2 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.KARRIER RAILCONTINUOUS KARRIER RAILBUTYL SEALANTBUTYL SEALANTOC-3 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.METAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)BUTYL SEALANT(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-3 INSIDE CORNER TRIMSUB FRAMING(NOT BY KINGSPAN)METAL PANEL(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-4 INSIDE CORNER TRIMOC-4 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.KARRIER RAILBUTYL SEALANTMETAL PANEL(NOT BY KINGSPAN)SUB FRAMING AS REQUIRED(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTOC-5 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-5 INSIDE CORNER TRIMBUTYL SEALANTKARRIER RAILOUTSIDE CORNER SCALE: N.T.S.PLAN VIEWSUB FRAMING(NOT BY KINGSPAN)METAL PANEL(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTOC-6 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.IC-6 INSIDE CORNER TRIMw/ #10 x 34" PPH @ 12" O.C.KARRIER RAILBUTYL SEALANTSCALE: N.T.S.PLAN VIEWINSIDE CORNER METAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-8 INSIDE CORNER TRIMKARRIER RAILBUTYL SEALANTOC-8 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.METAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)OC-9 OUTSIDE CORNERw/ #10 x 34" PPH @ 12" O.C.KARRIER RAILBUTYL SEALANT(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-9 INSIDE CORNER TRIMw/ POP RIVETS @ 12" O.C.KIP 602DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:48 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
202521192324262722SCALE: N.T.S.PLAN VIEWINSIDE CORNER @ PERP. TO PANEL(2) 14"-14 x 4" TEK 3 w/WASHER, PER SUPPORTCT-3 CAP TRIMCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)6(7.$55,(5&/,3,1BUTYL SEALANT ATFASTENER LOCATIONS.$55,(55$,/BACKER ROD & SEALANT(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/WASHER, PER SUPPORTCT-3 CAP TRIMCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTMETAL PANEL(NOT BY KINGSPAN)6(7.$55,(55$,/,1BUTYL SEALANT ATFASTENER LOCATIONS.$55,(5&/,3SUB FRAMING & FASTENER(NOT BY KINGSPAN)WINDOW SYSTEM(NOT BY KINGSPAN)EXPOSED SEALANT(NOT BY KINGSPAN)FIELD CUT PANELS AS REQUIREDFLASHING(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)CONTINUOUS BUTYL SEALANT14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.SUB FRAMING(NOT BY KINGSPAN)NOTE:SEE ARCHITECTURAL DETAILS 1 & 4/A8.04SCALE: N.T.S.PLAN VIEWINSIDE CORNER @ GLAZINGPANEL SYSTEM(NOT BY KINGSPAN)SUB FRAMING AS REQUIRED(NOT BY KINGSPAN)(2) 14"-14 x 4" TEK 3 w/oWASHER, PER SUPPORTCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTIC-10 INSIDE CORNER TRIMKARRIER RAILBUTYL SEALANTOC-10 OUTSIDE CORNERw/ POP RIVETS @ 12" O.C.(2) 4" DP3 PER SUPPORTSCALE: N.T.S.PLAN VIEWJAMBSCALE: N.T.S.SECTION VIEWHEADSCALE: N.T.S.SECTION VIEWSILLSCALE: N.T.S.PLAN VIEWDOOR JAMBSCALE: N.T.S.SECTION VIEWDOOR HEAD NOTE:SEE ARCHITECTURAL DETAILS 2 & 5/A8.04NOTE:SEE ARCHITECTURAL DETAILS 3 & 6 /A8.04WINDOW SYSTEM(NOT BY KINGSPAN)EXPOSED SEALANT(NOT BY KINGSPAN)FLASHING(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.SUB FRAMING(NOT BY KINGSPAN)FASTENER AS REQUIREDATTACHED TO STRUCTURAL MEMEBER(NOT BY KINGSPAN)WINDOW SYSTEM(NOT BY KINGSPAN)EXPOSED SEALANT(NOT BY KINGSPAN)FIELD CUT PANELSAS REQUIREDFLASHING(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)CONTINUOUS BUTYL SEALANT14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.SUB FRAMING(NOT BY KINGSPAN)CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTDOOR FRAME(NOT BY KINGSPAN)EXPOSED SEALANT(NOT BY KINGSPAN)FIELD CUT PANELS AS REQUIREDFLASHING(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)CONTINUOUS BUTYL SEALANT14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.SUB FRAMING(NOT BY KINGSPAN)NOTE:SEE ARCHITECTURAL DETAILS 1, 2, & 5/A8.01NOTE:SEE ARCHITECTURAL DETAILS 2 & 5/A8.04DOOR FRAME(NOT BY KINGSPAN)EXPOSED SEALANT(NOT BY KINGSPAN)FLASHING(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)14" - 14 x 4" TEK 3 FASTENERSw/ WASHER @ 12" O.C.SUB FRAMING(NOT BY KINGSPAN)FASTENER AS REQUIREDATTACHED TO STRUCTURAL MEMEBER(NOT BY KINGSPAN)CONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTBUTT JOINT TO OTHERPLAN VIEWSCALE: N.T.S.MP-1 CONTINUOUS MENDINGPLATE w/ POP RIVETS @ 12" O/CATTACHED TO STUD FRAMINGPRIOR TO PANEL INSTALLATIONCONTINUOUS BUTYLSEALANT WITH MARRIAGEBEAD TO HORIZONTALPANEL JOINTVERTICAL SUPPORT(NOT BY KINGSPAN).$55,(55$,/6(7.$55,(5&/,3,1%87</SEALANT AT FASTENERLOCATIONS5" MIN.(2) 14" - 14 x 4" TEK 3FASTENERS w/o WASHERMETAL PANEL SYSTEM(NOT BY KINGSPAN)SCALE: N.T.S.PLAN VIEWPANEL TO GLAZINGKARRIER RAILKIP 603DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:49 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
293430283233353631SECTION VIEWSOFFIT TO WALLSCALE: 3" = 1'-0"SECTION VIEWFASCIA TO SOFFITSCALE: 3" = 1'-0"14" - 14 x 4" TEK 3FASTENERSw/ WASHER @ 12" O.C.METAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)CONTINUOUS BUTYL SEALANTSOFFIT PANEL(NOT BY KINGSPAN)SOFFIT PANEL(NOT BY KINGSPAN)BUTYL SEALANTFASTENER AS REQUIRED(NOT BY KINGSPAN)PANEL SYSTEM(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)SECTION VIEWPARAPETSCALE: 3" = 1'-0"PARAPET FRAMING & FLASHING(NOT BY KINGSPAN)14" - 14 x 4" TEK 3FASTENERSw/ WASHER @ 12" O.C.METAL PANEL(NOT BY KINGSPAN)SUB FRAMING(NOT BY KINGSPAN)NOTE:SEE ARCHITECTURAL DETAIL 4/A8.02NOTE:SEE ARCHITECTURAL DETAIL 11/A8.02BUTYL SEALANTFILL VOIDS w/ F.I.P.FLEXIBLE FLASHING(NOT BY KINGSPAN)4" DP3 FASTENER@ 12" O.C.KIP 604DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:51 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUTMENDING PLATE26 GA. IMPERIAL WHITE SEMP-15CT-3CAP TRIM26 GA. IMPERIAL WHITE SEBLANK WIDTH: 6.001223COLOR12OC-1OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00121222COLOROC-2OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-2INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.001212COLORBLANK WIDTH:6.00IC-1INSIDE CORNER26 GA. IMPERIAL WHITE SECOLOR121233BLANK WIDTH: 7.00FOR PRODUCTION USE:CHKBYSTRETCH OUTFOR PRODUCTION USE:CHKBYSTRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHKBYSTRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
FOR PRODUCTION USE:CHK
BY
STRETCH OUT
OC-3OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 8.00IC-3INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.00OC-4OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-4INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.00FOR PRODUCTION USE:CHKBYSTRETCH OUT FOR PRODUCTION USE:CHKBYSTRETCH OUT
121222COLOR331212COLOR122122COLOR121233COLOR212212COLOR121233COLOROC-5OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-5INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.00121222COLOR123312COLOROC-6OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-6INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.001212121222COLOR33COLOROC-7OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-7INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 8.00121222COLOR1212412212COLOROC-8OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00IC-8INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.00121222COLOR121233COLORFOR PRODUCTION USE:CHKBYSTRETCH OUT FOR PRODUCTION USE:CHKBYSTRETCH OUT FOR PRODUCTION USE:CHKBYSTRETCH OUTOC-9OUTSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 7.00OC-10OUTSIDE CORNER26 GA. IMPERIAL WHITE SEIC-9INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00121233COLOR122122COLORIC-10INSIDE CORNER26 GA. IMPERIAL WHITE SEBLANK WIDTH: 5.00BLANK WIDTH: 7.00121222COLOR123COLOR312PLEASE VERIFYKIP 701DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:52 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
26 GA. IMPERIAL WHITEFLATSTOCKFS-1(2) BEADS OFBUTYL SEALANTFIELD NOTCHAS REQUIREDTRIM END LAP.$55,(55$,/16 GA. GALV. (BARE)"J" CLIP18 GA. BAREJC-1KARRIER RAIL MUST BE 50ksi STEEL. 33ksi STEEL WILL NOT BE ALLOWEDKIP 702DATEDRAWNSCALEJOB No.SHEETJOB NAMEPL03/04/15AS NOTEDM15 25376SWEDISH EDMONDS ACCDRAFTSMAN:
CONTACT NUMBER:
CONTACT NAME:
SHOPS CHECKED BY:
JOB NAME:
CUSTOMER NAME:
JOB LOCATION:
PROJECT COORDINATOR:
BY
Deland FL. ,Modesto CA., Columbus OH.
www.kingspanpanels.us
Fax: (209) 531-9055, Tel: (209) 5319091
R
REVISIONS THESE SHOP DRAWINGS WERE CREATED USING
THE FOLLOWING INFORMATION SUPPLIED BY
CUSTOMER AS THE BASIS OF DESIGN:
DATE:PLANS
6/10/14 NBBJ - ARCH SETSHEETƑAPPROVED AS NOTED
Ƒ APPROVED AS SUBMITTED
Ƒ REVISE / RESUBMIT
SIGNATURE:
DATE:3/31/2015 3:15:54 PMKingspan drawings for reference of panel layout only.Northshore drawings conforming to NBBJ comments perreturned submittal PAAN 0169-074219001-0 will takepresedence over information representied in these details.
NBBJ: PREVIOUSLYREVIEWED INFORMATIONNOT REVIEWED W/RE-SUBMITTAL
NBBJ: CONTINUOUS BUTYL SEALANTPER MANUFACTURER'S STANDARDDETAIL - OPTIONAL BEAD IN FORWARDGROOVE RECOMMENDED (TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: GC NOTE -COLD FORMEDMETAL FRAMINGTO EDGE OFSEISMIC JOINTGAPNBBJ: SEALANT BOTHSIDES OF TRIM TOMAINTAIN AIR BARRIERCONTINUITY W/ STUD (TYP)NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)NBBJ: GC NOTE - FLEXI-FLASHAS REQUIRED FOR AIRBARRIER CONTINUITY TOINNER SEAL (TYP)
NBBJ: SEE MARKUPS ON S01-DETNBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: NO VOID - CUTPANEL ENDS TOREQUIRED PROFILENBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DETNBBJ: GC NOTE - FLEXI-FLASHAS REQUIRED FOR AIRBARRIER CONTINUITY TOINNER SEAL (TYP)
NBBJ: GC NOTE - FLEXI-FLASHAS REQUIRED FOR AIRBARRIER CONTINUITY TOINNER SEAL (TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DETNBBJ: PANEL & FLASHINGSEALED TO UNDERSIDE OFSILL PAN SIMILAR TO 10-DET
NBBJ: SEE MARKUPS ON S01-DETNBBJ: GC NOTE -MAINTAIN CONTINUOUSROOF MEMBRANE SEALTO INSULATED METALPANEL SYSTEMNBBJ: CONFIRMWOOD NAILERSPER RFI-187
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DETNBBJ: PROVIDEDETAILING & DESIGNINFO FOR SOFFITPANELS & RAILS
NBBJ: SEE MARKUPS ON S01-DETNBBJ: CONFIRMWOOD NAILERSPER RFI-187NBBJ: GC NOTE - MAINTAINROOF MEMBRANECONTINUITY TOINSULATED METAL PANELSYSTEM
NBBJ: ALTERNATE DETAILSUGGESTED, EXTENDINGINSULATED PANELS DOWN TOWINDOW HEAD & ANCHORINGHSS TO "KARRIER" RAIL ASSHOWN. PLEASE CONFIRM IFVIABLE.
NBBJ: GC NOTE - MAINTAIN ROOFMEMBRANE CONTINUITY TOINSULATED METAL PANEL SYSTEMNBBJ: CONFIRMWOOD NAILERSPER RFI-187
NBBJ: PROVIDEDETAILING &DESIGN INFO FORSOFFIT PANELS &RAILS
NBBJ: SEE MARKUPS ON S01-DETNBBJ: CONFIRMWOOD NAILERSPER RFI-187NBBJ: GC NOTE - MAINTAIN ROOFMEMBRANE CONTINUITY TOINSULATED METAL PANEL SYSTEM
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEAL BETWEENSILL PAN & TOP OFPANEL TRIM (TYP)NBBJ: EXTEND SILL PANTO ALLOW FOR INNERSEAL CONTINUITY
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEAL BETWEENSILL PAN & TOP OFPANEL TRIM (TYP)NBBJ: EXTEND SILL PANTO ALLOW FOR INNERSEAL CONTINUITY
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: WINDOW JAMB TOADJOIN ENTRY FRAME.INSULATED PANEL WALLSLIVER NOT REQUIRED.
NBBJ: SEE MARKUPS ON S01-DETNBBJ: SEAL BOTTOMOF PANEL TRIM TOFOUNDATIONINSULATION (TYP)NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: CORNER JOINT ALTERNATE 1:KINGSPAN STANDARD MITEREDOUTSIDE CORNER DETAILKPH-OC-01-MTLV W/ BACKUP ANGLE &MARRIAGE BEADS TO HORIZONTALSEALANT JOINTS (SEE MARKUPS ON48/DET FOR ALTERNATE 2)
NBBJ: CORNER JOINT ALTERNATE 2:PANELS OVERLAPPED AS SHOWN. OVERLAPPING PANEL KERFED ONBACKSIDE TO PROVIDE THERMALBREAK, PANEL HORIZONTAL SEALANTBEADS CONTIGUOUS W/ VERTICALBEADS. (SEE MARKUPS ON 47/DET FORALTERNATE 1)KERFHORIZONTALSEALANT BEADSCONTIGUOUS W/VERTICAL BEADS(TYP)
NBBJ: ALTERNATE 1 OR 2CORNER DETAIL PER MARKUPSON 47/DET OR 48/DET
NBBJ: SEAL BOTTOMOF PANEL TRIM TOFOUNDATIONINSULATION (TYP)NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEAL BOTTOMOF PANEL TRIM TOFOUNDATIONINSULATION (TYP)NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)
NBBJ: NOTE - COORDINATEDETAIL W/ CURRENT 7/A8.06NBBJ: ALTERNATE 1 OR 2CORNER DETAIL PER MARKUPSON 47/DET OR 48/DET
NBBJ: BACKUP TRIM & BUTYL MARRIAGEBEAD TO HORIZONTAL PANEL SEAL PERKINGSPAN STANDARD DETAIL TO MAINTAINAIR BARRIER CONTINUITY & COVER FOAMPANEL END OPEN TO WALL CAVITY(TYP)
NBBJ: SEE MARKUPS ON S01-DET
NBBJ: GC NOTE -PROVIDE FRAMINGBACKUP ADJACENTCURTAINWALL JAMBNBBJ: GC NOTE -FLEX-FLASHING TOCURTAINWALL JAMB INNERSEAL AS NECESSARY TOMAINTAIN AIR BARRIERNBBJ: EXTENDINSULATED PANEL TOCURTAINWALL JAMBR.O. PROFILENBBJ: TWOPART FLASHINGNBBJ: CURTAINWALL PRIMARYSEAL @ LEADING EDGE OFJAMB - MAINTAIN AIR BARRIERTO THAT POINT
NBBJ: METAL TRIM W/"V" MOVEMENT BENDSEALED TO PANELS NBBJ: COMPRESSIBLEFOAM FILL
NBBJ: CONFIRMWOOD NAILERSPER RFI-187NBBJ: GC NOTE - MAINTAIN ROOFMEMBRANE CONTINUITY TOINSULATED METAL PANEL SYSTEM
NBBJ: CONFIRMWOOD NAILERSPER RFI-187NBBJ: GC NOTE - MAINTAINROOF MEMBRANE CONTINUITYTO SKYLIGHT SYSTEM
NBBJ: SEE MARKUPS ON 74-DETNBBJ: CONFIRMWOOD NAILERSPER RFI-187
NBBJ: SEE MARKUPS ON 74-DET
NBBJ: SEE MARKUPS ON 73-DETNBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)NBBJ: CONFIRMWOOD NAILERSPER RFI-187
NBBJ: ALTERNATE 1 OR 2CORNER DETAIL PER MARKUPSON 47/DET OR 48/DET
NBBJ: ALTERNATE 1 OR 2CORNER DETAIL PER MARKUPSON 47/DET OR 48/DET
NBBJ: TRIM ENDS SO NO EXPOSEDFOAM TO WALL CAVITY (TYP)
NBBJ: TRIM ENDS SO NOEXPOSED FOAM TO WALLCAVITY (TYP)
NBBJ: INSULATED METAL PANEL -MAINTAIN AIR BARRIERCONTINUITY & SEAL TO SILL PAN
NBBJ: ALTERNATE 1 OR 2CORNER DETAIL PER MARKUPSON 47/DET OR 48/DETNBBJ: INSIDE CORNERPER MARKUPS ON 65-DETNBBJ: TWO PARTTRIM W/ THERMALBREAKNBBJ: GC NOTE - PROVIDEFLEXI-FLASH AS REQUIREDTO MAINTAIN AIR BARRIERCONTINUITY TO INNER SEAL
NBBJ: INSULATEDMETAL PANELSYSTEM BACKUPNBBJ: THERMALLY BROKENTRANSITION DETAIL W/ AIRBARRIER CONTINUITY AS MARKEDUP ELSEWHERE IN THIS SUBMITTAL
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)NBBJ: SEAL BOTTOMOF PANEL TRIM TOFOUNDATIONINSULATION (TYP)
NBBJ: NO EXPOSEDFOAM TO CEILING ORWALL CAVITIES (TYP)
NBBJ: THERMALLY BROKEN& SEALED 2 PART ANGLEFLASHING RECOMMENDEDIN LIEU OF CHANNEL (TYP)NBBJ: SEAL BOTTOMOF PANEL TRIM TOFOUNDATIONINSULATION (TYP)
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL
NBBJ: NOT REVIEWEDUNDER THIS SUBMITTAL