20061212083919.pdfO Eby City of Edmonds 0 PLAN REVIEW COMMENTS -- BUILDING DIVISION Fsr 1$90 (425) 771-0220 DATE: December 12, 2006 TO: Gordon Gregg gordy@citybuildersinc.com FROM: Jenny Readwin, Plans Ex ine RE: Plan Check # 2006-1231 Project: Pontak Addition/Remodel Project Address: 1118 B Ave S During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Application form filled out specifies new gas water heater and boiler. Plans show existing furnace and water heater. Please clarify what is existing and what is proposed. 2) Note garage/dwelling separation on plans. Minimum %Z" sheetrock required on garage side of wall and 5/8" type X on the ceiling when there is habitable space above and minimum 20 minute rated or 1 3/8" solid core door. 3) Show size and location of attic access. 4) Provide attic ventilation calculations. 5) Each truss is required to be anchored to bearing wall with approved framing clips. Note on section detail. 6) Please provide complete framing and foundation plans including deck construction and lateral (shearwall) information included in the design calculations submitted. All this information is required to be on the plans. Not enough information was provided at this time to perform a complete a structural review. Please note it is likely that once this information is received there will be additional comments.