11-0255 Picket remodel.pdfof EDVo City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION �sr. i s90 (425) 771-0220 DATE: 4/18/2011 TO: Eric Koch Partners Architectural 16398 NE 85" St Ste 101 Redmond, WA 98052 RE: Plan Check: BLD20110255 Project: Picket Remodel Project Address: 823 Alder St During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1. Include interconnected smoke detectors throughout the existing residence at the bedrooms and immediate vicinity outside, per R314.3.1. 2. The storage room adjacent to bedroom #5, lower level would be considered a bedroom and is required to have an emergency egress opening. If the room does not have a closet, then it would not be considered a bedroom. 3. Engineer of Record: a. The longer flights of stairs appear to have overspanned stair jacks. Either provide center span supports, or calculations to show the code deflection standards will be met. b. Provide calculations for the 2x10 joists and 4x12 beam for the small deck. The typical 2 to 1 minimum backspan is not observed. Indicate connection hardware, lumber species and grade. c. Are the doubled 4x 14 beams to be going to be connected to each other? If so, how? If not, should the plywood diaphragm break occur at a location other than the between the two beams? 4. A guard is required at the new front stairs, but is not shown on the elevation sheets. Pat Lawler, CBO patrick.lawler@ci.edmonds.wa.us Plans Examiner/Building Inspector 425 7710220 x 1703