Loading...
170623_Westgate Edmonds - Permit Correction Response.pdf 1511 THIRD AVENUE SUITE 323 SEATTLE, WA 98101 TEL 206.957.3900 FAX 206.957.3901 www.quantumce.com June 23, 2017 Douglas Beck Beck & Associates, PLLC 16425 SE 66th Street Bellevue, WA 98006 Subject: Permit #2016-1538 – Westgate Village Quantum Project #16369.01 Dear Douglas: We have received the correction notice on the above-referenced project dated April 12, 2017. Below are the responses to the structural comments. All changes to the drawings due to a plan check comment have been clouded on the drawings and marked with a Delta 1. * * * * * GENERAL Geotechnical 1. The geotechnical engineer, PanGEO is required to review the plans to confirm that their recommendations are properly incorporated into the design and construction drawings (p. 12). The review, along with any additional recommendations, shall be summarized in letter format. It is our understanding that PanGEO will review the design drawings prior to the start of construction to verify that the recommendations of the geotechnical report match what is shown on the drawings. LATERAL General 2. Both the wood shear wall system and the concrete shear wall systems have Horizontal Structural Irregularity #5, Nonparallel System Irregularity. Provide calculations to demonstrate that the requirements for this irregularity are met. ASCE 7-10, Table 12.3-1 Additional seismic load combinations for orthogonal effects (100% + 30%) have been analyzed for the structure per the requirements of ASCE 7-10, section 12.5.3a. Please see the attached calculation pages (1 to 7) for the updated load combinations and wood shear wall results. Permit #2016-1538 – Westgate Village June 26, 2017 Page 2 The concrete shear walls at Level 1 below the transfer podium slab were originally designed for the orthogonal effects required by ASCE 7-10, section 12.5.3a and table 12.3-1. Refer to the original calculation pages (CL-12 to CL-18) for the load combinations used for design. 3. Provide calculations to demonstrate that allowable story drifts are within the limits of ASCE 7- 10. ASCE 7-10, 12.12 Please see the attached calculation pages 8 (wood floors) and 17 to 19 (L2 conc. slab) for the building story drifts. The story drifts are within the allowable limits. 4. Provide calculations for chords at the following locations. ASCE 7-10, 12.10 a) Wood levels – It is apparent that the double top plate will serve as the chord. In some cases, there is a discontinuity in the double top plate of exterior walls where the exterior wall jogs. Please address these conditions. b) Concrete levels a) At the wood levels, the top plate is adequate for the chord forces between the perpendicular shear walls. Please see the attached calculation page 9. Where ever the exterior wall jogs, there is typically a perpendicular shear wall, so no drag struts are needed for the discontinuous top plates to transfer loads into the floor diaphragm. b) At the concrete transfer slab (L2), the continuous slab edge reinforcement is adequate for the chord forces as shown on the attached calculation page 20. 5. Provide calculations to demonstrate that the Level 2 PT deck and connections have adequate strength to transfer forces to the concrete shear walls. Are collectors required at any locations? ASCE 7-10, 12.10 Refer to the attached calculation pages (21 to 23) for the shear transfer analysis between the concrete slab and shear walls. The slab dowels shown in the typical concrete details (S303) are adequate to transfer the lateral forces between the slab and walls with no additional collectors or reinforcement required. Lateral – Wood 6. The diaphragms of the wood levels are permitted to be idealized as rigid when the computed maximum deflection of the diaphragm itself under load is less than or equal to two times the average deflection of adjoining vertical elements of the lateral force-resisting system of the story. Please provide calculations that demonstrate that this criteria is met for each level. SDPWS 4.2.5 Please see the attached calculation page 10. As shown, the diaphragm deflections are much smaller than the shear wall deflections; thus, the upper wood floor diaphragms are assumed to be rigid for the design. Permit #2016-1538 – Westgate Village June 26, 2017 Page 3 7. It is unclear from the calculations whether accidental torsion is considered in the analysis for the semi-rigid/rigid analysis being used. Please provide documentation that demonstrates accidental torsion is being considered. ASCE 7-10, 12.8.4.2; SDPWS 4.2.5 Please see the original calculation page WL-11 for the accidental torsion input (5%) in each direction at the floor diaphragms. 8. Provide calculations to check for torsional irregularity for each level of the wood lateral force- resisting system. If torsional irregularity does exist, provide calculations to demonstrate that amplification of accidental torsion is considered and the criteria of SDPWS 4.2.5.1 are met. ASCE 7-10, 12.8.4.3; SDPWS 4.2.5.1 Amplification of accidental torsion is not required. Please see the attached calculation pages (11 to 14) for the torsional irregularity analysis at the upper wood floors. DRAWING SHEETS S100 – Structural General Notes 9. Reference the Design Criteria. It appears that the Wind Base Shears identified in the General Structural Notes are inconsistent with the analysis provided. Please coordinate. The wind base shear on sheet S100 has been updated to reflect the base shear for the entire building. Please see the attached calculation pages (15 & 16) that show the base shear for the entire structure vs the base shear for just the wood levels. 10. Note #13, Special Inspections, is general in its requirements for special inspections. The plans need to specify the required inspections and testing and extent of inspections or testing for each material. The statement of special inspections is required to identify the following: 1704.2.3, 1704.3 a) The materials, systems, components, and work required to have special inspections or tests. b) The type and extent of each special inspection c) The type and extent of each test d) Additional requirements for special inspections or tests for seismic as specified in 1705.12 and 1705.13. e) For each type of special inspection, identification as to whether it will be continuous, periodic, or performed in accordance with the notation used in the referenced standard where inspections are defined. The Special Inspections note (#13) has been revised on sheet S100 and a Special Inspections schedule has been added on sheet S102. 11. Reference the Geotechnical Section, #16. a) An allowable soil bearing pressure of 6,000 psf is not included within the geotechnical report. Provide documentation from the geotechnical engineer regarding the use of a 6,000 psf Permit #2016-1538 – Westgate Village June 26, 2017 Page 4 bearing pressure. Revise the foundation design as required (some of the foundations are currently designed based on an allowable bearing pressures of 6,000 psf). b) The passive soil pressure (350 pcf) includes a factor of safety of 2. This should be identified on the drawings. c) The soil coefficient of friction (0.50) includes a factor of safety of 1.5. This should be included in the drawings. a) It is our understanding that PanGEO will be providing a letter that indicates the use of 6,000psf for allowable soil bearing at the lower parking level based on previous correspondence during the project design phase. The General Notes (S100) and Foundation Plan (S200) have been revised to clearly show all the footings that were designed for 6,000psf allowable soil bearing. b) The passive soil pressure note has been revised on the General Structural Notes. c) The soil coefficient of friction note has been revised on the General Structural Notes. S200 –Parking Level / Foundation Plan 12. Foundation Plan Notes #5 should also reference the geotechnical report for subgrade preparation and vapor barrier recommendations (p. 9). The Foundation Plan Note (#5) has been revised. S201A – Level 1 Framing / Mild Reinforcing Plan 13. A discontinuous shear wall occurs at the shear wall located along grid C3 between grids CD & CE. Also reference 6/S303. This is considered to be an In-Plane Discontinuity in the Lateral Force resisting System. Please address this condition and demonstrate compliance in accordance with ASCE 7-10. ASCE 7-10, Table 12.3-2 The Level 1 framing plans have been revised to remove the discontinuous shear wall at the stair location. The wall at this location will either be a non-bearing concrete or CMU partition wall to separate the stairs from the parking area. Refer to the attached calculation page 21 for the updated shear wall forces without this wall. By inspection, the remaining shear walls are adequate to resist the slightly increased lateral forces. 14. Reference the column located at grids CB/C3. According to the calculations, top reinforcement in the E-W direction is required to be 8#6T (p. PT-139). Please coordinate. The structural plan (S201A) have been revised to show the correct top reinforcement to match the calculations. S202A – Level 2 Framing / Mild Reinforcing Plan 15. Reference the attached 11x17 plan with redlined mark-ups. There are numerous differences between the plans and the analysis. Provide coordination and address each item. I have provided references on the marked-up plan to corresponding calculation pages. Permit #2016-1538 – Westgate Village June 26, 2017 Page 5 The structural framing plan (S202A) has been revised to show the correct slab reinforcement and has been further coordinated with the calculations. Refer to detail 18/S302 for the concrete beam reinforcement at the Level 2 transfer podium. S202B – Level 2 Framing / Post-Tensioning Plan 16. Reference Post-Tensioning Plan Note #9. This slab is actually required to be designed to have a 3-hour rating. Clearance requirements are met with the current design. However, the note should be updated to identify the correct rating. The plan note (#9) on sheet S202B has been revised. S202C – Level 2 Wood Framing Plan 17. The shear wall located approximately along grid C10 between grids CH and CJ is required to be provided with DF studs according to the calculations (p. WL-30). Please coordinate. Notes specifying DF#2 studs at holdown posts have been added to sheet S202C and detail 20/S400. S203 – Level 3 Framing Plan There are a couple of areas on this level which have gravity loads which are unsupported from above. Please address the following areas: 18. Reference the attached pdf showing a Partial 3RD Floor Framing Plan from S203, labeled ‘Area 1’. Please address the locations indicated where loads are unsupported from above. The roof loads are transferred at the Level 4 framing (S204) where the walls don’t stack below. All the remaining bearing walls stack at each level down to the concrete transfer slab. At the Level 4 framing, blocking has been added between the joists for the short exterior walls at the amenity spaces. The long wall at the corridor has been shifted to align with the walls below. Please see sheet S204 for the framing revisions. 19. Reference the attached pdf showing a Partial 3RD Floor Framing Plan from S203, labeled ‘Area 2’. Please address the locations indicated where loads are unsupported from above. Refer to the response for comment #18 (similar framing revision). S204 – Level 4 Framing Plan There are a couple of areas on this level that support deck loads of 100 psf. It appears that the joists are undersized. 20. Reference the attached pdf showing a Partial 4TH Floor Framing Plan from S204, labeled ‘Area 1’. Please address the locations indicated where joists are required to support a 100 psf live load. Hatching has been added to the framing plan (S204) to indicate where the 100psf live load occurs. The floor framing has been designed and revised accordingly. Permit #2016-1538 – Westgate Village June 26, 2017 Page 6 21. Reference the attached pdf showing a Partial 4TH Floor Framing Plan from S204, labeled ‘Area 2’. Please address the locations indicated where joists are required to support a 100 psf live load. Refer to the response for comment #20 (similar plan revision). S301 – Typical Concrete Details 22. Reference 6/S301 – Typical Site Retaining Wall. PanGeo recommends that Mirafi 6000 or equivalent be provided at the face of the wall in order to prevent the potential build-up of hydrostatic pressures. This should either be specified on the detail or the geotechnical report should specifically be referenced for backfill and drainage recommendations. (p. 8) Detail 6/S301 has been revised to include the note for the drainage material behind the retaining wall. S303 – Concrete Details 23. Reference 1/S303 – PT Slab/Slab-On-Grade Transition. Detail 18/S301 is referenced. It appears the reference should be to 17/S301. Please coordinate. The note has been revised to indicate the correct detail reference. Please refer to detail 2/S303. * * * * * Please feel free to call me at 206-957-3900 if you have any questions regarding our responses. Sincerely, Quantum Consulting Engineers, LLC Todd Schoentrup, P.E. Senior Project Engineer