PLAN REVIEW COMMENTS
BUILDING DIVISION
Fst. l s4° (425) 771-0220
DATE: January 3, 2007
TO: Troy Renneke
FAX: 425-771-2872
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check #2006-1324, 1336
Project: Exterior Remodel
Project Address: 8705 238' Street SW
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Submit 2 sets of revised plans/documents to Marie Harrison,
Permit Coordinator.
1. Will there be any interior remodeling as part of this project? Please refer to the enclosed City's
"Commercial & Multifamily Work Exempt From Building Permit" handout.
2. We only received building plans for alterations for the north building. Provide plans for the
south building to clearly show work that will be done.
3. Provide the following information on the coversheet of the plans:
a. Written detailed scope of work for each building. Once a detailed scope of work is
provided and response to item 1 above, applicability of IBC Chapter 34 for
accessibility will be reviewed.
b. Floor area for each floor and total floor area of each building
c. Type of construction for each building. If it is Type VA construction, provide details
for 1 -hour construction, including listed and tested assemblies.
d. Number of stories for each building.
e. Occupancy for each building.
f. Occupant load for each unit and the total for each building.
4. This project is subject to RCW 64.55 (EHB 1848). Please read RCW 64.55 (which can be
found on the following website http://apps.leg.wa.gov/rcw/) to determine how it applies to your
proj ect.
a. Currently the County Assessor records show these buildings as apartments. If they
will remain apartments, enclosed is a Sale Prohibition Covenant as described in the
RCW. Complete and return to the City for recording with Snohomish County prior
to permit issuance. You will be responsible for recording costs.
b. If the buildings will be converted to condominiums, if the cost of the work is more
than 5% of the assessed value of the building, the following is required:
L Building Enclosure documents stamped and signed by a State licensed
Architect or Professional Engineer must be submitted.
ii. In addition to the building enclosure plans, the design professional must
submit a written statement stamped/signed that "The undersigned has
provided building enclosure documents that in my professional judgment are
appropriate to satisfy the requirements of RCW 64.55.005 through
64.55.090".
Hi. The building enclosure must be inspected by a qualified inspector.
1. Inspector qualifications:
a. A person with substantial and verifiable training and
experience in building enclosure design and construction.
b. Shall be free from improper interference or influence relating
to the inspections.
c. May not have a conflict of interest.
iv. Prior to final Building inspection/occupancy, the Building Enclosure
Inspector must submit a signed letter certifying that the building enclosure
has been inspected in substantial compliance with the building enclosure
design documents.
v. Where phasing of construction occurs, coordinate inspection with the City
Building Inspector to insure that all required inspections are performed.
Inspection by the building enclosure inspector to meet EHB-1848 does not
substitute for required City building inspections which must be performed by
the City Building Inspector.
c. If the cost of the work is 5% or less of the assessed value of the building, the owner
must submit a letter to the Building Official certifying this, and a written contractor's
bid for the building envelope work only.
5. Clarify on the plans if windows will be altered/replaced. If they are required egress windows
from sleeping rooms, clearly show that opening size, and sill height will be met. IBC 1025
6. Clearly show that required attic draflstops between dwelling units, and 1 -hour dwelling unit
separation (fire partition) are being maintained and carried through the new construction. IBC
708,717
7. Provide a written contractor's bid for the building envelope work only, and a separate bid for the
entire prof ect.
Page 2 of 2
City of Edmonds
COMMERCIAL & MULTIFAMILY
WORK EXEMPT FROM BUILDING PERMIT
• THE LISTED EXEMPTIONS DO NOT APPLY TO ANY PROPERTY DESIGNATED AS AN
EARTH SUBSIDENCE AND LANDSLIDE HAZARD AREA OR CRITICAL AREA
• BUILDING PERMIT EXEMPTIONS DO NOT CONSTITUTE EXEMPTION FROM
LAND USE, ZONING N BOARD REVIEW OR OTHER
PLAN*z N�' s ~ -P&M APPROVALS
� ds
The following construe �ot'I� �s ��erttpt�i�o�n o�t�n��� Criy�� dmonds Building Permit:
Accessory
is detache)
square few
must coo
N
i Deckpai
(30)'J-- e
setb k requirements for
drik�vays. Repair of exist
9 Fern
acce,
Gra,
criti
Gas
•
sds, playousesd sar uses, provided the building
rye �eteorvall�r post does not exceed 120
enentts s ould'be Birt ('0 es. Accessory structures
�%uentsfor �o�xe
adewalks, rampsd dnvewaysat do not exceed thirty
:t part of an aceessrle rauto o t el. Must comply with
rig Division for adclrtional excepats) for walkways and
idel work Is hrmted to fndlviclual decking members, joists,
N:
nye rs nat te, . Cit right-of-wayor
aei and notrec}z�ured byapter 17.30 ECDC_
e grading rs At an,. solafe _ f contained and non -
system and are not
• Steam, hot or chilled water piping within any heating or cooling equipment regulated by ECDC.
• Portable fuel cell appliances that are not connected to a fixed piping system and are not
interconnected to a power grid_
Moveable cases, shelving, cabinets, and partitions not over 5'-9" in height_
L:ITEMPIBUILDINGIHANDOUT ICODMEXEMPTCOMM.doe
Revised 9/06
i Parking lot re -striping, provided there is no change to existing striping or markings (i.e. traffic control
direction arrows, fire lanes, accessible striping) that would be contrary to the latest approved parking
lot striping plan on. file with the City.
Plumbing work/appliances:
• Stopping leaks in drains, water, soil, waste or vent pipe, valves or fixtures provided such repair
does not involve or require the replacement of pipes, valves, fixtures or traps.
• The clearing of stoppages or the repairing of leaks in pipes, valves or fixtures, and the removal and
reinstallation of water closets, provided such repairs do not involve or require the replacement or
rearrangement of valves, pipes or fixtures.
i Swimming pools (prefabricatecl�t"ec�alls�entirely above grade and the capacity does not
exceed 5,000 gallons. sand spas lesshan 5,O0'lpns, provided completely supported by the
ground. Pools, hot # and spa must comply wti setback regiments for zone.
Painting, papery tsing, cabinets, countertops, vinyl . floormR, eating, molding and similar finish
work.
Playgroungmprnent incldtng swtzigs ar�aTio arks
i Retaining waits dinei
our (4) feet hght or TeIML
ss measured vertically frorY he finished grade at the
expose'toe: of tyre retairntig vr�all to tlxe luglcst pont unless.
•
Si-
po - n a surcharge - .
• l pot�ximg ala s 1;IIs 111 hghtds
• Gated �I d critical area ' fZ taim€i-mall's must comply with setback and bight requirements for
ne
Ro eves less than eight (8) feet inti meed ,veriieally from the fihedgrade at the toe of the
roc ry to e'hrghest pnrnt, pro s of a os�on prot U' " purP ffle only and is placed
ag st anstxng�cut sl�Qpc
• caked to a tpticl area ply equirements for zone.
Shad s es icons a es
Signs
• Re pn a sign.
• Repan ing p&Nvo
• Painte eringlon st m
• Governme s, carlpai igns required by provision of
local, state o f lamPI (i.e.
• Temporary signs our>1cing other temporary signs as described in
ECDC 20.60.080 (i.e. x . r _ x plays)
i Temporary motion picture, televisiol, stage sets and scenery.
Television antennas less than thirty=nine (39) inches in diameter.
Water tanks supported directly by ground not exceeding 500 gallons provided, the ratio of height to
diameter or width does not exceed 2:1. Must comply with setback and height requirements for zone.
Windows or door replacement provided no change is made in the size or framing.
Please call the Building Department and ask to speak with a Permit Coordinator if you are unsure whether or
not the construction project. you are about to undertake requires a building permit. You could be saving
violation fees if it is later determined that a permit was required (425-771-0220).
LITEMPIBUILDINGIHANDOUT ICODESIEXEMPTCOMM-doe
Revised 9/06
After Recording return to:
City of Edmonds
Building Division
121 5th Avenue North - 2nd Floor
Edmonds, WA 98020
Document Title(s)
Sale Prohibition Covenant of Multiunit Residential Building
Reference Number(s) of Related Documents
NIA
Grantor(s) (Last, First and Middle Initial)
Grantee(S) (Last, First and Middle Initial)
State of Washington
Legal Description (abbreviated form; i.e., lot, plat or section,. township, range, quarter/quarter)
(Full legal description on Exhibit A)
Assessor's Property Tax Parcel/Account Number at the Time of Recording:
The Auditor/Recorder will rely on the information provided on this form_ The staff will not read the document to verity the accuracy or
completeness of the indexing information provided herein.
(BFP624253 _DOC; 1100006.900000/)
Sale Prohibition Covenant of Multiunit Residential Building
Pursuant to Chapter 64.55 RCW
This covenant has been recorded in the real property records of Snohomish County, Washington,
in satisfaction of the requirements of RCW 64.55.010 through RCW 64.55.090. The
undersigned grantor is the owner of the property described on Exhibit A (the "Property"), which
is addressed in the records of the City of Edmonds Building Division as
The owner of the Property
irrevocably covenants and agrees that until termination of this covenant, no dwelling unit in or
on the Property may be sold as a condominium unit except for disposition listed in RCW
64.34.400(2).
This covenant terminates on the earlier of either: (a) Compliance with the requirements of RCW
64.55.090, as certified by the owner of the Property in a recorded supplement hereto; or (b) the
fifth anniversary of the date of first occupancy of a dwelling unit as certified 'by the owner of the
property in a recorded supplement hereto.
This covenant shall run with the land and shall bind the grantor and the grantor's heirs, personal
representatives, successors in interest and assigns.
DATED:
GRANTOR
STATE OF WASHINGTON)
COUNTY OF SNOHOMISH )
On this day appeared before me
that he/she executed this document for the uses and purposes herein mentioned.
DATED:
NOTARY PUBLIC
Printed Name:
My Commission expires:
{8FP624248_D0C;1 /00006.900040/}
and stated
Sale Prohibition Covenant of Multiunit Residential Building
Pursuant to Chapter 64.55 RCW
This covenant has been recorded in the real property records of Snohomish County, Washington,
in satisfaction of the requirements of RCW 64.55.010 through RCW 64.55.090. The
undersigned grantor is the owner of the property described on Exhibit A (the "Property"), which
is addressed in the records of the City of Edmonds Building Division as
. The owner of the Property
irrevocably covenants and agrees that until termination of this covenant, no dwelling unit in or
on the Property may be sold as a condominium unit except for dispositions listed in RCW
64.34.400(2).
This covenant terminates on the earlier of either: (a) Compliance with the requirements of RCW
64.55.090, as certified by the owner of the Property in a recorded supplement hereto; or (b) the
fifth anniversary of the date of first occupancy of a dwelling unit as certified by the owner of the
property in a recorded supplement hereto.
This covenant- shall run with the land and shall bind the grantor and the grantor's heirs, personal
representatives, successors in interest and assigns.
DATED:
GRANTORS
By:
Its:
STATE OF WASHINGTON)
COUNTY OF SNOHOMISH )
On this day appeared before me the
, of , and stated that he/she is
authorized to execute this document on behalf of said corporation for the uses and purposed
herein mentioned.
DATED:
NOTARY PUBLIC
Printed Name:
My Cominission expires:
IBFP624261 _DOC;] /00006.900000/j