Loading...
11-0078 QFC Mechanical.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: 2/10/11 TO: Refrigeration Unlimited 5440 S. Proctor Tacoma, WA 98409 RE: Plan Check: BLD20110078 Project: QFC Mechanical th Project Address: 22828 100 Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1.Provide two sets of the omitted plan sheets R2.2, R2.3, R4, R5, and R6. 2.Phasing Notes indicates air handler to be removed and replaced with roof top units prior to commencement of work. Has this occurred, or are new rooftop units going to be installed? If new units are to be installed, a permit is required prior to the work being performed. City records indicate that a permit was issued on 7/25/2010 to install a rooftop AC unit, and that permit shows that work has been completed. 3.Were plans prepared by a mechanical engineer? If so, a stamp and signature showing licensure for the state of WA is required. Pat Lawler, CBO patrick.lawler@ci.edmonds.wa.us Plans Examiner/Building Inspector 425 771 0220 x1703