2006.0783RM.pdf08/14/06 12.46 FAX 425 741 3900 HEIDNIVULhTUN
I M-1 I it, IF R
August 14, 2006
File No. 212001.013.04502
W. Lyle Chrisman
City ofEdmonds
121 5th Avenue North
Edmonds, WA 98020
I
AUG 14 2006
BUILDING DEPARTMENT
av or- F-omcRIDS
Subject: Building Permit Plan Review - Second Submittal
Sheehan Residence — Retaining Walls (Task Order No. 06-03)
Dear Mr. Chrisman:
We reviewed the proposed project for compliance with the structural provisions of the
2003 International Building Code (IBC) as amended and adopted by the state of
Washington and the city of Edmonds- The permit applicant should address the
comments below.
Geotechnical
1. We are requesting a letter from the geotechnical engineer recommend-Ing lateral
earth pressures on retention structures due to earthquake motions- This
comment was included in the p revious review letter, however a letter from the
geotechnical engineer was not included in the second submittal. Per the
response from the Engineer -of -Record, the wall has been designed in accordRuce
with the geotechnical report. We are unable to locate recommendations for the
lateral earth pressures due to earthquake motions in the geotechnical report. It
does not appear that seismic lateral earth pressures have been included in the
structural calculations on pages 3 dirough 6. This may affect the structural
design of the retaining walls. Please verify. See IBC Section 1,802.23(l) and
ASCE 7-02 Sections 9.14.7.2. 1 and 9.7.5. 1 -
I The site plan shows limited clearance between the new retaining wall and the
pool wall, including overlaps between the new wall and the southeast and
southwest comers of the pool. Per the response from the Engineer -of Record,
there, -is no interference at the southwcstc.omer, and shoring of the pool structum
will be provided during construction. Note that the structural drawings still
indicate the southwest corner of the pool will interfere with the new wall. In
addition, it is our understanding that the geotechnical engineer has not reviewed
the final structural design for consistency with the geotechnical report- The
geotechnical engineer should provide a letter verifying that excavation for the
new wall will not undemiine the existing pool foundation.
iv.1 U z
Engiacers
Planner(
Slirveyorf
Washington
Otegan
Mak
Rgid Middleton, Inc.
728 1 34th Stmet SW
We 200
[wreff, WA 98204
Ph: 425 741-3800
foc- 425 741-3900
08/14/06 12:46 FAX 425 741 3900
REID MIDDLETON IA03
Mr- Lyle Chrisman
City of Edmonds
August 14, 2006
File No. 212001.013-04502
Page 2
3. Sections A/Sl and B/Sl indicate that granular backfill shall be placed behind the
new retaining wall. Per page 10 of the geotechnical report by Nelson
Geotechnical Associates, Inc., dated July 27, 2005, an 18-Inch wide zone of
clean granular material wrapped in filter fabric is recommended behind the
retaining wall. Per the response from the Engineer -of -Record, the structural
drawings have been updated. with this information, however it does not appear to
be included 'in the drawings. This information should be -included on Sheet Sl -
4. Page 3 of the structural calculations indicate that the retaining wall shown 'in
Section B/S I is restrained against sliding- The stability check for sliding states
that the footing is restrained and appears to indicate the evaluation of sliding
resistance has not been performed. Section B/S I now includes a key to provide
resistance against sliding, however calculations for sliding resistance have not
been performed. Calculations should be provided substantiating that the wall
has sufficient resistance to sliding. See IBC Section 1806- 1.
5. Page S of the structural calculations indicate that the retaining wall shown in
Section A/S I is restrained against sliding. The stability check for sliding states
that the footing is restrained and appears to indicate the evaluation of sliding
resistance has not been performed. Section AIS I now includes a key to provide
resistance against sliding, however calculations for sliding resistance have not
been performed. Calculations should be provided substantiating that the wall
has sufficient resistance to sliding- See IBC Section 1806. 1.
Corrections and comments made during the review process do not relieve the project
applicant or designer from compliance with code requirements, conditions of approval,
and permit requirements; nor is the designer relieved of responsibility for a complete
design in accordance with the laws of the state of Washington. This plan review check
is for general compliance with the International Building Code as it relates to the
project-
1 ReidMiddle
08/14/06 12:46 FAX 425 741 3900 REID MIDDLETON IM U4
Mr. Lyle Chrisman
City of Edmonds
August 14, 2006
File No. 212001.013.04502
Page 3
Enclosed are the drawings, structural calculations, geotechnical report, and any
correspondence from the engineer fot your records. If you have any questions or require
any additional clanification, please call.
Sincerely,
Reid Middleton, Inc.
Drew Martin, P-E.
Design Engineer
Enclosures
dop\2lCpk0l\013_Edmonds\eO45T2.doc\bam