Loading...
1861_001.pdf�Iat)0 j-,qjrj -14�qq- FIR s &A 4�4a-r DIS R T 1�00b 'r Fire Alarm Checklist Name of Building or complex Date Z-7 - I Address ?Z6711 2U -Ai 10i) Permit number.4-D Zlil Y 6)0�1_--? Fire alarm system complete andX Fire alarm system pre -testing complete Building occupants (if applicable) notified of fire alarm testing XS stem is in test mode [ noCom has been notified nox box has been provided 1,11 YS P rRie"mote annunciator is properly located, accessible, not obstructed and conforms to approved plans — f.3 P&ft-t- d"A 7-r-O AJ Q-r F"10 , &) 1A, A -9 DOOR 1% p,""Fire alarm control panel is properly located, accessible, and 6o-t—o-b—structed and conform to pproved plans. 3 Approved signage has been provided. This includes signage to specific locations and specific 7 feat es. ( ie. Dry Standpipe and FDC) ovide the alarm monitoring company's name and 24 hr number on the control panel. Monitoring company's name &fid/M a-,u zc& HAP,-rovide a manual pull station reset key(s) as needed for the Knox box. jd ystem loss of ac power, :VAES check list completed verify operation standby power (on reverse side) 0 Fire alarm control panel circuit breaker shall be labeled FACP, painted red, and locked in the ON position. 0 Fire alarm panel shall indicate what circuit breaker supplies power and the location of the panel where that circuit is located. r�eck a random selection of initiating devices (minimum of 25%) Activation of audible, visual and audible / visual devices. Verify visual synchronization "r), itside horn / strobe activation and location YVerify alarm, supervisory, and trouble retransmission signals to monitoring station e equire Certificate of completion m installer - WTJ_L iCiaArL, Signature of Fire Official 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrictl.org SNOHOMISH CO. FIR DIST ICT Wireless Mesh Network (AES) Installation Inspection Checklist All AES radio transmitters shall be installed and inspected according to NFPA 70, NFPA 72, WAC, manufacturer requirements/recommendations. /The AES Radio is mounted near the FACP in a temperature controlled environment. If it is mounted on the interior side of an exterior metal, concrete, or block wall it is mounted on an insulating board to prevent direct contact with moisture or temperature extremes. Alternate locations, if approved by the fire marshal may require the AES Radio to be located inside a lockable NEMA 4X enclosure with smoke detector and thermostatically controlled heater. V/`AES routing table shows a minimum of two (2) "good" paths with a net -con of 0-5 prior to connecting to FACP. /AES is protected by a smoke detector. %�XAA/C transformer to AES is protected inside a secured transformer enclosure. /The A/C transformer is one of the following 3 models; AMSECO model XF1640, Elk Products model TRG1640, or MG Electronics model MGT1640. ,Q--116ires from A/C transformer enclosure to AES enclosure are in conduit. V,---AES is powered via dedicated A/C circuit or shared with a dedicated circuit to FACP. /A C breaker to AES circuit is labeled and provided with a lock -on device. '-' �l ./All exposed wiring below seven feet (7') AFF is protected in conduit. Coaxial cable outside the AES enclosure is installed in conduit. Apir Exterior antennas are protected by a lightening arrester. Arrester is located a minimum 6'from AES radio and Irounded to earth with a minimum 6 AWG copper wire. .0, All bends in the coaxial cable outside of the AES enclosure (if applicable) have a minimum six inch (6'� radius. OES AND IntelliPro Fire or FireTap (if installed) is locally supervised at the protected premises (both audibly and visibly) in an approved manner for antenna cut, low battery, communication troubles, and charger fault as a s se 6rate zone or address on the FACP. (14 outputs) aGerneral alarm (zone 1), general trouble (zone 2), and supervisory (zone 3) outputs from the FACP are connected 0 _ to supervised input zones on the AES. p,""All zones, signals, or addresses capable of being transmitted by the FACP are transmitted to the central station. T is may require an IntelliPro Fire or FireTap. Co A current Routing Table showing the NetCon, Link Layer, and Signal Strength (minimum 2 "Good" paths with a miI minimum NetCon of 5 or less) is to be provided to the Fire Inspector at time of final inspection. 12425 Meridian Avenue S / Everett WA 98208 / 425-551-1200 www.firedistrictl.org