08-0938 620 Glenn St Condo #3.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: 11/17/09 TO: Nash, Jones, Anderson Attn: Mike Johnson th 11644 80 St Kirkland, WA 98023 RE: Plan Check: BLD20080938 Project: Condominiums Project Address: 620 Glenn St During the review of the resubmitted plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. The comment numbers are based on the original and subsequent comments and responses. 1.The city’s consulting engineer has not yet responded to the latest comments. If there are additional comments, these will be forwarded as soon as possible. 9. Planning will be discussing the height issue. 20. There is some confusion as to the definition of an “Exit Passageway”, see Section 1021. The hatched area showing a path to the exit door does not constitutes an exit passageway. In order for the space to be considered an exit passageway, the space shall be enclosed with floor, ceiling, and wall construction of not less than one hour, 1021.3. Exit passageways shall be constructed as fire barriers according to Section 706. The elevators shall not open into the exit passageway, 1021.4. Perhaps a separated elevator lobby is in order. 20. (Additional) The door at the bottom of the stairs is crowding the landing. IBC 1009.4, exception 2: Doors opening onto a landing shall not reduce the landing width to less than ½ the required width. When fully open, the door cannot project more than 7” into a landing. 29. Handrail extensions: The six inch extension note provided is incorrect. The handrails shall extend horizontally at least 12” beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser, IBC 1012.5. New: Looking over the different fire resistive rated construction, a couple of items should be addressed. Provide the Gypsum Association File Number for the one hour beam wraps, one hour floor ceiling assembly, and the one hour rated overhang from sheet A8. Provide a detail for each of the listed, tested assemblies. Typically one layer of gypsum surrounding a beam or column does not constitute one hour protection. Pat Lawler patrick.lawler@ci.edmonds.wa.us Plans Examiner 425 771 0220 x1703 Page 2 of 2