PLAN REVIEW COMMENTS
- BUILDING DIVISION
FSS lg9p (425)771-0220
DATE: October 4, 2006
TO: Ross Woods
Triad Development
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2006-0695
Project: Point Edwards Grading, Shoring and Site Retaining Walls for
Buildings 6, 7, and Amenities #2
Project Address: 21, 31, 41 Pine Street
Attached are review comments from the City's consultant. Please respond in writing to each
item and include the location(s) of the changes to expedite the re -review.. Please resubmit 3 sets
of revised plans/documents to Marie Harrison, Senior Permit Coordinator.
g
Memo
To: Ann Bullis, Chief Plan Reviewer and Asst. Building Official
From: Jerry J. Barbera, P.E. and Construction Codes Consultant
Date: October 4, 2006
Re: Results of the Review of the Shoring, Retaining Wall and Grading Plans
Discussion
As I indicated in a phone message last Friday, the shoring, grading and structural changes you sent
me are almost approved pending a solution to the few items below, which have now been
confirmed:
1. No rockeries can be used to support fill in Edmonds. These are shown in sketch form on.-
Sheets
n:
Sheets 4F, 13, & 22 of 30 by the southwest corner of Building 6 along the southerly portion
of the driveway_
✓ They are also shown in sketch form on Sheet SH2O of the Shoring plans_
✓ One is also shown in specific form on the Sanitary Sewer Water Profile Sheet 28 at SSCO
15H.
2. So they need to be removed and, in fact, DCI Engineers designed the new retaining walls to
replace those rockeries that were on the lid above the parking structure.
3. The DCl Structural Engineer, .aim Brink, assures me that the prestressed plans have the correct
location of the tendons especially for those retaining walls shown on Sheet S4.2 because they
are controlling the weight of the soils by filling the lower T height with lightweight foam plastic
material.
4. The retaining wall details need to be cross referenced on the grading plans.
5. Mr. Brink needs to show drainage on the structural plans to indicate how the three foot high soil
mass is drained and therefore, there isn't any water pressure surcharge from saturated soil.
5_ Mr_ Brink is going to justify the 0.4 friction factor between the concrete retaining wall and
. concrete prestressed slab, which still needs to be submitted_