PLAN REVIEW COMMENTS
-- BUILDING DIVISION
Fsr 1$90 (425) 771-0220
DATE: December 12, 2006
TO: Gordon Gregg
gordy@citybuildersinc.com
FROM: Jenny Readwin, Plans Ex ine
RE: Plan Check # 2006-1231
Project: Pontak Addition/Remodel
Project Address: 1118 B Ave S
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Application form filled out specifies new gas water heater and boiler. Plans show existing
furnace and water heater. Please clarify what is existing and what is proposed.
2) Note garage/dwelling separation on plans. Minimum %Z" sheetrock required on garage side of
wall and 5/8" type X on the ceiling when there is habitable space above and minimum 20 minute
rated or 1 3/8" solid core door.
3) Show size and location of attic access.
4) Provide attic ventilation calculations.
5) Each truss is required to be anchored to bearing wall with approved framing clips. Note on
section detail.
6) Please provide complete framing and foundation plans including deck construction and lateral
(shearwall) information included in the design calculations submitted. All this information is
required to be on the plans. Not enough information was provided at this time to perform a
complete a structural review. Please note it is likely that once this information is received there
will be additional comments.