Loading...
20061103114554.pdforD City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Es o (425)771-0220 r l89 DATE: November 3, 2006 TO: Ed Baker ed@bakerengineers.com FROM: Jenny Readwin, Plans Ex n RE: Plan Check # 2006-0783 Project: Sheehan Retaining Wall Project Address: 18902 94t' Ave W. During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. 1) Special inspections need to be performed by the Geotechnical Engineer of Record (Nelson Geotechnical Associates, Inc. Please provide new signed form from Geotechnical En.-ineer of Record. Still Need. Special inspections are required for the following. Complete the enclosed special inspection agreement signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance. • Soil Bearing Verification • Excavation/Gradmg/Site Preparation • Placement of Fill and Compaction • Subsurface drainage installation • Temp and Final Erosion Control • General Site Monitoring During Wet Weather Construction • Geotech of Record to determine location and extent of damage to leaking pool as noted in Geotech report and provide recommendations for repair if necessary