Loading...
20061214144536.pdfof ono City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Est 1g90 (425) 771-0220 DATE: December 14, 2006 TO: Dennis Olson 6233" Ave N Edmonds, WA 98020 FROM: Jenny Readwin, Plans Exami RE: Plan Check # 2006-0616 Project: Olson Remodel Project Address: 623 3rd Ave N During review of the above noted revision, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator. 1) Specify size and spacing of floor joists and what they are sitting on. Also, wood in contact with concrete must be pressure treated. 2) Minimum floor insulation required is R-30 which will fit in 2x10 joists. If 2XIO's or larger are not used then rigid insulation will be required. Note on plans. 3) Specify headroom on the section detail. Code requires 7' minimum. 4) Minimum roof insulation required is R-38. Please revise plans. 5) Please show smoke detectors on the plans.