20060630101234.pdfA 0,C ED DATE: June 30, 2006 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 TO: Peneloppe Chanel 1973120"' Ave NW Shoreline, WA 98177 FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 06-221 Project: Crescendo Achieve Educational Services Project Address: 8115 240" Street SW In reviewing the resubmitted plans for the above noted project, it was found that the following information, clarifications or changes must still be made to the plans. Most of the items in Building Division comments dated June 8, 2006 were discussed at the City meeting with the architect and building owner on June 20, 2006, however they have not been addressed on the plans. Based on past discussions, it is our understanding that this is now an E occupancy with children older than 2 1/2years of age. The following comments have been rewritten to reflect what was discussed at that meeting and must be addressed by the Architect. Please submit 2 sets of revised plans, stamped by the architect of record, and written responses to the comments below to Marie Harrison, Permit Coordinator. 1. Architect to provide a written scope of work for this project on the plans. 2. Architect to note the Type of Construction for the building (IBC Chapter 6). During the meeting the architect said it could qualify as a VB. This needs to be verified and shown on the plans- Previous item 3 3. Currently this building is a B occupancy, and based on verbal information, the proposed occupancy will be E (children older than 2 Y2. years of age). As discussed with the architect, a Change of Use is required including all required upgrades associated with the proposed occupancy and for accessibility, and must be clearly shown on the plans. This includes, but is not limited to. exiting, occupant load calculations (still needed for entire building, also see occupancy load comments below), corridors, minimum number of restrooms, accessibility throughout the building (except storage rooms), exterior wall and opening protection, etc. Clearly note the occupancy and ages of children on the plans as provided by the business owner. (IBC 3406. 1) previous items 4 & 5 4. Plans still do not clearly distinguish existing construction, construction built previously without permit, or construction proposed under this permit due to upgrades required by the change of use. This needs to be addressed by the Architect on the plans. Previous item 2 5. The site plan is still incomplete: previous items 6 & 7 a. Site plan needs to show the entire site (architect provided one at meeting for discussion purposes) b. Site plan needs to be stamped by the architect of record due to code issues discussed at the meeting, such as accessibility, exterior wall and opening protection., exit path of travel to the public way (particularly through the north exit through the playground and gated area), compliance of gate (for exiting, accessibility, signage, emergency lighting, etc), etc. c. Site plan still needs to show the following accessible path of travel from the accessible parking stall to the accessible building entry through the gate (not shown) through the play area (not shown), including slopes, curb ramps, landings, width of gate, and dimensions so accessible path of travel can be verified. This was discussed at length in the meeting and was not addressed at all on the plans. Show the location of the accessible parking stall sign. The accessible parking space must be located as close to the accessible entrance as possible. d. Show the location and height of all fences and gates. e. Note the scale of the site plan (minimum I "=20'), identify and dimension all property lines, streets/alleys/easements, driveway entrances, sidewalks, and dimension the trash enclosure area. f, Dimension distances from this building to property lines and adjacent structures so exterior wall and opening protection can be verified for the E * occupancy (IBC 704). 6. As discussed in the meeting, the architect must clearly show the accessible path of travel throughout the building (except storage rooms), including but not limited to accessible entrance/exit� door widths, maneuvering clearances at doors, restrooms, signage, etc. previous item 8 & 10 7. A portion of the reception counter must be accessible per ICC/ANSI Al 17.1 section 904. For a forward approach the accessible portion of the counter must be minimum 30" in width and maximum 36" in height above the finished floor. Previous item 9 8. Fully dimension the floor plans of the overall building and all rooms. Note the floor area of each room (storage room areas not noted) and for the overall building. Previous item 11 9. Note all door sizes, fire ratings, and clearances at openings without doors. Previous item 12 10. 2 exits are required from the building and must be spaced apart Y2the maximum overall diagonal distance of the building. Based on the discussion in the meeting, this would be the exit at the reception area and the most westerly exit door on the north side of the building. The exit doors from tutor offices 2 & 3 are intervening rooms with no discernable exit path for the occupants, however they can be exits for the tutor offices only. Revise exit signage to direct occupant to the 2 required exits noted previously. Architect to also verify and clearly show illuminated exit signage (with power backup) locations, and emergency lighting (with power backup) locations on the plans. IBC 1013.2, 1014.1, 1014.2, 1016.3 previous item 13 11. The maximum length of dead end corridor is 20 feet. As discussed in the meeting, the architect was going to redesign the exiting, doors, and corridor configuration at the west end of the building, which has not been done. Also, the architect was going to redesign or request a written modification to address the east dead end corridor issue, which also has not been done. IBC 10 16.3 previous item 14 12. Clearly show on the plans that the common path of egress travel does not exceed 75 feet per IBC 10 13.3 and as defined in IBC 1002- previous item 15 13. Maximum occupant load signs must be posted at each classroom, tutor room, and conference room. IBC 1004.3 previous item 16 14.. The main exit doors must have panic hardware. The actuating door bar must extend at least Y2of the door leaf width. All other door hardware (except storage room doors) must be accessible hardware such as lever -style. Note the type of locking devices for each door. IBC 1008.1.9 previous item 17 15. Provide the floor area for the storage rooms on the plans. Storage areas greater than 100 square feet must be separated from the rest of the building with a I -hour fire barrier unless the building is fully sprinkled. Provide I -hour fire rated wall construction detail extending to the underside of the roof sheathing, and listed and tested fire rated assembly. Cross reference where it applies on the plans. IBC 302. 1.1 previous item 18 16. Provide wall construction details (stud size, spacing, gyp, etc.). Show how the wall will be anchored to .. the floor and ceiling. IBC 1621.1.2, ASCE 7 section 9.6.2.8.1 previous item 19 17. For 1 -hour rated walls and ceiling, provide construction details and listed/tested assemblies, and cross reference where they apply on the plans. Corridors must be 1 -hour fire rated (walls and ceiling), with self -closing 20 minute rated doors. Architect to revise plans and verify existing corridors meet minimum code requirements. Previous item 20 18. Provide a mechanical plan showing how supply and return will be provided to each occupied space. Show location of smoke/fire dampers where applicable. Previous item 21. 19. Ventilation must be provided either mechanically gr with natural ventilation using building openings (windows and doors): previous item 22 Page 2 of 3 a. Natural ventilation: Provide in each room or area at the rate 4% of the floor area. Show the calculations on the plans. OR b. Mechanical ventilation: Provide outdoor air at the rates specified in VIAQ Table 3 -4 (based on the occupant load established for the building) to each room or area. The system must be balanced (supply and retum/exhaust). Provide mechanical plans and calculations showing compliance. Provide manufacturer's specs for the existing mechanical units and/or new units to be installed. 20. A lunch room is now shown on the plans. Provide a letter from the business owner stating whether food will be prepared on site, or if children/staff will bring their lunch to school with no on -site food preparation. If food will be prepared on site, show kitchen layout, equipment plan, and contact Jon Lein, Pretreatment Technician for waste pretreatment requirements (such as grease trap or grease interceptor). Architect to revise/clarify plans. 2 1. Based on the floor area for the lunch room now shown on the plans, 2 exits are required, and must be spaced apart V2 the overall diagonal distance of the lunch room. Also, the occupant load factor for this room would be 15. Architect to revise plans. 22. Based on the floor area for the dance and music studio now shown on the floor plan, the occupant load factor would be 15. Architect to revise plans- 23. The occupant load factor for the lobby area should be 15. Architect to revise plans. 24. Business owner to provide a letter describing the use of the "waiting gallery" and "teacher's room" so that appropriate uses and occupant load factors can be verified. Architect to revise plans as needed based on letter. Cc: Michael Perry, Architect — FAX: 425-827-9218 Page 3 of 3