20060830161430.pdfCity of Edmonds 0 PLAN REVIEW COMMENTS BUILDING DIVISION Eso (425)771-0220 t 189 DATE: August 21, 2006 TO: Steve Kellett FAX (206) 542-2228 FROM: Jenny Readwin, Plans Ex in RE: Plan Check # 2006-0868 Project: Knowles 2n6 Story Garage Addition Project Address: 17627 Talbot Rd. During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) ok 2) ok 3) ok 4) ok 5) ok 6) ok 7) 8/30 Review: New ridge beam will place a point load of 6350# on the existing 6x12 -arae door headers. Provide calculations for existing header to justify that it is adequate to carry additional loads. 8/21 review: Provide calculation for new ridge beam (51/8 x 15 GLB). 818 Review: R802.3.1 requires a ridge beam design if ceiling joists or rafters are not provided at the top plate. Revise roof design to meet conventional construction or provide calculations stamped and signed by a Washington State Licensed Professional Engineer. 8) 8/30 review: Beam was increased to 7x18 and has a reaction of 7993# provide calculations to iustifv that the existine foundation is adequate to carry additional loads. 8/21 review: Provide calculation for new proposed 51/8 x 18 floor beam. 818 Review: On the building section specify post to beam connector. 9) Through 16) ok