10-0006 Michel 316 Walnut HVAC .pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: 1/11/10 TO: Michel Construction th 7907 212 St SW #102 Edmonds, WA 98026 RE: Plan Check: BLD20100006 Project: HVAC Project Address: 316 Walnut St. During review of the re-submitted plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1.Indicate on the plans the size and location of the kitchen hood exhaust ductwork. Bear in mind that the stairwell walls are a vertical exit enclosure and cannot be penetrated by the ductwork per IBC section 1020.1.2 2.Provide cut sheets for the firestop products proposed for all penetrations requiring a firestopping system. 3.Units 202 and 302 both need to have min. 50 cfm fans in the separate master toilet rooms. 4.How are the rated horizontal assemblies to be protected at the fan and duct penetrations? If the fans will have radiant ceiling dampers provide the product data. If the fans enclosures will have gypsum boxes built around them, provide a construction detail. 5.For all membrane and through penetrations provide the listed, tested firestopping product data. 6.The “shafts” that the vents are proposed to be enclosed in will need to be built as shafts per section 707 if the floor/ceiling assembly is not complete and firestopping provided at each penetration. 7.Indicate the piping size and material of the hydronic piping from the water heater to the heating units. 8.Indicate the hydronic piping insulation. Pat Lawler patrick.lawler@ci.edmonds.wa.us Plans Examiner 425 771 0220 x1703