Loading...
12-0858 Plan Review Comments.pdfCITY OF EDMONDS • 121 5" AVENUE NORTH • EDMONDS, WA 98020 j PHONE: 425.771.0220 • FAX: 425.771.0221 • WEB: www.edmondswa.gov DEVELOPMENT SERVICES DEPARTMENT: PLANNING • BUILDING November 20, 2012 James Thomas, Architect jthomas@arch-design.net RE: PLAN REVIEW COMMENTS FOR PLAN CHECK # 2012-0858 NEW SFR AT 15500 75TH PLACE WEST Dear Mr. Thomas, I have reviewed the above building permit application for the Planning Division. Before I can sign off on the permit, however, the following information needs to be clarified in a written response: 1. Driveway/bridge: The proposed driveway/bridge approach is greater than 3' above original grade within the required 25' street setback. Unfortunately, this design is not code -compliant. Structures may not be taller than 3' within a required setback unless excepted in ECDC 16.20.040 or 21.90.150. There are two options for moving forward: applying for a variance to reduce the 25' street setback to allow placement of the bridge as proposed, or redesigning the project to accommodate a code -compliant driveway approach. See ECDC 20.75 for code requirements about variances and or ECDC 18.80.060 for further requirements for driveways. Redesigning or relocating the driveway and residence may result in changes throughout the site; keep in mind the critical area mitigation sequencing criteria in ECDC 23.40.120 as you consider any changes. When resubmitting (or with the variance application, as appropriate), please include a cover letter describing how the mitigation sequencing criteria were evaluated relative to the selected design. Finally, any changes would have to be addressed by the geotechnical engineer. Below are additional comments which should be considered during the redesign of the project. Grading: Because a portion of the project site is within 200' of the Ordinary High Water Mark (OHWM) of Puget Sound, the Shoreline Master Program of Chapter 23.10 ECDC applies. The site is designated Suburban Residential I in the code. A single family residence in this area is exempt from a Substantial Development Permit if the unit is owner -built in accordance with WAC 173.27.040(g); however, grading for appurtenances in excess of 250 cubic yards would be subject to permit if it occurs within 200' of the OHWM. As proposed, grading is shown to be 740 cy of cut and 370 cy of fill. It is unknown if the grading will be inside or outside the 200' boundary of the OHWM and if it would be for the main house or appurtenances. As a result, please update the site plan (SP1.0) and the related engineering plans (Sheet Cl) to show the 200' distance from the OHWM. Call out the amount of grading occurring both inside and outside the 200' boundary on the engineering plans and describe whether the purpose of the grading is for the house or the garage, driveway, decks, utilities, or fences, etc. 3. Structural lot coverage: On the site plan, please provide a structural lot coverage calculation for the proposal, breaking out the individual items contained in the calculation. ECDC 21.15.110, "[c]overage means the total ground coverage of all buildings or structures on a site measured from the outside of external walls or supporting members or from a point two and one-half feet in from the outside edge of a cantilevered roof, whichever covers the greatest area." 4. Height calculations: Please move corners B and C of the height rectangle slightly to the west to enclose the dining room bump out. Make any adjustments necessary to the height calculations on the site plan as well as the building plan elevation sheets (A1.0 and A1.1). Also on the elevations, please show the lines of average original grade, proposed elevation, and maximum allowed height for the project. 5. Setback encroachments: Two proposed setback encroachments do not appear to meet code requirements: a small section of eave at the northeast corner of the house and the eastern steps and entry area. For eaves, according to ECDC 16.20.040.13, "eaves and chimneys may project into a required setback not more than 30 inches." The eave at the northeast corner of the house appears to project into the setback more than 30 inches. For porches, ECDC 16.20.040.0 states, "Uncovered and unenclosed porches, steps, patios, and decks may project into a required setback not more than one-third of the required setback, or four feet, whichever is less; provided, that they are no more than 30 inches above ground level at any point." The eastern steps and entry are within the required 25' street setback area. As a result, the steps and porch may only encroach 4' into the setback (using the lesser of 4' and 8.3'). Please verify and revise the site and building plans accordingly. If the variance course is chosen for the driveway/bridge, these encroaching features could also be included. 6. Tree retention and mitigation plan: a. Trees 347, 349 and 385 appear to be on the property line with County Park adjacent to the north. Please submit signed confirmation from Snohomish County that removal of these three trees is acceptable and whether any specific replacement is required. b. Tree 320 is identified as to be removed on Sheet L2.0. However, the tree matrix on the same sheet indicates that the tree has good vigor and average structure, despite having co -dominant leaders. It would seem that this tree might be a good candidate for retention with appropriate maintenance and/or bracing. c. It is assumed that those living and dead trees to be removed from within the identified clearing limits will be removed from the site. Tree 381 is dead but falls outside the clearing limit. Confirm whether this tree will be left onsite or removed in accordance with ECDC 23.40.220.C.7.b.iii. d. Sheet 1-1.0 shows 21 replacement trees as opposed to the 22 described in the mitigation calculations. 7. Geotechnical setbacks: On the site plan, please show the top of slope and the setbacks as determined by Nelson Geotechnical Associates on page 8 of their July 15, 2011 report. It should be noted that separate buffer and setback distances are required in accordance with ECDC 23.80.070 (buffers) and ECDC 23.40.280 (setbacks), unless otherwise provided. 8. Clearing limits: The clearing limits shown on Sheets C1 and L2.0 do not match. Please update the limits on L2.0 to show the location of the proposed drainage pipe. All referenced code sections are available at the following website: http://www.mrsc.org/mc/edmonds/Edmondsnt.html. Please submit three copies of your updated site plan (one being reduced size of 11 x 17 or smaller) and two sets of any updated sheets of the building plans. Please make all submittals to a Permit Coordinator, Monday through Friday, 8:00 am to 4:30 pm. If you have any questions, please contact me at (425) 771-0220. Sincerely, tc Mike Clugston, AICP Associate Planner