Loading...
20060925144859.pdforono City of Edmonds t PLAN REVIEW COMMENTS BUILDING DIVISION �Sr s g90 (425) 771-0220 DATE: September 25, 2006 TO: Gary Southwick Fax (425)778-7630 FROM: Jenny Readwin, Plans Exa finer RE: Plan Check # 2006-0993 Project: Addition/RemodeI Project Address: 21712 85"' PL W During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) ok 2) Based on new plan provided the deck footings do not meet conventional construction. Provide a soils evaluation stamped and signed by a Washington State Licensed Professional Geotechnical Engineer for the deck footings near the rockery area which includes recommendations for footing design. Also, provide foundation plans/section views stamped and signed by a Washington State Licensed Professional Engineer (Geotechnical or Structural) taking into account the recommendation in the Geotechnical Engineer's soils evaluation. Provide a section detail to show footings in relation to firm bearing undisturbed soil and the existing rockery. Footings must extend to firm bearing undisturbed soil. 3) ok 4) It is unclear how the deck roof beam supports are carried to bearing. The dimensioned spans on tine roof framing plan do not match the post spacing on the deck framing plan. Please clarify. Add all posts and roof beam information to the roof framing plans to verify spans. 5) ok 6) ok 7) ok 8) ok 9) ok 10) Clarify deck framing near the garage area. There are anchor bolts shown horizontally at the "existing rim joist" is this acting as a ledger? If so this connection is non -conventional and calculations stamped and signed by a Washington State Licensed Professional Engineer are required and special inspections will be required for installation (i.e. epoxy). Also provide calculations for 4x10 deck beams in this area (some are hanging off others creating point loads and, specify type of hangers to be used. Provide section details through this area to clarify. Clarify deck framing at the sistered joists. Joists must sit on the existing exterior wall of the house and top of the proposed beam or it does not meet conventional construction and must be stamped and signed by a Washington State Licensed Professional Engineer. 11) ok