PLAN REVIEW COMMENTS
BUILDING DIVISION
�sr 1g90 (425)771-0220
DATE: August 21, 2006
TO: Dave Cleven
deckeonnection@earthlink.net
FROM: fenny Readwin, Plans Ex e
RE: Plan Check # 06-248
Project: Ziedalski Deck
Project Address: 15900 70' Ave W.
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the above items to a
Permit Coordinator.
1) ok
2) Plan from Geotechnical Engineer does not match plan from Structural Engineer (i.e. extra
footings along the East side of the deck on the Structural Engineer's plan). Add extra
footings to Geotechnical Engineer's plan or provide revise Structural Engineer's plan. On the
framing plan specify size of footings under each post shown. Also, show which footings will
require two piles versus one per the Structural Engineers calculations.
3) Still need. Revise section detail to reflect actual grade as well as the Geotech and Structural
Engineer's requirements (i.e. footing dimensions, pin piles, grade is shown over posts, etc.).
4) Still need. Special inspections are required for the following. Complete the enclosed special
inspection agreement signed by the owner, the general contractor and the special inspector and
submit to the City for approval prior to issuance.
• Soil Bearing Verification
• Pin pile installation including connection to footings
• Field welding if required