20060845 old milltown Revision-GI & DCDA.pdf
Old Milltown - Renovation
City of Edmonds
TH
121 5 AVENUE NORTH EDMONDS, WA 98020 (425) 771-0220 FAX(425) 771-0221
Website: www.ci.edmonds.wa.us
DEVELOPMENT SERVICES DEPARTMENT
Planning Building Engineering
Plan Review Comments
Application: Date:January 2, 2008
# bld20060845
th
Project Name/Address:
Old Milltown/201 5 Ave S - Grease Interceptor and DCDA Relocation
Contact Person/Address/Fax:
: Ralph Allen / e-mail: rwallen@gracearchitectspllc.com
Reviewer: Division:
Jeanie McConnell Engineering
The resubmittal for the subject application has been reviewed but cannot be completed until the
following items have been addressed/corrected.
Please provide a written response to each item and resubmit 3 sets of revised drawings to Theresa
Umbaugh, Permit Coordinator.
1.The civil plans were not updated to show the new DCDA location and any changes, if any, to the location of
the tie in at the City main. The relocation of the DCDA will be reviewed under the civil plans. Please
revise and resubmit.
2.All plan revisions shall be clouded with an associated revision number.
3.The DCDA vault, per City standard details E7.8 and E7.8.1, is intended for application on the exterior of the
building. The proposed location, as shown per the Architectural plans, is on the interior of the building.
The vault will not be approved in the proposed location. Some of the concerns with this application include:
lighting, drainage, replacement and accessibility. Please revise the plans to show a configuration similar to
what was originally approved or with the vault location on the exterior of the building on private property.
4.The civils have been revised with regards to the grease interceptor location. Please show, revise or provide
the following:
a.Show separate lines to each kitchen facility for connections directly to the the sanitary sewer line and
connections directly to the grease interceptor. The only waste lines connected directly to the sewer at
this time appear to be the bathroom facilities.
b.Show the connection of the outfall line from the grease interceptor to the 8 sewer line within the
building.
c.The sewer line for the new public restrooms and the existing tenant spaces on the south end of Old
Milltown run through the same area as the proposed sewer line to the grease interceptor. Provide
invert elevations and additional information as needed to show there is no conflict between these
lines or revise the plans accordingly.
1 of 1
DATE E-MAILED 1/2/08
PAGE(s)