Loading...
09-0743 Isaacson #2 SFR-ESLHA.pdf Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Theresa Umbaugh 121 5th Ave N Edmonds, WA 98020 Re: Brian and Cindy Isaacson Residence rd 16007 73 Place West Edmonds, WA 98026 Plan Review # 2009-0743 EECE # EDM 09-18 (2) Plan review number 02 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back-check time. SCOPE OF REVIEW structural The scope of this review is for therequirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. Page 2 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 STRUCTURAL COMMENTS General 1.5. The design analysis for the stem wall used a depth to the tension steel of 6.16. However, the drawings specify 2” clear. Please resubmit an analysis with correct distance from the extreme compression fiber to the tension reinforcement. ACI 2.1 Sheet S-8 detail 4 states 2” clear but the analysis did not use this. The “d” shall be measured to the centroid of the tension steel. Please clarify where in the analysis this wall was analyzed with the decrease in the “d” to the reinforcement steel. 2.The design analysis in the response used surcharge forces over the heel to resist sliding. This is not conservative as per the response. Please resubmit the design analysis without the live load surcharge load to justify the wall will support the loads. IBC 1806 Sheet S0 General Notes 3.7. The design analysis used grade 60 for the #4 bars but the general notes state to use grade 40 for #4 bars. The retaining wall requires grade 60 steel for all reinforcement bars. Please modify the drawings or the analysis accordingly. It is not clear, based off the analysis submitted, where the number 4 are required to be grade 60 and where grade 40 may be used. Clarify where in the submitted analysis using grade 40 for the number 4 bars for the retaining wall will support the design loads. All that was noted in the response was this is for temperature reinforcement, however, the analysis submitted uses grade 60 and not grade 40. 4.The general notes reference the UBC which is not the currently adopted code. For example, under timber sections it states UBC. Modify all general notes to the current adopted code. Sheet S1 Schedules 5.9. Grade beams: Grade beams do not have any shear reinforcement as required for beam design. Please specify the shear reinforcement on the concrete grade beam. ACI chapter 11. The response states tie beams do not require shear reinforcement. Please clarify where, in the adopted code, that shear reinforcement is not required for these beams. Sheet S2 foundations Plan 6.12. The design analysis used the dead load and lived load at the center of the grade beam but the drawings show it at the edge. Please resubmit an analysis to Page 3 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 account for the load being applied at an eccentricity from the centerline of the grade beam. The response states the 1.6” is not significant. Submit an analysis to justify this is not significant. Sheet S-3 Main Floor Framing & Low Roof Framing 7.13. EOR, please specify the required collector elements for shear wall SW5 at the elevator. The response states see S7, but this does not show the required collector element to transfer the horizontal diaphragm force into the shear walls. Please add to the plans, the required collector elements and the attachment to drag the design force into these highly loaded shear walls. 8.14. EOR, please specify the required collector for shear wall SW5 at the entry. The response states see S7, but this does not show the required collector element to transfer the horizontal diaphragm force into the shear walls. Please add to the plans, the required collector elements and the attachment to drag the design force into these highly loaded shear walls. 9.16. EOR, please clarify the mark (7)6 or (3) 6 for the post supporting beams. It is not clear what posts/columns are required at these locations in order to check. The response states these are the posts within the wall that is supporting the beams. All post to beam connections shall be specified. Please add details for the beams that are supported by these multiple studs, and the required connections. 10.17. EOR, please specify the required floor joist connections. For example, the FJ1 to B13. The response state ISU1.81/11.88 but the beam mark B13 is low and not in the same plane as the floor joist. This is located near the stairway. 11.18. EOR, please specify the required floor joist connections to the interior wall. It is not clear what will be used at this location to support the design loads. The response states see new sections 10/S8 but this detail is not referenced to be used on this floor. Please add this detail reference to the plans to show the builder where this shall be used. 12.19. EOR, please provide a detail for the interior shear wall SW4. This is for floor joists FJ 2 and FJ1. The response states see new sections 10/S8 but this detail is not referenced to be used on this floor. Please add this detail reference to the plans to show the builder where this shall be used. 13.20. EOR, please specify the post/number of studs to support the beam mark B13 and low B11. The response states see revised plan. The revised plan states HUCTF which must be skewed. Per Simpson catalog hanger option matrix the HUCTF can Page 4 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 not be skewed. Please provide analysis and detail of how this member will be supported. Simpson Hanger Options Matrix 14.22. EOR, it is not clear what is supporting the beam mark B17. Based off the lower floor there is not any supporting member to support this beam. Note, not all beams were checked for vertical supporting members, so please verify all beams and joists for members to support them. Please provide a detail reference at this location for the support of this member. It is not clear based off the information provided. 15.24. EOR, please specify the required collector for shear wall SW4 at the 3’4 length wall in the garage. The drawings do not specify the required collectors nor the nailing required for this wall. The response just states see sections on plan sheet S7 for shear wall top connections to rim and blocking. But this will not transfer the load at this connection for this wall. Please add details at this wall and the plans to transfer the lateral diaphragm forces into this wall. Sheet S4 Upper floor Framing Mid Roof Framing 16. 25. EOR, please provide a detail at the column C6 where beams B5(5-1/8X12) and B8 (6-3/4X16-1/2) intersect this column. The connections specified in the schedule will not work for this location since the beams are different depth and different depth. Please modify accordingly. The revised drawings state to use HUC612. The beam B8 bears on the column. Therefore, the hanger will be end connected to the face of the glu-lam beam. Submit an analysis for the end nailing of the hanger to the edge of the beams will support the design loads per NDS. 17.28. EOR, please specify the required connections for the beam mark B13 to B13 at the stairs. Nothing is specified at this time. The response states the beam may be dropped. Provide a detail at this location to show these connections. 18.29. EOR, please provide a detail on the drawings for the joist being supported by the beams. For example, the FJ2 and FJ1 connection to beam mark B8. The response states see new detail 11/S8. Please reference the detail to the plans to show where this shall be used. 19.30. EOR, there is not any interior collector elements to drag the diaphragm forces in the interior shear wall. For example, shear mark SW4. The response states the rim joist and joist are the collector elements but the drawings do not reflect this. Please modify the drawings to clearly show the required collector elements and the connections required. Page 5 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 20.31. EOR, Please provide a detail for the joist framing over the stairs. The code requires a minimum head clearance of 6’8”. Based off the layout, this appears not to be able to maintain this head clearance. Please add a detail at this locations. The response states see architect for stair clearance but the floor plan and elevations do not reflect this based of the structural drawings. Please add structural detail to show proper head clearance. 21.At the stair, framing the floor joists are specified as FJ1, but based off the span the joist connections appears to require FJ2. Please submit an analysis to justify. 22.32. EOR, please provide a detail for the support of the RF1 located at header B11 located at the bedroom area. The roof is sloped but the beam is at floor line. Please add a detail to support the forces. A detail has not been referenced at this location to show the required support. The response states supported by B11. Add a detail at this location to show required vertical support. Sheet S5 High Roof Framing 23.34. EOR, please clarify where the T# information is specified. For example, T6 noted at the girder truss. The response states hold down schedule but this is being used at the girder. Provide a detail on the drawings for how this is to be used at this location. 24.35. EOR, please specify the required collector element for interior shear wall SW2. IBC 2305.1.2. The interior shear walls do not show any collectors aligned with the shear wall as noted in the response. Modify the drawings to clearly show the collector elements and connections to transfer the shear force to these elements. 25.The response specifies the interior shear walls are going to use the roof trusses to transfer the horizontal diaphragm forces. The trusses used at these locations are required to be designed for these forces. Currently this force is not specified on the drawings. Please add to the drawings the required collector force that the interior roof trusses used at the shear wall shall be designed for. This is required to be noted on the drawings. 26.36. EOR, please specify the required post under the GT truss and the connections. IBC 2303.1.6. The response states see revised drawings but the number of studs/post are not specified as the response implies. Please modify accordingly. Sheet S7 Sections & Details 27.39. Section 1: EOR please provide an analysis for the ledger connection nailed only to plywood to resist the design loads. The roof rafters are at 24” O/C but the Page 6 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 wall studs are spaced @ 16” O/C. Based off check analysis this detail will not support the design loads. Please justify with the analysis and modify detail accordingly. The response states the nails are to be installed in the studs. Submit an analysis for withdrawal lateral loads that will be applied to the ledger. Since the diaphragm is not continuous at this location, out of plans forces will be applied. Please submit an analysis for this connection to use nails to resist this force. 28.40. Section 8 (Section 7): This detail is on sheet S4. The joists are 2x10 but there are not any connections specified at the wall. Please specify the required connections. EOR, please submit an analysis for nails to resist the out of plan forces induced by the diaphragm. Sheet S8 Sections & Details 29.41. Sections 8: The design analysis for the typical retaining wall states slab is to resist sliding but there is not a slab to resist the sliding. Please submit an analysis for the wall without the slab resisting the sliding forces. The response states the typical wall does not use the slab but the analysis submitted for this wall shows the safety factor of 1.5 for sliding is not resisted. Please submit an analysis for the wall to resist this force. IBC 1806 30.42. Sections 8: EOR please clarify where the surcharge of 50 psf, over the heal, came from to resist the sliding force. The drawings do not reflect a surcharge. The response states this is a conservative design. However, the design analysis used this surcharge to resist sliding and overturning. This is not conservative under this use. Resubmit an analysis not including this surcharge force. IBC 1806, IBC 1604.2 and IBC 1604.4 31.43. Section 8: The design analysis used a clearance of 1.5” and not 2” as noted on the drawings. This is not conservative but less than conservative. Please modify analysis accordingly. The response states this is ACI standard for 4/S6. This is not the case. If the analysis used 1.5” clear it is not correct to specify 2” clear. Modify the drawings either to reflect the analysis of 1.5 or modify detail with supporting analysis. 32.44. Section 7: EOR, please provide an analysis for the ledger connections shown on this detail. In addition, are washers required? Please provide an analysis and modify details accordingly. The response states see general notes for washer. Also, please clarify what a KB bolt is. There are Hilti kwik bolt II but not KB bolts. Please modify and submit analysis in order to complete the review. Additional corrections may be required following receipt of corrections and additional information as requested. Page 7 of 7 Plan Review Number 02 EECE#: EDM 09-18 (2) Brian and Cindy Isaacson Residence 2009-0743 Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President