20060821111907.pdfQF EoCity of Edmonds ,011 PLAN REVIEW COMMENTS BUILDING DIVISION �sr 1g90 (425)771-0220 DATE: August 21, 2006 TO: Dave Cleven deckeonnection@earthlink.net FROM: fenny Readwin, Plans Ex e RE: Plan Check # 06-248 Project: Ziedalski Deck Project Address: 15900 70' Ave W. During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator. 1) ok 2) Plan from Geotechnical Engineer does not match plan from Structural Engineer (i.e. extra footings along the East side of the deck on the Structural Engineer's plan). Add extra footings to Geotechnical Engineer's plan or provide revise Structural Engineer's plan. On the framing plan specify size of footings under each post shown. Also, show which footings will require two piles versus one per the Structural Engineers calculations. 3) Still need. Revise section detail to reflect actual grade as well as the Geotech and Structural Engineer's requirements (i.e. footing dimensions, pin piles, grade is shown over posts, etc.). 4) Still need. Special inspections are required for the following. Complete the enclosed special inspection agreement signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance. • Soil Bearing Verification • Pin pile installation including connection to footings • Field welding if required