20061120115731.pdfa� Eng City of Edmonds
O
PLAN REVIEW COMMENTS
- BUILDING DIVISION
(425) 771-0220
DATE: November 20, 2006
TO: Gerlach Construction, Inc.
gerlacheonst@msn.com
FROM: Jenny Readwin, Plans Ex ne
RE: Plan Check # 2006-1255
Project: Cannon Interior Remodel
Project Address: 205 Highland Drive
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) On the site plan show location/area of proposed remodel.
2) Provide complete main floor plan showing entire house.
3) An additional smoke detector is required in the hallway outside the bedrooms. Note on plans.
4) Specify source specific exhaust fans are minimum 50 cfin.
5) Provide general roof framing plan to verify that all walls being removed are non-bearing.
6) Clarify bedroom window sill height is maximum 44". Two dimensions are given on the floor
plan and it is unclear if they meet the minimum sill height requirements.