Loading...
16111 75TH PL W.PDF11111111111111 14850 16111 75TH PL W • Bullis, Ann From: Westfall, John Sent: Tuesday, May 27, 2003 1:50 PM To: Bullis, Ann Cc: Smith, Mike Subject: Meadowdale Marina 16111 75th PI W Milo was in this day with his architect and engineer to discuss fire protection and access issues for the future marina development. Regarding fire access: Milo wishes to "overbuild rather than underbuild". The existing property appears to have been sprinklered due to lack of required access. Milo discussed considerations for providing access to the pier. I indicated the live loads must accommodate our fire apparatus and the width of the causeway must be minimum 20'. If access is provided, using the former logic, the building would not require a sprinkler system UNLESS the new occupancy might require it. Being proposed are replacing wood with steel columns and providing a concrete deck for a noncombustible pier. Shoreline management/property upgrade issues are well in the spotlight. Regarding fire protection: Hopefully the corroded, leaky portion of the existing sprinkler system came down with the old building. There is an encapsulated 8" line that has never frozen (to my knowledge) for fire suppression purposes. No pedestrian/firefighter access would be provided around the exterior due to seaside coverage from ? A standpipe would be a reasonable accommodation whether access is provided or not. John Fire Department notes: Requirements from UFC 902.2.1 Access and ECDC 19.65 Marinas. Check NFC and other standards if plans make it that far.