PLAN REVIEW COMMENTS
BUILDING DIVISION
Fsz. ago (425) 771-0220
DATE: December 4, 2006
TO: John Uberuaga
uberua.ga@msn.com
FROM: Jenny Readwin, Plans Exami er
RE: Plan Check # 2006-1051
Project: Uberuaga SFR
Project Address: 22319 95' PI W
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) ok
2) 12/4/06 Distance front the trap arm to the trap vent can not exceed 3'4'"per UPC 1002.1.
Distance on the plans scaled to 6'. Provide loop vent complying with UPC 909.0 or relocated
sink. Show how island sink will be vented through the roof or with a loop vent as permitted by
UPC 909.0.Air admittance valves are not permitted unless first approved by the Building
Official under and alternate method per UPC 301.2.
3) ok
4) ok
5) ok
6) ok
7) New: Provide reduce site plan that shows the entire property including flag portion.
8) New: Specify on the site plan if the rockeries shown are existing or proposed. It appears that the
rockery along the flag portion is supporting a surcharge. If this is the case a separate application
is required for rockery and the application must be signed by the adjacent property owner.