20060906112102.pdforD City_ of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: September 6, 2006 TO: Dorina Iacoban Fax (206) 365-1683 FROM: Jenny Readwin, Plans Ex e RE: Plan Check # 2006-0988 Project: AFH Compliance Project Address: 8327 186Th St SW During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents {affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Caretaker bedroom does not meet the minimum 44" sill height required. Closets will have to be completely removed and this room designated as an alternate use or the window will need to be lowered to 44". Note on plans. 2) Specify if furnace shown in caretaker bedroom closet is gas. If so it must be a direct vent unit in order to be located in a bedroom. Specify on the plans.