20070122142455.pdfor Eao City of Edmonds =CJS PLAN REVIEW COMMENTS BUILDING DIVISION Fst. g9° (425) 771-0220 DATE: January 22, 2007 TO: Bruce Smith FAX: 425-742-5718 FROM: Ann Bullis, Assistant Building Official RE: Plan Check #2006-1386 Project: Greenberg Mechanical/HVAC Project Address: 155 3`d Ave S During review of the plans/documents for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Submit 2 sets of revised plans/documents to Marie Harrison, Permit Coordinator. 1. The mechanical plans as drawn are difficult to read. Attached is the mechanical handout which contains the submittal requirements. Please revise the plans so a complete review can be done. 2. Basement floor plan is missing from this application and must be included. The approved architectural plans for this building show a mechanical room with boiler and water heater on the lower floor next to the trash enclosure, with venting though the large shaft at the center of the building. If this will no longer be used as a mechanical room and the shaft will be altered, submit revised architectural and mechanical plans. The architectural revision must be stamped and signed by the Engineer of Record for this project. 3. Provide elevator equipment ventilation system (supply and exhaust) on the basement floor plan. Show duct path(s) to the exterior of the building. 4. Garage mechanical ventilation must be included in this permit. The 1 -hour fire rated garage exhaust shaft is shown on the approved architectural plans. Provide manufacturer's information for the exhaust fan. The approved architectural plans note the fan size as 6200 cfm. Verify that the shaft size will accommodate the proposed exhaust fan. If the shaft needs to be altered to accommodate the exhaust system, provide revised architectural and mechanical plans. The architectural revision must be stamped and signed by the Engineer of Record for this project. 5. Complete the attached State Energy Code forms for Mechanical and return for review. 6. This is a Type VA (1 -hour fire rated) building. Where ducts, exhaust fans, etc. penetrate the 1 -hour fire rated assemblies, show how the rating will be maintained, such as with lined joist bays, vertical shafts, soffits, etc., and provide details. 7. Mechanical ventilation (supply and return) must be provided to each room/space on the 1St floor (office floor). Clearly show this on the plans. S. Complete the enclosed ventilation worksheets for the two dwelling units. 9. The approved plans for this building do not show a suspended ceiling system on any of the floors. If there will be a suspended ceiling system, provide revised architectural and mechanical plans, including seismic anchoring details, and seismic anchoring details for office partitions. The architectural revision must be stamped and signed by the Engineer of Record for this project. 10. Provide listed and tested fire stopping assemblies for each type/size of penetration (ducts, gas piping, etc.). 11. The restrooms (both floors) must each have minimum 50 cfm exhaust fans. 12. Ducts not permitted to pass through the 1 -hour fire rated stair enclosures, nor the 1 -hour rated assemblies that enclose the stairway. Provide details showing how ducts will be run at the stair enclosure areas without penetrating the 1 -hour fire rated floor, wall, or ceiling assemblies of the enclosure. IBC 1019.1.2 13. Clearly show how combustion air will be provided to the gas-fired appliances. 14. Provide a roof plan showing location of duct outlets and roof mounted equipment. No penetrations are permitted within 5 feet of the north and south property lines. See approved architectural roof plans for location. 15. Show the location(s) of the water heater(s) for the office floor. 16. Will there be roof -mounted equipment? The permit application notes that there will be 4 air conditioners, but they are not shown on the plans. Also provide manufacturer's information as noted in the handout. IT Dimension the distance of exhaust outlets in exterior walls in relation to building openings. Page 2 of 2 VENTILATION WORKSHEET SOURCE SPECIFIC VENTILATION: Exhaust fans are required in each kitchen, bathroom, laundry room, indoor swimming pool, spa, and other room(s) where excess water vapor or cooking odor is produced. Complete the following table: Location.. Required CFM Actual CFM KITCHEN FAN 100 CFM BATHROOM #1 FAN 50 CFM BATHROOM #2 FAN 50 CFM BATHROOM #3 FAN 50 CFM LAUNDRY FAN 50 CFM WHOLE HOUSE VENTILATION: Each dwelling unit shall be equipped with a whole house ventilation system supplying outdoor air to all habitable rooms and exhausting stale air out via a designated fan. Complete the following questions and table: ❑ Not applicable for additions less than 500 sq.ft. SELECT TYPE OF WHOLE HOUSE VENTILATION SYSTEM TO BE USED: ❑ Exhaust fan system with ducted forced air heating system (VIAQ 303.4.1): • Exhaust fan sized per table below with 24 hour timer. • Forced air heating system ducted to all habitable rooms. • Interior doors undercut %2" minimum above floor covering. ❑ Exhaust fan system with fresh air inlets(VIAQ 303.4.1):, • Exhaust fan sized per table below with 24 hour timer. • Manual through -wall port or approved window vent. ❑ Inte rated with forced air furnace S stem (VIAQ 303.4.2): • Outdoor air inlet duct sized per table 3-5 connected to the return air plenum of the forced air system. • Volume damper. ❑ Supply fan system (VIAQ 303.4.3): • Distribute air through the forced -air system ducts or through dedicated ducts to each habitable space with 24 hour timer. • Outdoor air must be filtered • Outdoor air inlet connected to supply or return. • Back draft and volume dampers. ❑ Heat recovery system (VIAQ 303.4.4) L:ITEMPIBUILDINGIHANDOLiT ICODESIENERGY B26.DOC Last Date Revised: 1/22/2007 A WHOLE HOUSE EXHAUST FAN MUST BE PROVIDED FOR EACH DWELLING UNIT. Floor Area Bedrooms* (square feet) 2 or less 3 4 5 6 Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. <500 50 75 65 98 80 120 95 143 110 165 501-1000 55 83 70 105 85 128 100 150 115 173 1001-1500 60 90 75 113 90 135 105 158 120 180 1501-2000 65 98 80 120 95 143 110 165 125 188 2001-2500 70 105 85 128 100 150 115 173 130 195 2501-3000 75 113 90 135 105 158 120 180 135 203 3001-3500 80 120 95 143 110 165 125 188 140 210 3501-4000 85 128 100 150 115 173 130 195 143 218 4001-5000 95 143 110 165 125 188 140 210 155 233 *for more than 6 bedrooms and/or over 5000 square feet see Table 3-2 Washington State Ventilation and Indoor Air Quality Code. Total Floor area: Bedrooms: Whole House Fan Size: Location: ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE INTERMITTENTLY? Yes ❑ No ❑ Both automatic and manual control needed. Automatic control timer shall be set to operate whole house fan for a minimum of eight hours per day. WHOLE HOUSE EXHAUST FAN ALSO SERVES AS A BATH OR LAUNDRY FAN? Yes ❑ No ❑ The capacity shall be the larger CFM requirement. ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE CONTINUOUSLY? Yes ❑ No ❑ Note: Installers shall provide the manufacturer's installation, operating instructions, and a whole house ventilation system operation description. A label shall be affixed to the whole house timer control that reads "Whole House Ventilation (see operating instructions). " L:ITEMPIBUILDINGIHANDOUT ICODESIENERGY B26.DOC Last Date Revised: 1/22/2007 r� city of edmonds development information Commercial Mechanical/HVAC Permit Submittal Requirements PERMIT REQUIRED: A permit is required for the installation of mechanical equipment. CODES: International Building (IBC) and Mechanical (IMC) Code (2003 Edition) Uniform Plumbing Code (UPC) (2003 Edition) International Fuel Gas Code (2003 Edition) Washington State Energy Code (WSEC) (2003 Edition) Washington State Ventilation & Indoor Air Quality Code (VIAQ) (2003) FEE: Based on size and type of equipment or appliance SUBMITTAL REQUIREMENTS: 1. Two (2) sets of plans must be submitted showing the following: a) Locations of all heating, ventilation, air conditioning equipment. Provide manufacturer's specifications. Note fuel source, Btu input/output. b) Submit applicable State Non -Residential Energy Code compliance forms. Forms can be found on the web at hLtp://www.neec.net/resources/resources.btml. c) Show duct smoke alarm (detector) locations. d) Show or detail how combustion air will be provided. e) Provide HVAC ductwork layout, including supply diffusers, return air grills, and cfm. f) Specify duct and pipe insulation R -value, and duct sealing. g) Label all plenums and provide details showing plenum construction and exposed materials within the plenum. h) For roof mounted equipment, provide weight of equipment and structural support information, including roof framing plans, snow and dead loads, etc. Provide building elevations showing visibility of mechanical equipment and screening and equipment dimensions_ i) Provide construction details for mechanical equipment support structures, including wall and ceiling platforms. j) Dimension clearances around mechanical equipment. k) Show condensate waste discharge location. 1) Provide seismic anchoring details. m) Provide outdoor air calculations per State VIAQ Table 3-4 and show how it will be provided/distributed. n) Show location and size of all exhaust fans_ o) Provide parking garage ventilation calculations, show location and size of supply and exhaust fans, and location of exhaust outlet to building openings, supply inlets, property lines, and height above grade. p) Location and type of all fire/smoke dampers. Provide manufacturer's specifications. q) Venting path for exhaust ducts, dryer vents, gas appliance vents, B -vents, etc. and show outlet/inlet locations. r) Locations and construction details of all mechanical shafts, including listed and tested assemblies. s) Gas piping layout, sizing, pipe material, and support hanger spacing, and number of gas piping outlets. NOTE: All listed and tested appliances or units shall be installed per the manufacturer's specifications. NOTE. THE PURPOSE OF THIS HANDOUT IS TO ASSIST THE PUBLIC IN COMPLY]NG WITH DETAILED PERMIT SUBMITTAL RE UIREMENTS_ IT I5 NOT A COMPLETE LIST OF PERMIT OR CODE REQUIREMENTS AND SHOULD NOT BE USED AS A SUBSTITUTE FOR APPLICABLE CAWS AND REGULATIONS_ IT IS THE RESPONSIBILITY OF THE OWNER/DFSIGN PROFESSIONAL TO REVIEW THE SUBMITTAL FOR COMPLETENESS AND APPLICABILITY TO OTHER CODES. ONLY COMPLETE APPLICATIONS WILL BE ACCEPTED BY THE CITY FOR REVIEW L:ATEMPIBUILDINGIHANDOUT ]CODESWOMMECHicodes_DOC Revised 7104 2004 Washington State Nonresidential 2004 Washington State Nonresidential Energy Code Compliance Forms Code Compli, Form Revised May 2005 Project Info Project Address Date Capacity2 OSA CFM SEER Btulh Total CFM or Econo? or EER IPLV3 Location For Building Dept. Use Applicant Name: Applicant Address: Applicant Phone: Project Description Briefly describe mechanical system type and features. ❑ Includes Plans Include documentation requiring compliance with commissioning requirements, Section 1416. 0 Simple System 0 Complex System 0 Systems Analysis COl>KkpllanCe Option (See Decision Flowchart (over) for qualifications. Use separate MECH-SUM for simple & complex systems.) Equipment Schedules The following information is required to be incorporated with the mechanical equipment Schedules on the plans. For projects without plans, fill in the required information below. Cooling Equipment Schedule Equip. Capacity, OSA cfm ID Brand Name' Model No.' Btulh Total CFM or Econo? Input Btuh Equip. ID Brand Name' Model No.' Capacity2 OSA CFM SEER Btulh Total CFM or Econo? or EER IPLV3 Location Heating Equipment Schedule Equip. Capacity, OSA cfm ID Brand Name' Model No.' Btulh Total CFM or Econo? Input Btuh Output Btuh Efficiency4 Fan Equipment Schedule Equip. ID Brand Name' Madel No.' CFM SP' HP/BHP Flow Controls Location of Service 'If available. , As tested according to Table 14-1A through 14-1G. 3 if required. a COP, HSPF, Combustion Efficiency, or AFUE, as applicable. s Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS). 2004 Washington State Nonresidential Energy Code Compliance Form System Description See Section 1421 for full description of Simple System qualifications. If Heating/Cooling or Cooling Only: ❑ Constant vol? ❑ Split system? ❑ Air cooled? ❑ Packaged sys? ❑ <20,000 Btuh? ❑ Economizer included? If Heating Only: ❑ <5000 cfm? ❑ <70% outside air? Decision Flowchart Use this flowchart to determine if project qualifies for Simple System Option. if not, either the Complex System or Systems Analysis Options must be used. START Heating/Cooling Air Cooled, System Type or Cooling Only Constant Vol? No Reference Heating Only Section 1421 Yes <5000 Ingle plit Syste cfm? Yes Package N <-84,000 Yes Unit? Btuh? No Yes <70% OSA �—Y EEcono ool Ca con d? N <20,000 N Btuh? Yes Yes Reference Section 1423 Simple System Allowed (section 1420) /Total Ca wo econor <240,000 1 or 10% Yes or Adjacent to No <54,000 Use Complex Systems (section 1430) Refer to MECH-COMP Mechanical Complex Systems for assistance in determining which Complex Systems Complex Systems requirements are applicable to this project. 2004 Washinaton State Nonresidential Fnerav CndP Comnliance Farre Mechanical - Complex Systems Checklist MECH-COMP 2004 Washington State Nonresidential Energy Code Compliance Forms Revised May 2005 Project Address Date The following additional information is necessary to check a mechanical permit application for a complex For Building Department Use mechanical system for compliance with the mechanical requirements in the Washington State Nonresidential Section 1431.1 Energy Code. Use the checklist as a reference for notes added to the mechanical drawings (see the MECH- Section 1432.2.2 riot CHK checklist for additional system requirements). This information must be on the plans since this is the Calculations of Total official record of the permit Having this information in separate specifications alone is NOT an acceptable Water Supply alternative. On -Site Energy Input Applicability Code Maximum Jacket & Oupui Required Location Building Department (yes, no, n -a-) I Section Component I Information Required on Plans Notes ADDITIONAL CHECKLIST ITEMS FOR COMPLEX SYSTEMS ONLY 1431.1 Field assem. sys- Provide calculations Controls Required (continued 1432.1 Setback & shut-off Indicate separate systems or show isolation devices on plans 1432.2.1 Air system reset Indicate automatic reset 1432-2.2 Hydr. system reset Indicate automatic reset Indicate economizer on equipment schedule or provide 1433 Air Economizer calculations to justify exemption and demonstrate 10% higher efficiency for equipment with out economizer. Indicate water economizer and provide calculations if 1433 1433 Water Economizer Exception 2 is utilized 1434 Separate air sys. Indicate separate systems on plans Indicate that simultaneous heating and cooling is prohibited, 1435 Simul. htg. & clg. unless use of exception is justified Indicate heat recovery on plans; complete and attach treat 1436 Heat recovery recovery calculations 1437 Elec. motor effic. MECH-MOT or Equip. Schedule with hp, rpm, efficiency 1438 Variable flow sys. Indicate variable flow on fan and pump schedules 1439.1 Kitchen Hoods Indicate uncooled and unheated make-up air 1439.2 Fume Hoods Indicate VAV, unheatedluncooled or heat rec. makeup IT no is circiea ror any question, provtae explanation: Decision Flowchart Use this flowchart to determine how the requirements of the Complex Systems Option apply to the project. Refer to the indicated Code sections for more complete information on the requirements. Start Here Section Effir Air System apacity of HW, Equipment Efficiency��> lOii Furnace Field -Assembled N Serving Multiple N Heating System > Shall Meet Tables5,0008tuh? Equipment? Zones? 00,000 Btuh� 14-1A through 14-1G Yes Yes Yes Yes No 1411,1 Intermittent Ignition Device & Section 1431.1 Section 1432.2.2 riot Power Venting or Calculations of Total Section 1432.2.1 Water Supply Damper, 0.75% On -Site Energy Input Supply Air Reset ' Temperature Reset Maximum Jacket & Oupui Required Controls Required Required Loss 1412.6 Modulating or Staged Combustion Controls Required (continued onback} 2004 Washington State Nonresidential Enerqv Code Compliance Form 2004 Washington State Nonresidential Energy Code Compliance Forms 0% Air Econ Provided? Section 1413 Yes No Water Cooled\N_ /EER 10% Bel /Water Econo? / 0`T than Code Yes Yes Total Clg tal Cap. ! Section 1433 Capacity w! N conn <=480,00 N Air -Side Economizer Water Econo Btuh or 20% of Required <50D Tons otal Cap.? Yes Yes Yes ..J ipply Air >5,0ZMI Section 1436 cfm & OSA > Ye 50% Effective Heat . 71 Recovery Required otor Incl. [ Multi speed Section 1437 gpmt. Covr'd by Motors Must Meet N Motor in Multi- N Tbl 14-1A-14- eed system? Efficiencies in 1G? Table 14-4 Yes Yes Yes Section 1435 ystem or Zone Zone Controls Must wt Simultaneous Yes Reduce Supply Air Htg. & Clg.? Quantity Before ReheatinglRecooling No (Application Section 1438 s Variable Ye ans or Pumps >Ye Variable Flow low? 10 HP? Devices Required No No Yes Revised May 2005 Section 1439.2 o Bldg. Fu One Required: Exhaust > 15,000 Yes— a. 50% VAV Exhaust & cfm? Make-up b. 75% Direct Makeup wl Tempering Only No c. Heat Recovery per 1436 Section 1439.1 d. Constant Volume wl Itchen Exhau No Heating or < 50fpm Face Velocity Hood > 5,000 Ye Cooling for at least I c No DONE 50% of Make-up Air Yes Yes Revised May 2005 2004 Washington State Nonresidential Enerov Code Compliance Form Electric • a • 2004 Washington State Nonresidential Energy Code Compliance Forms Revised May 2005 Project Address Date Complete the following for all design A & B squirrel -cage, T -frame induction permanently wired polyphase motors from 1 hp to 200 hp having synchronous speeds of 3600, 1800 or 1200 rpm (unless one of the exceptions below applies). For Building Department Use Motor No. or Location HP Type (openiclosed) Description of Application or Use Min.Notn. Synch. Full load Speed Efficiency Minimum Nominal Full -Load Efficiency Open Motors Closed Motors Exceptions: Motors in systems designed to use more than one speed of a multi -speed motor. 2. Motors already included in the efficiency requirements for HVAC equipment (Tables 14-1 or 14-2) 3. Motors that are an integral part (i.e. not easily removed and replaced of specialized process equipment (i.e. equipment which requires a special motor, such as an explosion - proof motor). 4. Motors integral to a listed piece of equipment for which no qualifying motor has been approved (i.e. if the only U.L. listing for the equipment is with a less -efficient motor and there is no energy-efficient motor option). For motors claiming an exception, list motor and note which exception applies. Synchronous1. Speed (RPM) 3,600 1,800 1,200 3,600 1,800 1,200 HP Efficiency (%) Efficiency (%) 1.0 - 82.5 80.0 75.5 82-5 80.0 1.5 825 84.0 84.0 82.5 84.0 85.5 2.0 84.0 84.0 85.5 84.0 84.0 86.5 3.0 84.0 86.5 86.5 85.5 87.5 87.5 5.0 85.5 87.5 87.5 87.5 87.5 87.5 7.5 87.5 88.5 88.5 88.5 89.5 89.5 10 88.5 89.5 90.2 89.5 89.5 89.5 15 89.5 91.0 90.2 90.2 91.0 90.2 20 90.2 91.0 91.0 90.2 91.0 90.2 25 91.0 91.7 91.7 91.0 92.4 91.7 30 91.0 92.4 92.4 91.0 92.4 91.7 40 91.7 93.0 93.0 91.7 93.0 93.0 50 92.4 93.0 93.0 92.4 93.0 93.0 60 93.0 93.6 93.6 93.0 93.6 93.6 75 93.0 94.1 93.6 93.0 94.1 93.6 100 93.0 944.9 94.1 93.6 94.5 94.1 125 93.6 94.5 94.1 94.5 94.5 94.1 150 93.6 95.0 94.5 94.5 95.0 95.0 200 94.5 95.0 94.5 95.0 95.0 1 95.0 2004 Washington State ]Nonresidential Energy Code Compliance Form ,Mechanical H L -C H 2004 Washington State Hlonresidential Energy Code compliance Forms Revised May 2005 Project Address Date The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the Washington State Nonresidential Energy Code. Applicability (yes, no, n.a. ) Code Section Component Information Required Location on Plans Building Department Notes HVAC REQUIREMENTS (Sections 1401-1424) 1411 Equipment performance 1411.4 Pkg. elec. htg.& clg. List heat pumps on schedule 1411.1 Minimum efficiency Equipment schedule with type, capacity, efficiency 1411.1 Combustion htg. Indicate intermittent ignition, flueldraft damper & jacket loss 9412 HVAC controls 9412.1 Temperature zones Indicate locations on plans 1412.2 Deadband control Indicate 5 degree deadband minimum 1412.3 Humidity control Indicate humidistat 1412.4 Automatic setback Indicate thermostat with night setback and 7 diff_ day types 1412.4.1 Dampers Indicate damper location and auto. controls & max. leakage 1412.4.2 Optimum Start Indicate optimum start controls 1412.5 Heat pump control Indicate microprocessor on thermostat schedule 1412.6 Combustion htg. Indicate modulating or staged control 1412.7 Balancing Indicate balancing features on plans 1422 Thermostat interlock Indicate thermostat interlock on plans 1423 Economizers Equipment schedule 1413 Air economizers 1413.1 Air Econo Operation Indicate 100% capability on schedule 1413.1 Wtr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F wb 1413.2 Water Econo Doc Indicate clg load & water econoe & clg tower performance 1413.3 Integrated operation Indicate capability for partial cooling 1413.4 Humidification Indicate direct evap or fog atomization wl air economizer 1414 Ducting systems 1414.1 Duct seating indicate sealing necessary 1414.2 Duct insulation Indicate R -value of insulation on duct 1415.1 Piping insulation Indicate R -value of insulation on piping 1416 Completion Requirements 1416.1 &2 Drawings & Manuals Indicate requirement for record drawings and operation docs. 1416.3.2 Air Balancing Indicate air system balance requirements 1416.3.3 Hydronic Balancing Indicate hydronic system balance requirements 1416.4 Commissioning Indicate requirements for commissioning and prelim. Report 1424 Separate air Sys. Indicate separate systems on plans Mechanical Summary Form Completed and attached. Equipment schedule with types, input/output, efficiency, cfm, hp, economizer SERVICE-WATER-HEATIN-G-AN13 HEATED POOLS (Sections 1440-1454) 1440 Service water htg. 1441 Elec. water heater Indicate R-10 insulation under tank 1442 Shut-off controls Indicate automatic shut-off 1443 Pipe Insulation Indicate R -value of insulation on piping 1452 Heat Pump COP Indicate minimum COP of 4.0 1452 Heater Efficiency Indicate pool heater efficiency 1453 Pool heater controls indicate switch and 65 degree control 1454 Pool covers Indicate vapor retardant cover 1454 Pools 90+ degrees Indicate R-12 pool cover If "no" is circled for any question, provide explanation: 2004 Washinciton State Nonresidential Enerciv Code Corrioliance Form echanlcal - General Requ 1411.1 General: Equipment shall have a minimum performance at the specified rating conditions not less than the values shown in Table 14 -IA through 14-1G. It a nationally recognized certification program exists for a product covered in Tables 14-tA through 14-1 G. and it includes provisions forverification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program. Gas-fired and oil -fired forced air furnaces with input ratings > 225,000 Blulh (65 kW) shall also have an intermittent ignition or interrupted device (nD), and have either mechanical draft (including power venting) or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings > 225,000 Btuth (65 kW), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75% of the input rating. 1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions and procedures when available. Where no applicable procedures exist, data shall be furnished by the equipment manufacturer. 1411.3 Combination Space and Service Water Heating: For combination space and service water heaters with a principal function of providing space heat, the Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard 124-1991. Storage water heaters used in combination space heat and water heat applications shall have either an Energy FActor (EF) or a CAE of not less than the following: EF CAE < 50 gal storage 0.58 0.71 SO to 70 gal storage 0.57 0.71 >70 gal stora a 0.55 0.70 1411.4 Packaged Electric Heating and Cooling Equipment: Packaged electric equipment providing both heating and cooling with a total cooling capacity greater than 20,000 Bluth shall be a heat pump. Exception: Unstaffed equipment shaelters or cabinets used solely for personal wireless service facilities. 1412 Controls 1412.1 Temperature Controls: Each system shall be provided with at least one temperature control device. Each zone shall be controlled by individual thermostatic controls responding to temperature within the zone. At a minimum, each floor of a building shall be considered as a separate za ne. 1412.2 Deadband Controls: When used to control both comfort heating and cooling, zone thermostatic controls shall be capable of a deadband of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut-off or reduced to a minimum. Exceptions: 1. Special occupancy, special usage, or code requirements where deadband controls are not appropriate. 2. Buildings complying with Section 1141-4, if in the proposed building energy analysis, heating and cooling thermostat setpoints are set to the same temperature between 70 degrees F and 75 degrees F inclusive, and assumed to be constant throughout the year. 3. Thermostats that require manual changeover between heating and cooling modes. 1412.3 Humidity Controls: If a system is equipped with a means for adding moisture, a humidistat shall be provided. 4412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through control setback or equipment shutdown during periods of non-use or alternate use of the spaces served by the system. The automatic controls shall have a minimum seven-day clock and be capable of being set for seven different day types per week. . Exceptions: 1. Systems serving areas which require continuous operation at the same temperature setpoint. 2. Equipment with full load demands at kW (6,826 Bluth) or less may be controlled by readily accessible manual oft -hour controls. 1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving conditioned spaces shall be equipped with dampers which close automatically when the system is offer upon power failure. Exceptions: 1. Systems serving areas which require continuous operation. 2. Combustion air intakes. 3. Gravity (nonmotorized) dampers are acceptable in buildings less than 3 stories in height. 4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief outlets in the first story and levels below the first story of buildings three or more stories in height, 1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply air capacities exceeding 10,000 cfm shall have optimum start controls. Optimum start controls shall be designed to automatically adjust the start time of an HVAC system each day to bring the space to desired occupied temperature levels immediately before scheduled occupancy. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint and the amount of time prior to scheduled occupancy. 1412.5 Heat Pump Controls: Unitary air cooled heat pumps shalf include microprocessor controls that minimize supplemental heat usage during start-up, set-up, and defrost conditions. These controls shall anticipate need for heat and use compression heating as the first stage of heat. Controls shall indicate when supplemental heating is being used through visual means (e.g., LED indicators). 1412.6 Combustion Heating Equipment Controls: Combustion heating equipment with a capacity over 225,000 Bluth shat€ have modulating or staged combustion control. Exceptions: 1. Boilers. 2- Radiant Heaters. Revised May 2005 1412.1 Balancing: Each air supply outlet or air or water termina evice shall have a means for balancing, including but not limited to, dampers, temperature and pressure test connections and balancing valves. 1413 Air Economizers 1413.1 Operation: Air economizers shall be of automatically modulating outside and return air dampers to provide 100 percent of the design supply air as outside air to reduce or eliminate the need for mechanical cooling. Water economizers shall be capable of providing the total concurrent cooling load served by the conneted terminal equipment lacking airside economizer, at outside air temperatures of 45°F dry-bulbl40*F wet -butte and below. For this calculation, all factors including solar and internal load shall be the same as those used for peak load calculations, except for the outside temperatures. Exception: Water economizers using air-cooled heat rejection equipment may use a 35°F dry-bulb outside air temperature for this calculation. This exception is limited to a maximum of 20 tons per building. 1413.2 Documentation: Water economizer plans submitted for approval shall include the following information: 1. Maximum outside air conditions for which economizer is sized to provide full cooling. 2. Design cooling load to be provided by economizer at this outside air condition. 3_ Heat rejection and terminal equipment performance data including model number, Flow rate, capacity, entering and leaving temperature in full economizer cooling mode. 1413.3 Integrated Operation: Air economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Exceptions: 1. Individual, direct expansion units that have a rated capacity less than 65,000 Bluth and use nonintegrated economizer controls that preclude simultaneous operation of the economizer and mechanical cooling. 2. Water-cooled water chillers with waterside economizer. 1413.4 Humidification: If an air economizer is required on a cooling system for which humidification equipment is 10 be provided to maintain minimum Indoor humidity levels. then the humidifier shall be of the adiabatic type (direct evaporative media or tog atomization type). Exceptions: 1. Health care facilities where WAC 246-320-525 allows only steam injection humidifiers in ductwork downstream of final filters. 1412.6 Combustion Heating Equipment Controls: Combustion heating equipment with a capacity over 225,000 Btulh shall have modulating or staged combustion control. 2. Systems with water economizer 3. 100% outside air systems with no provisions for air recirculation to the central supply fan. 4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a building's air economizer capacity as measured in cfm. This refers to the system cfm serving roams with stand alone or duct mounted humidifiers. 1414 Ducting Systems 1414.1 Sealing: Duct work which is designed to operate at pressures above 112 inch water column static pressure shall he sealed in accordance with Standard RS -18. Extent of sealing required is as follows: 1. Static pressure: 112 inch to 2 inches; seal transverse joints. 2. Static pressure: 2 inches to 3 inches; seal all transverse joints and longitudinal seams. 3. Static pressure: above 3 inches; seal all transverse joints, longitudinal seams and duct wall penetrations. Duct tape and other pressure sensitive tape shall not be used as the primary sealant where ducts are designed to operate at static pressures of 1 inch W .C. or greater. 1414.2 insulation: Ducts and plenums that are constructed and function as part of the building envelope, by separating interior space from exterior space, shall meet all applicable requirements of Chapter 13. These requirements include insulation installation, moisture control, air leakage, and building envelope insulation levels. Unheated equipment rooms with combustion air louvers must be isolated from the conditioned space by insulating interior surfaces to a minimum of R-11 and any exterior envelope surfaces per Chapter 13. Outside air ducts serving individual supply air units with less than 2,1300 cfm of total supply air capacity shall be insulated to a minimum of R-7 and are not considered building envelope. Other outside airduct runs are considered building envelope until they, 1. connect to the heating or cooling equipment, or 2. are isolated from the exterior with an automatic shut-offdamper complying with Section 1412.4.1. Once outside air ducts meet the above listed requirements, any runs within conditioned space shall comply with Table 14-5 requirements. Other ducts and plenums shall be thermally insulated per Table 14-5. Exceptions: 1. Within the HVAC equipment. 2. Exhaust air ducts not subject to condensation. 3. Exposed ductwork within a zone that serves that zone. 1415 Piping Systems 1415.1 insulation: Piping shall be thermally insulated in accordance with Table 14-6. Exception: Piping installed within unitary HVAC equipment. Water pipes outside the conditioned space shall be insulated in accordance with Washington State Plumbing Code (WAC 51-26) 1416 Completion Requirements (Referto NREC Section 1416 and the Building Commissioning Guidelines, published by the Building Commissioning Association, for complete text and guidelines for building completion and commissioning requirements.)