09-786 Pac Emerald SFR #1.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: 12/3/09 TO: Pacific Emerald Homes Inc PO Box 822 Edmonds, WA 98020 RE: Plan Check: BLD20090786 Project: SFR th Project Address: 808 9 Ave S During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1.Engineer of Record: a.Provide full size sealed and signed structural sheets including shearwall plan and details. If the engineer is willing to stamp and sign the sheets by the building designer, the details will need to be consistent with the engineering calculation package, e.g. 1/A-10 shows the three 6x6 posts as #2 grade unlike the engineering detail 4 shows a 6x6 #1 DFL column and there are shear transfer details on the plans that do not appear in the calculation package. The 6’ max height for the RSW detail #1 will need to be transferred to the full sized plan, or justified. b.Provide a full gravity analysis, and this will include comparing engineered truss drawings and the point load path from the girder trusses to the foundation. c.Indicate the min. 3”x3” x .229” plate washers for anchor bolts, or show where on the plans this is noted. Provide an anchor bolt minimum at non-shear wall locations. d.Provide shear wall to roof diaphragm details at both truss heel and rafter locations. 2.Provide an anchor bolt minimum at non-shear wall locations. 3.Due to the complicated nature of the roof system, and some apparent incongruities with the roof plan, provide engineered truss drawings from the truss manufacturer, including all girder trusses, hangers, and the truss layout. These drawings need to be stamped and signed by the truss engineer and provided to the EOR for the required gravity calculations. 4.Foundation vent calculations need to be performed using the net free ventilation area, which for a typical 8”x16” manufactured foundation vent has 73 net free square inches of ventilation, not 128 as indicated on plans. 5.Detail 3/A-9 does not provide the min standard hook extension into the foundation of 14” per R403.1.3 6.The 6x6 column in the garage is required to be pressure treated or elevated a minimum of 12” above the concrete slab per R319.1(4). 7.Garage floor slab to slope to door openings, R309.3. 8.Provide at least one full cross section from footing to roof, exterior wall to exterior wall. 9.Indicate roof pitches on roof framing plans. There appears to be something strange about beam #2, the 2x12 rafters, and the location of the hip. If the #2 beam is the hip beam, it will only work in that location if only if both pitches are the same. Hopefully the truss engineering plan will help to clarify this anomaly. 10.A smoke detector is missing from the “immediate vicinity” outside bedroom #2. Pat Lawler patrick.lawler@ci.edmonds.wa.us Plans Examiner 425 771 0220 x1703 Page 2 of 2