DATE: August 10, 2006
TO: Thrnh Tram
8410 Main Street, Suite B
Edmonds, WA 98020
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2006-0915 CCS
Project: Plumbing permit application for 3 pedicure chairs
Project Address: 8410 Main Street
In reviewing the plans for the above noted project, it was found that the following information, clarifications
or changes are needed. Please submit 2 sets of revised plans/documents to Marie Harrison, Permit
Coordinator.
Please have your plumber help you provide information and plans for the following comments:
1. Provide manufacturer's installation instructions for the pedicure chairs.
2. Show the water supply piping (type, size and layout) on the floor plan for both hot and cold water,
where it enters the tenant space and is run to all plumbing fixtures.
3. Reduced Pressure Backflow Assembly (RPBA) required to protect the public water system within the
tenant space. If the chairs are plumbed at the end of the water supply line, one RPBA is required
immediately before the connection of the first chair to the water supply line. If the chairs are not
plumbed at the end of the water supply line, then one RPBA is required for each chair. Show location(s)
of the RPBAs on the plumbing plan.
4. How will the water be drained from the pedicure chairs? If they are connected to the sanitary waste
system, show drain, waste, and vent piping (layout, sizing, slope, pipe material).
5. The Public Works Department is requiring premise isolation (RPBA) to protect the public water system
where the water supply line enters the tenant space. Please show this on the plan, and contact Linda
McMurphy, Cross Connection Control Specialist at 425-771-0235 if you have any questions regarding
this item.
Attachment: Plumbing Permit Submittal Requirements handout with highlighted items.
B55
Plumbing
Permit Submittal Requirements
PERMIT REQUIRED: A separate plumbing permit is required for new commercial
construction (excluding multifamily projects).
CODES: Uniform Plumbing Code (Current Edition)
International Fuel Gas Code (Current Edition)
LPG per 2001 NFPA-58 and 2002 ANSI 2223.1/NFPA-54
FEE: Based on the number of plumbing fixtures
SUBMITTAL REQUIREMENTS:
Submit a permit application, Plumbing Fixture Schedule Form (attached), copy of the
approved floor plans with details as required below, and calculations showing the
following:
J. Drain, Waste and Vent piping layout; sizing, slope. and pipe material
2. Potable water line layout,sizing and pipe material
3. Fixture unit and flow calculations to support line sizing
4. Cross connection devices are required.on all direct connections.to the potable water
system. Specify ` all fixtures that require cross connection devices (i.e., ice
machines, soap ejection ,systems, beverage dispensers, boilers, etc.) and note the
make/model of each device.
5. Indicate the location and cross connection device for premise isolation
6. Manufacturer's specifications for equipment ;such as sump pumps, ejector pumps,
water heater boosters, etc.
7. Gas piping layout, sizing and pipe material, pipe sizing calculations, and maximum
design operating pressure, location of pressure regulators
8. Listed and tested Fire Stopping Assemblies
9. Gas meter location
NOTE: No underground plumbing can be installed until the plumbing permit is obtained.