Loading...
20061214092311.pdfOV EDO City of Edmonds r. PLAN REVIEW COMMENTS BUILDING DIVISION �sr t $qo (425) 771-0220 DATE: December 14, 2006 TO: Guy Lofstrom Fax 206-364-4529 FROM: Jenny Readwin, Plans Exa er RE: Plan Check # 2006-0874 Project: Custer Project Address: 18230 Olympic View Drive During review of the above noted revision, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator. 1) ok 2) Per IRCR309.3 garage floor surfaces shall be of approved non-combustible material. R202 definition of non-combustible material states that non -combustibility must meet ASTME136. ASTM E136 specifically states that it is not intended to apply to laminated or coated materials therefore the plywood floor with `fluid applied membrane" is not considered a non-combustible surface. Please revise to approved non-combustible surface such as concrete and revise calculations to account for additional loads. Original plans showed slab on top of the joists. Please specify floor material to be used on top of existing floor joists. If concrete please include additional weight in calculations. 3) ok