City of Edmonds JUL 16 2019
o
E3u!inMc orrnRTn4Erv1
PLAN REVIEW COMMENTS C1 IN OF en
BUILDING DIVISION
CSC. g9° (425) 771-0220
DATE: July 1, 2019
TO: Tom Budinick
Email: tbudinick0mbudinickassoc.com
FROM: Leif Bjorback, Building Official
RE: Plan Check: BLD2019-0702
Project: Restaurant expansion into adjacent suite
Project Address: 190 Sunset Ave
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses to each comment, and submit
revised plans/documents to a permit coordinator in the Development Services Department.
1. A complete review by the Building Division cannot be performed until the following
documents
are provided and changes made:
Provided a Floor plan for the enure '
a,
y�
y p In addition to the floor plans already provided for the work area, provide a
partial
restaurant shown on page A_01,
r
r-
,including occupant loads as provided
floor plan including the layout of the entire restaurant. The layout does not need to
in the original TI in 2016:
BDL2016-0222
show extensive detail of the existing unchanged areas except for the square footages
and occupant loads of each space, and the overall egress system for the suite.
°. Completed on "'�' A.°1
Label the use of each room or space.
c. The occupant load clacs are shown "C,.�
On sheet a01, provide new occupant load calculations, showing a breakdown
:table on A.M. Itemized by existing
restaurant space and proposed TI
including each room or space, with a proposed occupant load total for the entire
space. The total occupant load for the
entire restaurant is662.
interior of the restaurant. It is advisable for you to reference the calculations for the
previous work completed under permit BLD2016-0222 as applicable.
d. Lighting design completed for the d:
Due to the alterations and the partial change of occupancy/use of this project, a
existing space (E.01) and the
TI E.01 design was
lighting design will be required for the complete restaurant, complete with fixture
proposed (E.02).
approved in2016: BDL2016-0222.
wattages and lighting controls sufficient to show compliance with WSEC C405.
Energy forms are attached to the -e. Provide energy forms for Lighting in support of the required lighting plan in item (d)
resubmiltal set
above.
Thank you,
Leif Bjorback, Building Official
City of Edmonds
(425) 771-0220
Lei f.biori back(u edmondswa.sov
Page 1 of 1