Loading...
20061204094024.pdfOV EDS City of Edmonds O PLAN REVIEW COMMENTS BUILDING DIVISION Fsz. ago (425) 771-0220 DATE: December 4, 2006 TO: John Uberuaga uberua.ga@msn.com FROM: Jenny Readwin, Plans Exami er RE: Plan Check # 2006-1051 Project: Uberuaga SFR Project Address: 22319 95' PI W During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) ok 2) 12/4/06 Distance front the trap arm to the trap vent can not exceed 3'4'"per UPC 1002.1. Distance on the plans scaled to 6'. Provide loop vent complying with UPC 909.0 or relocated sink. Show how island sink will be vented through the roof or with a loop vent as permitted by UPC 909.0.Air admittance valves are not permitted unless first approved by the Building Official under and alternate method per UPC 301.2. 3) ok 4) ok 5) ok 6) ok 7) New: Provide reduce site plan that shows the entire property including flag portion. 8) New: Specify on the site plan if the rockeries shown are existing or proposed. It appears that the rockery along the flag portion is supporting a surcharge. If this is the case a separate application is required for rockery and the application must be signed by the adjacent property owner.