Loading...
20060816083638.pdf°` EDo City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION 103 (425) 771-0220 DATE: August 16, 2006 TO: Chris Amonson TGB Architects FAX: 425-774-7803 FROM: Ann Bullis, Assistant Building Official RE: Revision to permit #2005-0962 Project: Medical Gas Room Ventilation Shaft Project Address: 21911 76th Ave West During review of the above noted revision, it was found that the following information, clarifications or changes are still needed. Please submit 2 sets of revised plans/documents (affected sheets only) to Marie Harrison, Permit Coordinator. 1. Revised sheets note a 2 -hour shaft for the shaft, however the shaft wall types referenced are 1 -hour walls per Sheet B9.20 of the shell/core plans. Please revise to 2 -hour shaft assembly. 2. Sheet A2.01 shows two exhaust ducts coming from the med gas room running horizontally to the vertical shaft. Both must be within 2 hour rated shafts and run to the exterior of the building. This is not shown on the plans. 3. No section/construction detail was provided. (previous item 1) 4. The mechanical plans for PSASC (permit application 2006-0758 shows a different mechanical design of the med gas room ventilation and shaft locations/sizes. This needs to be coordinated.