Loading...
19. Glu-lam Alternate Methods Letter.pdfSALUS HEALTHCARE ARCHITECTURE June 18, 2018 Leif Bjorback Linda Thomquist City of Edmonds, Development Services Department 121 5th Ave N Edmonds, WA 98020 Subject: Edmonds Recovery Center - Northpoint Recovery Remodel of Edmonds Facility - 7416 212th Street SW Alternate Methods for providing glu-lam fire rating - Letter of Rationale Permit # BLD2018-0447 Dear Leif This letter concerns Beck & Associates Northpoint Recovery comment #1 9a: "Provide documentation that demonstrates that all of the glulam beams maintain a 1-hour rating, consistent with the floor -ceiling assembly rating. ff this cannot be provided, an alternate means ofproviding the 1-hour rating at the glulam beams is required to be provided" The Code Issue: Since there does not appear to be a rated listing for gludams we cannot met the code prescriptively, we are submitting an "alternate method of construction (I BC 104.11)" for your review. Code requirements for Floor Assemblies in a Type VB. This building is a VB fully sprinklered. The Occupancy is 1-1 Condition-2 IBC Section 420.3 Horizontal Separation "floor assemblies separating sleeping units from other occupancies contiguous to them shall be constructed as horizontal assemblies in accordance with Section 711. IBC Section 711.2 Horizontal Assemblies shall comply with Sections 711.2.1 through 711.2.6. IBC Section 711.2.3 Supporting Construction shall be protected to afford the required fire-resistant rating of the horizontal assembly support. Exception (to 711.2.3) in buildings of VB construction the construction supporting the horizontal assembly is not is not required to be fire -resistance rated at the following: Exemption#2 - Horizontal assemblies at the separation at the separation of sleeping units as required by Section 420.3. Code Requirement (711.2.3)for floor rating: This part of the code appears to allow a non -rated floor assemblv. 1402 Third Ave, Suite 200 / Seattle, WA 98101 / T 206.652.0722 / F 206.340.2266 / wwwsalus.arclhi Mr. Leif Bjorback J u ne 18, 2018 Page 2 Code requirements for Floor Assemblies with smoke and fire partitions The IBC requires both 1 -hour smoke barriers (Section 709) and fire partitions (Section 708) in this project. In Sections 708.4 Continuity: "fire partitions shall extend to the underside of the fire resistance -rated floor or roof assembly". In Sections 709.4 Continuity: "smoke partitions shall extend to the underside of the fire resistance -rated floor or roof assembly". Code Requirement (708.4 and 709.4) for floor rating: This part of the code appears to require a rated horizontal assembl . Glu-lam Fire Resistance: We looked at what sort of fire resistance the gludams have: - To determine strength of the glulam after charring has occurred, we used the APA Engineered Wood Association Technical Manual: "Calculating Fire Resistance of Glulam Beams - EWS Y24513". (APA is located in Tacoma WA. Phone: #253-565- 6600) - Per the Technical Manual, the char -rate thru the glulam is at 1/40" per minute or 1.5" of glu-lam per 60 minutes. - Per the Technical Manual, the char -rate thru the glulam is at 1/40" per minute or .75" of glu-lam per 30 minutes. Glujams that support the second floor: The gludams that support the second floor are 63/4" wide x 31 " high. However, only the lower 17" of the glu-lam are exposed because the adjacent 1 -hour rated floor assembly (see attached detail SD2.01) covers the rest of the gludam. Grea Lee of ABKJ Structural Enaineers (See attached letter dated 6-18-2018) evaluated the exposed 17" of this glu-lam and found that the 2nd floor glu-lam can handle 30 minutes of charring and still support unfactored (service level) loads at the factored or ultimate stress levels. Since there isn't a UL listed method to provide a rated enclosure for the additional 30 or 60 minutes of coverage, we propose three alternate method options: Brian Perry (Product Engineer for Albi Protective Coatings) attached letter (6/15/2018) states: "Based on the technical Note #EWS Y2445B from the APA — Engineered Wood Association, the fire resistance rating up to 1 -hour can be calculated for glu-lam members. This method is recognized by the International Building Code. Based on the calculations, the 6 3/3" x 31 " glu-lam has a fire resistance rating of 58 minutes and the 5.5" x 27" glu-lam has a fire resistance rating of 53 minutes. These calculations were made assuming the beams would be carrying 100% of their maximum design load. Mr. Leif Bjorback J u ne 18, 2018 Page 3 Glu-lam Fire Resistance Conclusion: Based on Greg Lee and Brian Perry's letters, it appears the exposed glu-lams will not be able to provide a 1 -hour fire resistance. However, the glu-lams will provide at least 30 minute or greater resistance. The following are (3) Options for an "alternate method of construction (IBC 104.11)" to comply with the intent of the provisions of the code. Of the three Options below, Salus prefers Option #1 for ease of assembly and as it is the least expensive. OPTION#1 (see attached detail) - Provide (2) layers of 5/8" Type-X GWB on 1/2" metal clips on the three exposed sides of the gludam. This assembly matches the one -hour rated ceiling assembly (UL L570) shown on Detail 7/A9.01 which is located on either side of the gludam. (See attached Detail SD2.02) OPTION #1 Rationale: If a fire (in a fully sprinklered building) can penetrate (2) layers of GWB enclosing the gludam, it would also be able to penetrate the (2) layers of GWB in the rated floor assembly on either side of the gludam. If (2) layers of rated GW13 are sufficient for the 1 -hour ceiling assembly, then (2) layers of rated GWB and the 30 minutes of fire resistance provided by the gludarn should be sufficient to provide the lower 17" of gludam with at least 60 minutes of protection. Sealant where glu-lam meets the horizontal GWB assembly: Spec seal-SSS or LCI Sealant sealant will be installed. (See attached "engineered Judgement Firestop Detail" NS14918024) This sealant can also be applied when the glu-lam is enclosed with rated GWB. OPTION#2: Provide 1 -hour shaft wall (UL Des U469) on the on the three exposed sides of the glu- lam. (See attached detail SD2.03) OPTION #2 Rationale: Rated shaft wall is used thru-out this country to provide fire rated protection and should be more than sufficient to provide 60 minutes of fire resistance for the glu-lams. OPTION#3: Provide 40 mils WFT (28 mils DFT) of Albi Clad FT of intumescent paint over the exposed sides on the three exposed sides of the gludam. (See attached Detail SD 2.04). OPTION #3 Rationale: - See attached Albi Brochure for basic product information. - See attached letter (dated 6/15/2018) from Brian Perry (Product Engineer for Albi- Protective Coatings) which states: Mr. Leif 13jorback J u ne 18, 2018 Page 4 Albi would recommend applying 40 mils WFT (28 mils DFT) of Albi Clad FP to protect the exposed glulam beams and deck in place of using gypsum to provide a 1-hour fire resistance rating, This judgement is based on Western Fire Center Inc, Report # 04042(a), where 40 mils WFT of Albi Clad FP is specified for a 1 hour rating on an open wood floor joist assembly featuring 2"x10" joists and a deck of TG subfloor and CDX plywood. Based on the Technical Note #EWS Y245B from the APA - Engineered Wood Association, the fire resistance rating up to 1 hour can be calculated for glulam members. This method is recognized by the International Building Code. Based on the calculations, the 6"x3l" beam has a fire resistance rating of 58 minutes and the 5.5"x27" beam has a fire resistance rating of 53 minutes. These calculations were made assuming the beams would be carrying 100% of their maximum design load. Based on this, 40 mils WFT of Albi Clad FP applied to the exposed glulam beams will provide the extra time necessary to achieve a 1 hour rating, Please note that Albi does not have any direct test data for Albi Clad FP over glulam beams and this judgement is based on an established calculation method and indirect test data. Option #3 Conclusion: Combining 40 mils of intumescent paint with the at least 30 minutes of fire resistance provided by the glu-lam should be more than sufficient to provide 60 minutes of fire resistance. Please review these three options and let us know if you have any questions. Thank you for your consideration. Douglas McNutt Principal 1402 Third Avenue, Suite 200 Seattle WA 98101 Cell: 206 605-5597 Direct: 206 957-1906 Office: 206 652-0722 Fax: 206 652-0720 Email: douglas.mcnuttasalus.archi Web: www.salus.archi 0o, SALUS HEALTHCARE ARCHITECTURE Encl: Details SD2.01, SD2.02, SD2.04, SD2.04, STI-Engineered Judgement, Calculating Fire Resistance for Gludams, Greg Lee Letter, Brian Perry-Albi Letter, Albi Fire proofing Brochure C: R. David Frum, FAIA, ACHA Z:\16029 Northpoint Recovery\Docs\06.01-Municipa]Review\Permit Responses\Altemate Methods Letter\Northpoint -Alternate Methods letter 6-18-2018.doex 02 Third Ave. fj ISALUS s14-ite 200 Seattle, Wa 01 ARCHITECTURL 98101 (206)652-0722 JOB #: 16029 NEW 1 1/2" THICK CEMENTITIOUS TOPPINGS OVER 5/8" PLYWOOD EXISTING GLULAM EXISTING TJ1 7/8" RESILIENT CHANNELS PROVIDE 2 LAYERS OF 5/8" TYPE X GWB AT UNDERSIDE OF EXISTING I JOISTS FIRE/SMOKE SEALANT AT BOTH SIDES COMPLYING WITH UL 2079 EXPOSE ALL SIDES OF GLULAM SECTION EDMONDS RECOVERY CENTER NORTHPOINT RECOVERY RATED CEILING AT GLULAM SD2.01 DATE: 06/18/18 REV TYPE: Author Calculating, Fire Resistance of Glulam Beams and Colu-- /fAg_ e4rwl- typa-, Number EWS Y215_B r-Or et�+irv_ IC.-Pa�r Deceinber 2009 4ftek-eme_r,4 ;7V INTRODUCTION r e_fy,,�-4, _S ex- tP%-e_ fm d 0 F= n #5 / e-ff e,� Glulam beams and columns provide architectural warmth and beauty along with structural strength and natural fire resistance. In the presence of fire, the outer portion of a glulam member becomes charred. This layer of charred wood then functions as an insulator, helping to protect the undamaged interior of the member from the heat. The rate of advancement of this insulating char layer into the remaining, undamaged portion of the mernber has been well documented (approximately 0.025 inches [0.6 minj per minute) and forms the theoretical basis o t e equations used to predict fire endurance.' Full-scale fire tests--o—n-Fo—acTea-Fearns --and columns' have confirmed the validity of the equations in predicting their load -carrying capability under fire conditions and the method is recognized by the International Building Code (IBC). 19 4A U-3 Z M JI I A d : r-13 -T-1 Ir-11-YA Calculation of the ability of a glulam beam or column to resist fire for up to one hour is described in the 2009 International Building Code (IBC), Section 721.6. The equations apply to members With fire on three or four sides. Beams: Fire on 3 sides t = 2.54ZB14 - 1�1 .............. (1) D Fire on 4 sides t = 2.54ZB14 - 2BI ............ (2) Columns: Fire on 3 sides t = 2.54ZB 3 - B 1 2DI ............. (3) Fire on 4 sides t = 2.54ZB 3 -1 .............. (4) 1 DI Where: t = fire resistance in minutes Z = partial load compensation factor (see Figure 3) which is a function of applied load to design capacity B = the breadth or width of a beam or the smaller dimension of a column (in.) (see Figure 1) D = the depth of a beam or the larger dimension of a column (in.) (see Figure 1) (1) Lie, T. T., 1977. A method for assessing the fire resistance of laminated timber beams and columns. Fire Research Section, Division of Building Research, National Research Council of Canada, Ottawa, Ont., Canada. (2) Fackler, J. P., 1961. Essais de r6sistance au feu. Centre Scientifique et Technique du BAtiment, Cahier 415, et al. APA ABKJ1 ANDERSEN - BJORNSTAD - KANE - JACOBS June 18th, 2018 Mr. Douglas McNutt Principal Salus Architecture RE: Charring Calculation for Existing GIL Beam Douglas, At your request, I have reviewed the carrying capacity of the Glu-Lam (GL) beams based on a 1/40" charring rate per minute. I found that the exposed area of the 2nd floor 6 Wx 311/2" GL beam can handle 1/2 hour of charring and still support unfactored (service level) loads at the factored or ultimate stress levels. This is apart from any consideration of any of the three applied options: 2-layers of GWB protection (which normally is counted as 1-hour rating) below the ceiling, shaft wall, or inturnescent paint, either of which will increase the over-all resistance. I also checked the roof 5 1/8"x27" GL beam capacity if charred and found that the roof GL can handle 1 hour of charring and still support unfactored (service level) loads at the factored or ultimate stress levels, again without consideration of any of the three previously mentioned options. Furthermore, I also used the method for calculating the fire resistance of Glu-Lam Beams found in the APA document EWS Y245B "Calculating the Fire Resistance of Glu-Lam Beams and Columns", and found that according to their method, the 2nd floor 6 Wx 311/2" GL beam would have 62.7 minutes of fire resistance, and the roof 5 1/8"x27" GL beam would have 47.1 minutes of fire resistance. Thus, for both GL types, it seems to me that the combination of 2 layers of or shaft wall or inturnescent paint GWB (on the exposed sides of the GL) should be considered as more than adequate protection as the GL beams would have a reserve of at least 30 to 60 additional minutes of capacity during charring even neglecting the fire protective layers) before the beams would be overstressed at service load. If you have any questions or need additional information, please feel free to call at 206-340-2255. 1402 - Third Avenue, Suite � ABKJ1 ANDERSEN - BJORNSTAD - KANE - JACOBS Sincerely, Greg Lee, PE, SE Principal ABKJ Inc. 1402 - Third Avenue, Suite 200 VAIN Protective Coatings June 15, 2018 RE: Northpoint Recovery Center To whom it may concern, Albi would recommend applying 40 mils WFT (28 mils DIFT) of Albi Clad FP to protect the exposed glulam beams and deck in place of using gypsum to provide a 1-hour fire resistance rating. This judgement is based on Western Fire Center Inc. Report # 04042(a), where 40 mils WIFT of Albi Clad FP is specified for a 1 hour rating on an open wood floor joist assembly featuring 2"xlO" joists and a deck of TG subfloor and CDX plywood. Based on the Technical Note #EWS Y245B from the APA - Engineered Wood Association, the fire resistance rating up to 1 hour can be calculated for glulam members. This method is recognized by the International Building Code. Based on the calculations, the 6"x3l" beam has a fire resistance rating of 58 minutes and the 5.5"x27" beam has a fire resistance rating of 53 minutes. These calculations were made assuming the beams would be carrying 100% of their maximum design load. Based on this, 40 mils WIFT of Albi Clad FP applied to the exposed glulam beams will provide the extra time necessary to achieve a 1 hour rating. Please note that Albi does not have any direct test data for Albi Clad FP over glulam beams and this judgement is based on an established calculation method and indirect test data. Brian Perry Product Engineer Albi Protective Coatings 401 Berlin Street, East Berlin, CT 06023 T 860 828 0571 Albi.com 02 Third Ave. fj ISALUS s'4uite 200 Seattle, Wa 01 ARCHITECTURL 98101 (206)652-0722 JOB #: 16029 Kir'%Al 4 4 /nit -1­1 11.-11Z f1r'RArK1-r1 I 1UU0 (OOD EDMONDS RECOVERY CENTER NORTHPOINT RECOVERY RATED CEILING AT GLULAM OPTION 1 E OF 30TH L 2079 SD2.02 DATE: 06/18/18 REV TYPE: Author ENGINEERING JUDGMENT FIRESTOP DETAIL NS14918024 *F Rating - 1 HR mm 1. Floor/Ceiling Assembly (1 Hr) - Wood floor/gypsum ceiling assembly (UL L570 Design). 2. Penetrant - Max 20' long x 6" wide x 27" tall (or smaller) glularn beam. Penetrant to be rigidly supported. Annular space is min 1/4" to max 3/4". 3. Sealant - SpecSeal@ SSS or LCI Sealant applied into annular space to full depth, flush with bottom of gypsum ceiling. *Note: 1 - Rating of the firestop system is dependent on the performance of the surrounding construction under fire exposure with a maximum possible F rating of 1 Hr. THIS DESIGN REPRESENTS A FIRESTOP SYSTEM EXPECTED TO PASS THE STATED RATINGS IF TESTED Project: Signature: System Reference: Northpoint Recovery Center W-L-1461, W-L-7244, F-C-7045 Project Address: Edmonds, WA 98020 Designed by: Bernadette Guerrero Douglas McNutt/RMI N.T.S. 1' "05/302018 1 PAGE 1 OF 1 ,=" ASTM E814/UL 1479: Standard for Fire ion Fi—tops All statements, technical information, and recommendations contained herein are based upon tests we believe to be accurate; however since the conditions of use and application 90 Spectifted Technologies Inc. are beyond our control, STI shall not be liable for any damage, direct or consequential, OT114fans Way - goemMile, NJ 0076 USA- Toll Fra: MOM2.1111110 - T.' +1 "52MM resulting from the use of this material or design. STI's sole warranty shall be to refund or P44"2SI-8416-E:twhiorvCWAred6p.oach-www.dMtwop.ow replace materials found to be defective. KIMAI 4 4 /1111 -rL_llf�lZ D SECTION 02 Third Ave. EDMONDS RECOVERY CENTER 0Pj ISALUS s'4.ite 200 Seattle, Wa 01 ARCHITECTURL 98101 NORTHPOINT RECOVERY (206)652-0722 JOB #: 16029 RATED CEILING AT GLULAM OPTION 2 79 SD2.03 DATE: 06/18/18 REV TYPE: Author 1402 Third Ave. fj ISALUS Suite 200 Seattle, We 01 ARCHITECTURE 98101 (206)652-0722 JOB #: 16029 ['111 M&WMAIKINKMAILME MINI MAO 1FAMAJ 40 9111111161 ME pw ' WATITO As- I EDMONDS RECOVERY CENTER NORTHPOINT RECOVERY RATED CEILING AT GLULAM OPTION 3 4NELS OF 5/8" )ERSIDE OF �T AT BOTH VITH UL 2079 IT POSED SD2.04 DATE: 06/18/18 REV TYPE: Author Calculating fi�re Resistance of Glulam Beams and Columns 77�7$ ;5 Py- " -�t t'y- r CAa ri- Number EWS Y245B December 2009 INTRODUCTION Glulam beams and columns provide architectural warmth and beauty along with structural strength and natural fire resistance. In the presence of fire, the outer portion of a glulam member becomes charred. This layer of charred wood then functions as an insulator, helping to protect the undamaged interior of the member from the heat. The rate of advancement of this insulating char layer into the remaininy— un a na,-rl- portion oLthe member has been well documented (approxiTItely.0.025 inches [0.6 mm] per minute) and forms the theoretical basis of the equations used to predict fire endurance� Full-scale fire tests on loaded beams and columns' have confirmed the validity of the equations in predicting their load -carrying capability under fire conditions and the method is recognized by the International Building Code (IBC). DESIGN METHODOLOGY Calculation of the ability of a glulam beam or column to resist fire for up to one hour is described in the 2009 International Building Code (IBC), Section 721.6. The equations apply to members with fire on three or four sides. Beams: Fire on 3 sides t = 2.54ZB14 — 1�1 .............. D (1) Fire on 4 sides t = 2.54ZB 4 _ 2B 1 D I ............ (2) Columns: Fire on 3 sides t = 2.54ZB 3 — B ............. 1 2DI (3) Fire on 4 sides t = 2.54ZB 3 — 1 1 DI ..... I ........ (4) Where: t = fire resistance in minutes Z = partial load compensation factor (see Figure 3) which is a function of applied load to design capacity B = the breadth or width of a beam or the smaller dimension of a column (in.) (see Figure 1) D = the depth of a beam or the larger dimension of a column (in.) (see Figure 1) (1) Lie, T. T., 1977. A method for assessing the fire resistance of laminated timber beams and columns. Fire Research Section, Division of Building Research, National Research Council of Canada, Ottawa, Ont., Canada. (2) Fackler, J. P., 1961. Essais de r6sistance au feu. Centre Scientifique et Technique du BAtiment, Cahier 415, et al. APA These equations apply to glulams with a minimum nominal size of six inches by six inches before expo- sure to fire. Equation 3 is accurate only when the smallest dimension (B) is the side not exposed to the fire. When a beam or column is partially recessed into a wall, floor or ceiling, the full dimension of the member, including the portion of the column recessed into the wall, floor or ceiling may be used in the calculations to obtain the maximum calcu- lated fire resistance. Equations 3 and 4 are slightly altered from the way they appear in the IBC. In the column equations, the dimensions B and D are reversed to maintain consistency and clarity of notation on glulam beams and columns (see Figure 1). B is assumed to be the narrowest dimension of the column (weak axis buckling). Tables la, lb and lc show the minimum dimensions FIGURE 1 DIMENSIONS FOR CALCULATION OF FIRE RESISTANCE Where B is always the lead dimension. T D B D 01' B B D Beam Column of a glularn member that will provide 100 percent design capacity and one -hour fire protection. These tables have been generated using Equations 1-4 Beams and columns with dimensions less than those shown in Tables la, lb and 1c, but at least 6 inclies by 6,inches nominal size, may meet the requirements for one -hour fire resistance when the member is over -designed for the applied load. This principle is demonstrated in the design examples that follow. SPECIFYING A ONE -HOUR FIRE -RATED GLULAM Tension laminations of glularn beams are always positioned as the outermost laminations of the beam subjected to maximum tension stresses, and in a fire, the outermost fibers in a wood member are the first to be damaged. For this reason, when a one -hour rating is required for a glularn beam, the designer should specify one additional tension lami- nation in place of a core lamination (see Figure 2) and the glularn should be marked "Fire -rated one - hour" by the manufacturer. For a balanced beam layup, an additional tension lamination should be added to both outer zones. An additional tension lamination is not required for columns and arches. FIGURE 2 TYPICAL UNBALANCED GLULAM BEAM LAYUPS FOR UNRATED AND ONE -HOUR FIRE -RATED GLULAM One extra tension lamination added for one -hour resistance. Outer Compression Outer Compression Inner Comp. Inner Comp. Inner Comp. Inner Comp. Core Core Core Core Core Core Core Core Core Core Core Inner Tension Inner Tension Inner Tension Inner Tension Extra Outer Tension Outer Tension Outer Tension Unrated One Hour TABLE 1 a Member Type Beam Fire Exposure Fire Three Sides Fire Four Sides Beam Width (in.) 6-3/4 8-1/2 8-3/4 10-1/2 10-3/4 6-3/4 8-1/2 8-3/4 10-1/2 10-3/4 Minimum Depth (in.): 13-1/2 - 7-1/2 - 6 27 - 13-1/2 - 12 1- 1 /2" thick Laminations Minimum Depth (in.): 13-3/8 6-7/8 - 6-7/8 27-1/2 13/3-4 - 12-3/8 - 1-3/8" thick Laminations TABLE 1 b Member Type Column Fire Exposure Fire Three Sides* K.1/d Condition(,) I I >11 Column Width (in.) 8-1/2 8-3/4 10-1/2 10-3/4 8-1/2 8-3/4 10-1/2 10-3/4 Minimum Depth (in.): - 9 - 7-1/2 - 15 - 10-1/2 1- 1 /2" thick Laminations Minimum Depth (in.): 8-1/4 - 8-1/4 - 19-1/4 - 9-5/8 - 1-3/8" thick Laminations *Minimum dimensions are only valid when the unexposed side of the column is the smaller side. (a) See Figure 8. TABLE I c Member Type Column Fire Exposure Fire Four Sides K.1/d Condition(a) I I >11 Column Width (in.) —8-1/2 8-3/4 10-1/2 10-3/4 8-1/2 8-3/4 10-1/2 10-3/4 Minimum Depth (in.): - 12 - 10-1/2 - 30 - 13-1/2 1- 1 /2" thick Laminations Minimum Depth (in.): 12-3/8 - 9-5/8 - 38-1/2 - 13-3/4 - 1-3/8" thick Laminations (a) See Figure 8. General Note for Tables la, 1 b and 1c: Glulam members having a net width of 8-1/2" or 10-1/2" are typically manufactured using 1-3/8" thick laminations. Glularn members having a net width of 8-3/4" or 10-3/4" are typically manufactured using 1-1/2" thick laminations. FASTENERS Because metal fasteners conduct heat directly into the member, exposed fasteners must be given rated protection from fire that is equivalent to that expected of the member. For a one -hour rating, sufficient wood, gypsum wallboard or other material must be applied to protect the exposed portions of the fasteners for one hour. This may be 1-1/2 inches (38 mm) of wood, 5/8 inch (16 min) Type X gypsum board or other approved material. Example details can be found in Figures 9-14. DESIGN EXAMPLE 1: GLULAM REAM FOR ONE-NOUR FIRE RATING IN ACCORDANCE WITH THE 2009 INTERNATIONAL BUILDING CODE Assume a simply supported roof beam is to span 30 feet, carry 240 lb/ft of total load (dead load plus snow load) and be used in a dry service condition. It is continuously supported along its compression side and will have three sides exposed to fire. A one -hour rating is required. The beam used will be a 24F-V4/DF (Douglas -fir) with the following allowable design stresses: Fb 2400 psi E 1.8 x 101 psi Fv 265 psi What size glulam beam should be used? From Table 3 of EWS Data File Glued Laminated Beam DesigA Tables, Form EWS S475, select a 5-1/8 x 15 beam with total capacity of 266 plf, which is greater than 240 plf. (Note that the tabulated capacity in EWS S475 has considered the dead weight of the beam.) Determining the actual beam depth that will continue to carry the design load for one hour is aided by the use of Figure 4, Beams - Fire 3 Sides. From this graph, the range of depths that might be practical to use can be anywhere from approximately 12 to 30 inches. Obviously, this beam must be deeper than 15 inches as the beam in this exam- ple is stressed to approximately 90 percent of design capacity. All of the 5-1/8-inch-wide beams in the depth range of 12 to 30 inches will retain 50-60 percent of design capac- ity after one hour. An initial estimate of a percentage that corresponds with this range of beam depths is 55 percent, which corresponds to a beam depth of 18 inches. Section modulus, S = 5.125(18)2 = 276.75 in.' 6 Determine if this beam will have sufficient strength left after one hour of fire exposure to continue to carry the design load by determining the ratio of applied moment to design flexural capacity. Beam size will also have to be checked for shear and deflection. Determine Fb' 12)-L (5.125)TIO (21)-�10 Volume factor = C, = ( 10 B L (L2 I (5.125)T'Lo (Ll)' 18)" _�._1_25 30 To = 0.9266 Fb' = FbC,C, = (2,400)(1.15)(0.9266) = 2,557 lb/in? Determine fb Calculate beam weight using 35 lb/ft3 Beam weight = (5.125)(18)(12) (35) = 22.4 lb/ft 123 M Applied = w L 2 = (240 + 22.4) 30' = 29,520 ft-lb = 354,240 in.-Ib T __iT f b 354,240 = 1,280 lb/in.2 S 276.75 Check the ratio of applied moment to flexural capacity fb 1,280 Fb' 2,557 : 0.50 < 55% => OK Check fire endurance: From Figure 3, for a beam loaded to 50% of capacity, Z is approximately 1.3. Using Equation 1: t = 2.54(l.3)(5.125) 4 — 5.125] = 62.9 minutes > 60 => OK; use 5-1/8-inch x 18-inch 24F-V4 Douglas -fir glulam beam. 1 18 This beam has a moment capacity that is significantly greater than is needed if the one -hour fire resistance is not a requirement. In some cases, a wider beam may be required to satisfy a beam depth limitation while still meeting the one -hour fire resistance requirement. For instance, a 6-3/4-inch-wide beam that is 13-1/2-inch deep, and has the extra tension lamination, will carry 100 percent of its design load after one hour of fire exposure on three sides. See Table la and Figure 4. The designer will also need to confirm that the design shear and deflection values for the trial beam size are less than 50 percent of these capacities. When specifying the beam, advise the manufacturer to eliminate one core lamination and substitute one additional tension lamination (Figure 2) and mark the beam "Fire -rated one -hour." ALTERNATIVE SOLUTION IN ACCORDANCE WITH THE 2005 NATIONAL DESION SPECIFICATION, CHAPTER 16 Step 1: From Table 3 of Data File, Glued Laminated Beam Design Tables, Form EWS S475, select a 5-1/8-inch by 15-inch beam with total capacity of 266 plf which is greater than 240 plf (note that the tabulated capacity in EWS S475 has considered the dead weight of the beam). Step 2: Determine the actual beam depth that will continue to carry the design load when exposed to a one -hour fire as follows: Step 2a: From Chapter 16 of NDS, 1.2% tO. 187 Where: P = nominal char rate of 1.5 in./hr Pe.ff = effective char rate (in./hr) t = exposure time (hrs) Therefore, when t = I hr, P,ff = 1.8 in./hr Step 2b: The residual cross section after a one -hour fire exposure on three sides (top of the beam is protected from fire damage) can be calculated as: bresidual � 5.125 — (1.8 x 2) = 1.525 in. h residual = 15 — 1.8 = 13.2 in. 3 Sresidual = 1.525 x 13.22/6 = 44.3 in. Step 2c: The residual moment capacity after a one -hour fire exposure on three sides can be calculated based on Table 16.2.2 of the 2005 NDS. Mresidual � 2.85 F b? X Sresidual � 2.85 x 2,400 x 0.9437 x 44.3/12 = 23,821 ft-lb. Where: Fb' = adjusted allowable bending stress, including beam volume effect factor, but not the load duration factor. 0.9437 = glulam beam volume effect factor (see Appendix A of EWS S475) Step 2d: The applied moment due to the 240 lb/ft of total load and the beam weight of 18.7 lb/ft can be calculated as: M.pplied wV = (240 + 18.7) x 302 = 29,102 ft-lb > 23,821 ft-lb =� NG 8 8 Step 2e: Therefore, the beam size should be increased to accommodate the one -hour fire exposure. Select a 5-1/8-inch by 18-inch beam. From Table 3 of EWS S475, the load carrying capacity of this beam is 470 plf which is greater than 240 plf. Step 2f. Repeat Steps 2b and 2c for one -hour fire exposure, bresidual = 5.125 — (1.8 x 2) = 1.525 in. hresidual = 18 — 1.8 = 16.2 in. 2 3 S.idual = 1.525 x 16.2 /6 = 66.7 in. Mresidual = 2.85 Fb' X Sresidual = 2.85 x 2,400 x 0.9266 x 66.7/12 = 35,213 ft-lb. Ma O)e2 _ (240 + 22.4) x 302 = 29,522 ft-lb < 35,213 ft-lb => OK pplied = 8 8 Therefore, use a 5-1/8-inch by 18-inch 24F-V4 Douglas -fir glulam beam. DESION EXAMPLE 2x GLULAM COLUMN FOR ONE-NOUR FIRE RATINO IN ACCORDANCE WITH THE 2009 INTERNATIONAL BUILDINO CODE An existing building is to be remodeled with a change of occupancy requiring that the glulam columns meet a one - hour fire -resistance requirement. The existing glulam column is 20-foot high, measures B = 8-3/4-inches wide by D = 10-1/2-inches deep and will remain dry in service. It supports a concentrated total floor load (DL + LQ of 50,000 lb. (CD = 1.0) applied concentrically to the top of the column. The column is not subjected to any lateral loads. From the original specifications, the glulam is a Douglas -fir Combination 2 (see Table 3, Form EWS Y240). Determine if the column is adequate to carry the imposed axial load for one hour with fire on four sides and how long it can be expected to carry the applied load. If it is not adequate, determine what size column is required. To address these issues, the total load capacity of the column must be determined along with the percentage of the total load capacity used by the applied load and the partial -load compensation factor, Z. Determine Load Capacity B = 8.75 in. D = 10.5 in. A = B x D = 8.75(10.5) = 91.875 in.2 CD = 1.0 for DL plus floor LL E = 1,600,000 lb/in.1 F, = 1,950 lb/in.1 C = 20(12) = 240 in. K, = 1.0 (see Figure 8) Column is assumed to be pinned at both ends. = f K� = 240(l.0) = 240 in. = 240 = 27.43 B 8.75 c = 0.9 Where: E = tabulated modulus of elasticity (lb/in.2) E' = adjusted modulus of elasticity (lb/in .2) F,� = tabulated compression design value parallel to grain (lb/in.1) A = area of cross section (in.') B = least dimension being evaluated for potential buckling (in.) f = length of column (in.) V, = f K, = effective length of column (in.) Ke = buckling length coefficient for compression members c = coefficient that depends on member type (0.9 for glularn) (E'[1 - 1.645 COVE] 1.05) (1,600,000[l - (1.645)(0.10)] 1.05) E'.,.. = 1.66 1.66 = 845,566 lb/in? Where: COVE = coefficient of variation in modulus of elasticity = 0.10 for glulam 1.05 = conversion factor to obtain true E (1.05 for glulam) 1.66 = factor of safety FC* = tabulated compression design value multiplied by all applicable adjustment factors except CP (lb/in.1) 0.822 E'.i�. 0.822(845,566) 2 FcE = I ! ) 2 27.43 2 924 IbAn. ( B FcE 924 0.474 F,* 1,950 + JLL�J 2 (1 LE �E Fc.* 1 + 0.474 1 + 0.474 0.474 .1(0.9) 0.440 CP = 2c 2c _c 2(0.9) � 1 0.9 F�' = F,:*Cp = allowable compressive stress (lb/in.2) F�' = 1,950(0.440) = 857 psi Axial load capacity = AFC 91.875(857) = 78,737 lb > 50,000 => OK for concentric axial load without fire endurance consideration Check fire endurance based on ratio of applied load to design capacity Applied Load - 50,000 - 0.635 = 63.5% Design Capacity 78,737 From Figure 7, for a column 8-3/4-inches wide and I./B > 11, 63.5% corresponds to about a 13-1/2-inch depth which is greater than the existing column's depth of 10-1/2 inches. The existing column will therefore not carry the applied load for the full duration of the prescribed one -hour fire. To check this conclusion, calculate the fire endurance From Figure 3, for a column with 1,/B > 11 and the load at 63.5% of capacity, Z is approximately 1. 16. Using Equation 4: B 8.75 in. D 10.5 in. t = 2.54ZB 3 — L = 2.54(l.16)(8.75) 3 — �1'75 = 56 minutes < 60 => NG I D 1 1 10.51 The existing column is inadequate to meet the one -hour fire -resistance requirement even though it is adequate to carry the applied load in occupancies not requiring a one -hour fire rating. Determine column size necessary to carry the design load and meet the one -hour requirement Using Figure 7 as a guide, try a 10-3/4-inch x 10-1/2-inch glulam, Douglas -fir Combination 2, assuming a depth of 10-1/2 inches is a design requirement. A = 10.75(10.5) = 112.875 in.2 Slenderness ratio = I /B = 240/10.5 22.86 C 0.822 E'mj� = 0.822(845,566) 1,330 lb/in.2 F,:E e 2 22.861 F�* 1,950 lb/in .2 F, 1,330 0.682 Fc* 1,950 2 (,FcE)= c* I + 0.682 1 + 0,6821 2 — 0.682 595 C, 2c 2c _c —T(0—.9) 2(0.9) 0.9 Fc' 1,950(0.595) = 1,160 lb/in .2 Axial load capacity = AFc' = 112.875(1,160) 130,939 lb > 50,000 lbs. OK Check the fire endurance Applied Load 50,000 = 0.382 = 38.2% Maximum Capacity 130,939 Z, from Figure 3, is 1.3. Using Equation 4: B 10.5 in. D 10.75 in. t = 2.54ZB 3 — B I = 2.54(l.30)(10.5)13 — 10-5 = 70 minutes > 60 => OK-1 1 15- 10.751 use 10-3/4-inch x 10-1/2-inch Combination 2 Douglas -fir glularn column. ALTERNATIVE SOLUTION IN ACCORDANCE WITH THE 2005 NATIONAL DESIGN SPECIFICATION, CHAPTER 16 Step 1: The 8-3/4-inch by 10-1/2-inch glularn column capacity can be calculated based on Section 3.7.1 of the 2005 NDS as 78,713 lb > 50,000 lb =:> OK Step 2: Determine the actual column size that will continue to carry the design load when exposed to a one -hour fire as follows: Step 2a: From Chapter 16 of NDS, 1.2p. P,ff � tO.187 Where: P. = nominal char rate of 1.5 in./hr P'ff = effective char rate (in./hr) t = exposure time (hrs) Therefore, when t = 1 hr, P,ff = 1.8 in./hr Step 2b: The residual cross section after a one -hour fire exposure on four sides can be calculated as: bresidual � 8.75 - (1.8 x 2) = 5.15 in. hresidual = 10.5 - (1.8 x 2) = 6.90 in. A,,sidual = 5.15 x 6.90 = 35.54 in? Step 2c: The residual axial capacity after a one -hour fire exposure on four sides can be calculated based on Table 16.2.2 of the 2005 NDS. Fc' = 2.58 x F, x CP = 2.58 x 1,950 x 0.1273 = 640.4 psi Presidual = F.' x Aresidual = 640.4 x 35.54 = 22,755 lb < 50,000 1 => NG Where: Cp = column stability factor, which can be calculated based on Section 3.7.1 of the 2005 NDS with the exception that the column buckling strength F�, is determined using equation given in Table 16.2.2 of the 2005 NDS Step 2d: Therefore, the column size would need to be increased to accommodate the one -hour fire exposure. Select 10-3/4 inches by 10-1/2 inches. The column capacity can be calculated based on Section 3.7.1 of the 2005 NDS as 130,939 lb > 50,000 Ib z* OK Step 2e: Repeat Steps 2b and 2c for one -hour fire exposure, bresidual � 10.75 - (1.8 x 2) = 7.15 in. h residu.1 = 10.5 - (1.8 x 2) = 6.90 in. Aresidual = 7.15 x 6.90 = 49.34 in.2 Fr' = 2.58 x F, x CP = 2.58 x 1,950 x 0.2253 = 1,133.3 psi Presidual = F�' x Aresidual � 1,133.3 x 49.34 = 55,911 lb > 50,000 lb => OK Therefore a 10-3/4-inch by 10-1/2-inch Combination 2 Douglas -fir glulam column is required to meet the one -hour fire rating. Summary As shown by the preceding examples, glued laminated timber members can be designed to provide a one -hour fire rating when required. Based on the 2009 IBC, Tables la, lb and Ic provide basic minimum dimensions for one -hour fire -rated glulam beams and columns when the applied load represents 100 percent of the member design capacity. Figures 4, 5, 6 and 7 provide estimated sizes of beams and columns that will satisfy a requirement for a one -hour fire rating when the member is loaded to less than 100 percent of capacity. Alternatively, the design methodology pro- vided in Chapter 16 of the 2005 NDS can be used to design one -hour fire -rated glulam beams and columns. For additional information related to the design of glulams, contact APA Product Support Help Desk, 7011 South 19th St., Tacoma, Washington 98466-5333, Phone (253) 620-7400. FIGURE 3 FACTOR Z AS A PERCENTAGE OF DESIGN CAPACITY 1.60 1.50 Columns — I,/B < 11 1.40 N 1.30 2 NNI V 1.20 — 0 1.10 — Columns — 1�/B and Beams i.00 L 40 50 60 70 80 90 100 Applied Load or Bending Moment/Design Capacity (%) FIGURE 5 BEAMS — FIRE 4 SIDES 30 25 20 .S 6-3/4 inchesA 15 8-3/4 inche E 10 10-3/4 inches wide 5 01 1 1 1 1 50 55 60 65 70 75 80 85 90 95 100 Strength After One Hour (%) FIGURE 4 BEAMS — FIRE 3 SIDES 4 35 30 5-1/8 inches wide 25 10 20 E 15 6-3/4 inches wide 10 5 01T 50 55 60 65 70 75 80 85 90 95 100 Strength After One Hour (%) (Beams wide, than 6-3/4" will generally carry 100% of capacity far 1 hour provided they are as deep as they are wide.) FIGURE 6 COLUMNS — FIRE 3 SIDES 4) 35 6-3/4 inches wid 8—"/, 30 1� I I I 6-3/4 inches wide — le/B < 11 25 .S 20 E 0 15 10 1-0000' 1 4-7 1-, 8-3/4 inches wi e — �/B > 11 5 01 50 55 60 65 70 75 80 85 90 95 100 Strength After One Hour (%) Calculating Fire Resistance of Glulam Beams and Columns [12 FIGURE 7 COLUMNS - FIRE 4 SIDES 40 6-3/4 inches wide - 1�/B > 11 oil 35 30 9 25 0 20 E 0 15 rwwwwbo ;PON'pom ..m - 10 8-3/4 riches wide -,],/B I I 5 1< 0 50 55 60 65 70 75 80 85 90 95 100 Strength After One Hour (%) FIGURE 8 APPENDIX G, 2005 NDS - EFFECTIVE COLUMN LENGTH Buckling modes t t t t t Theoretical K. value 0.5 0.7 1.0 1.0 2.0 2.0 Recommended design K,, when 0.65 0.8 1.2 1.0 2.1 2.4 ideal conditions approximated Rotation fixed, translation fixed Rotation free, translation fixed End condition code Rotation fixed, translation free Rotation free, translation free Form No. EWS Y245B N 0 2009 APA - The Engineered Wood Association n www.apawood.org Calculating Fire Resistance of Glulam Beams and Columns L3 FIGURE 9 FIGURE 10 BEAM TO GIRDER — CONCEALED CONNECTION COLUMN CONNECTIONS — COVERED Provide lateral support for end of beams . . ........... P" Wood beam 0 0 ................ .................... \—Wood plug Plan View Standard steel connections — box Wood column in using 2x wood to protect steel E ............ ------------ Floor Wood cover typical bottom and sides ---------- Elevation Elevation [Form No. EWS Y245B 0 2009 APA — The Engineered Wood Association m www.apawood.org FIGURE 11 BEAM-TO-COLLIMN CONNECTION Connection not exposed to fire Provide lateral support for end of beam Exposed portion of beam 2x backup nailer to box in around beam 5/8" Fire -rated gypsum board 0 0 0 Column enclosed within 0 one -hour wall. Column may also be a concrete or masonry pilaster, in which case the beam -to -column connection would be boxed in with 2x4s and 5/8" Elevation fire -rated gypsum board. FIGURE 12 BEAM -TO -COLUMN CONNECTION Connection exposed to fire where appearance is a factor Provide lateral support for end of beam End View Wood plug over bolt Cross - shaped connection recessed in wood Wood beam ;:(D Q Fill void around seat with plaster of Paris or Wood column approved ____/j _ compound Elevation Calculating Fire Resistance of Glularn Beams and Columns 15 FIGURE 13 FIGURE 14 BEAM -TO -COLUMN CONNECTION CEILING CONSTRUCTION Connection exposed to fire where appearance is not a factor Provide lateral support for end of beam Standard one -hour rated ceiling framing Steel connection T. welded to steel plate cast in top of 7ailer concrete column 5/8" Fire -rated 2.4 n strip gypsum board Apply fire protective coating that is allowed by the code Exposed portion for one -hour rating of steel of beam Concrete column Section Elevation F—Form No. EWS Y245B (9 2009 APA — The Engineered Wood Association www.apawood.org Calculating Fire Resistance of Glulam Beams and Columns We have field representatives in many major U.S. cities and in Canada who can help answer questions involving APA and APA EWS trademarked products. For additional assistance in specifying engineered wood products, contact us: APA HEADQUARTERS 7011 So. 19th St. - Tacoma, Washington 98466 - (253) 565-6600 - Fax: (253) 565-7265 R�- PRODUCT SUPPORT HELP DESK (253) 620-7400 - E-mail Address: help@apawood.org DISCLAIMER The information contained herein is based on APA — The Engineered Wood Association's continuing programs of laboratory testing, product research and comprehensive field experience. Neither APA, nor its members make any warranty, expressed or implied, or assume any legal liability or responsibility for the use, application of, andlor reference to opinions, findings, conclusions or recommendations included in this publication. Consult your local jurisdiction or design professional to assure compliance with code, construction and performance requirements. Because APA has no control over quality of workmanship or the conditions under which engineered wood products are used, it cannot accept responsibility for product performance or designs as actually constructed. Form No. EWS Y245B/Revised December 2009 APA REPRESENTING THE ENGINEERED WOOD INDUSTRY