PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 10, 2006
TO: Chris Amonson
TGB Architects
Sent via e-mail
FROM: Ann Bullis, Assistant Building Official (!�07
RE: Revisions to Permit #2005-0962 & 2006-0559
Project: Revision — Exterior ramps for accessible exit from Suite 110
Project Address: 2191176' Ave W
During review of the revision for the above noted project, it was found that the following information,
clarifications or changes are needed. Please submit 2 sets of revised plans (affected sheets only) to Marie
Harrison, Permit Coordinator.
1. Revise ramp handrail height: 34" minimum to 38" maximum measured vertically to top of handrail.
2. Edge protection is required at each side of the ramp per ICCIANSI Al 17.1 Section 405.9. The 17" mid
. rail noted on the plans is not a permitted edge protection.