20060911140359.pdfo� Efl City of Edmonds PLAN REVIEW COMMENTS 5 BUILDING DIVISION Esr. isa° (425) 771-0220 DATE: September 11, 2006 TO: Eric Sundquist Fax (425)774-6315 FROM: Jenny Readwin, Plans Exa ne RE: Plan Check # 2006-0972 Project: Viking Addition Project Address: 10222 244`x` St SW During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Provide existing upper and lower floor plans. 2) On the site plan specify if the deck off the South side of the house is existing or proposed 3) R403.1.3 requires all vertical rebar to have a standard hook. Revise all foundation details to reflect. 4) Provide calculations to justify that larger footings are not required under B2 and 133. 5) Specify required hangers for hung deck joists at the GLB. 6) Special inspections are required for the following. Complete the enclosed special inspection agreement signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance. Epoxy Installation