Plan Review Comments
Plan Check : Date:
# 20061094 1 Feb 07
Project Name/Address:
Old Woodway Elementary School Demolition
Contact Person/Address/Fax: fax/email
: Mike Creeden :425-741-3900
Reviewer: Division:Engineering
Lyle Chrisman, Engineering Program Manager
The 90% submittal has been and the following items need to be incorporated into the drawings and
specs.
Sheet C1.0
1.Add a scale to the drawing.
2.Comments from Olympic View Water and Sewer District:
a.Abandon the existing water service line (at the s.e. corner of the site)all the way to the main. If
the valve exists, cap and shut off valve.
b.The existing ssmh located on the south side of the site connects does not go south as shown on
th
the drawings, but goes to an existing ssmh on the east side of 104 Ave which is located
approximately 35’ n. of the south property line. Show the manhole and the connection between
the two manholes. Add a note to cut and cap, and add a cleanout to the 8” line, going into the
th
manhole on 104, on the right-of-way side att the property line for future use.
c.The sewer from the school connects to the ssmh on the south side of the property.
d.There are sewer manholes on site that need to be demolished. Please call Roger Eberhart at
OVWSD (425-774-7769). Also, take another look at the site
3.General note #6: Change Part V to “Part VI”.
4.Demolition note #4: Change 10000 to 9500
5.Demolition note #5: Change 4000 to 1900
6.Demoltion note #12: Remove reference of computer equipment.
__________________(Attach fax transmittal)
DATE FAXED
PAGE ____ OF ___
C:\\Users\\cockrum\\AppData\\Local\\Temp\\20061094B old woodway elementary school demo.doc_153535\\20061094B old woodway elementary school demo.doc
Sheet C2.0
7.Original comment not addressed: Show sedimentation pond on the drawing.
Specifications
8.Table of contents to be revised: See attached table of contents with Standard bid document package
9.Section 01500-1 (1.1) : This section appears to apply more to a construction project than to a
demolitions project. Edit as appropriate to demolition contract.
nd
10.Section 01500-3 (1.5D): Change temporary fencing to “portable”. Change 2 sentence to read
“Portable fencing shall be securable and supported by the use of concrete pads”
11.Section 02220-3 (2.1A): add “ and OVWSD” after City of Edmonds.
12.This comment has not been addressed. (topic under this paragraph has changed) Section 02220-4 (3.2 I)
now paragraph 3.2M: What precautions will be taken to prevent contaminates from getting into the
storm system?
13.Section 02220-5 (3.2.L): delete the remainder of the sentence beginning with the word ‘or’.
14.Section 02220-6 (3.3D.3.b) Add “ and as noted on the contract drawings”.
15.Section 02220-8 (3.3 H.3) Add “Cap pipes and” to the beginning of the statement.
16.This comment has not been addressed: Section 02321-3 (2.1 F): Specify that CDF shall be ¾ sack mix
per WSDOT standards. Will CDF be used at all?
17.Section 02300-3(2.1.B) Previous submittal referred to on-site material as suitable and now is specified as
select. Please clarify. It is our understanding that select material has tighter requirements than suitable
but the sentences are identical.
18.Section 02300-5 (3.2.A.7): delete the remainder of the sentence after the word ‘site’.
19.Section 02321-8 (3.5 D): Delete ‘telephone’.
20.Section 02371-4 (3.3.A) add between colon and ‘field’: “ Install filter fence per City of Edmonds
Standard Detail E.1.1.”
21.Part VII: Standard Details; Change ‘plan’ to “details” in the boxed enclosed note.
22.Section 02900 was omitted.
23.Section 02900-3 (2.3 B.1): the 5 pound/ 1000 sf does not match the lawn rate (2.5 A) of 8 pounds/1000
sf. Are they suppose to be the same?
24.Seciton 02900-3 (2.5A): Change perennial rye percentage to 60%; change fine fescue to Reed fescue
(Illhaee, Rainer or Pennlawn) and its percentage to 40%.