PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: September 6, 2006
TO: Dorina Iacoban
Fax (206) 365-1683
FROM: Jenny Readwin, Plans Ex e
RE: Plan Check # 2006-0988
Project: AFH Compliance
Project Address: 8327 186Th St SW
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents {affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Caretaker bedroom does not meet the minimum 44" sill height required. Closets will have to be
completely removed and this room designated as an alternate use or the window will need to be
lowered to 44". Note on plans.
2) Specify if furnace shown in caretaker bedroom closet is gas. If so it must be a direct vent unit in
order to be located in a bedroom. Specify on the plans.