Loading...
20070131093435.pdfCity of Edmonds PLAN REVIEW COMMENTS 6E BUILDING DIVISION ESt t 890 (425) 771-0220 DATE: January 31, 2007 TO: Danny Johnson 2215 Main St Everett, WA 98203 FROM: Jenny Readwin, Plans Exin, RE: Plan Check # 2007-0033 Project: Gow Re -Roof Project Address: 714 Edmonds St. During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or. submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Provide roof framing plan or truss layout sheet (see attached sample plan) showing new trusses and how they will tic into the existing roof. 2) Description of work specifies that the existing flat roof is to remain. On the section detail show existing roof and how trusses will be placed on top (i.e. are the existing rafters sitting on top of the double top plate? Will the existing roofing material be removed and trusses paced in between existing rafters?, etc.). Also, if existing roof and roofing material is to remain show proposed attic access into new attic area. 3) Provide attic ventilation calculations in accordance with R806. O h SAMPLE ROOF FRAMING PLAN SCALE 1I4" = 1'-0" ao•-0^ 10'-6" 26-0„ `f` = Area of new roof Truss specifications stamped by a Washington State Licensed Professional Engineer to be provided on-site to L:Uemplbuilding4handeut4additionlroof.vsd--3/00 Building Inspector at framing inspection. L:ITEMPIBUILDINGIHANDOUT ICODESII-Iandouts WebpagelREMOADD BGI.DOC Revised 7/04 0 ED e T P N \ 24•' Eave (typ) ATTACHMENT G 17 Existing 2x12 Rafters @16" c.o, �v.r�:.s. ..;a.. g�lCiL. 9a: i.e.-:».- '^'F�.3-;xa!f•t.'.t kc b7. °diu°. la i >. ELr #i mac, ,. ✓ 52040 €a`is-eYays&t'�xyTj o .� st ..-h ANIcAccess ME , x 3! MINION53°.i�•.<?..t ..,�.R.A:"Lar� ;4�E.d ;11 ... p �-G, Cyt, RE P N����rAS � 1'1 aqut 44utr��d: n]sses; FSM '.i•'':'i" FF,:st.�:a,.y �}y �.y�-' ^ 1 ,� r ...... .F s:fi W v's., a if 26-0„ `f` = Area of new roof Truss specifications stamped by a Washington State Licensed Professional Engineer to be provided on-site to L:Uemplbuilding4handeut4additionlroof.vsd--3/00 Building Inspector at framing inspection. L:ITEMPIBUILDINGIHANDOUT ICODESII-Iandouts WebpagelREMOADD BGI.DOC Revised 7/04 0 ED e T P N \ 24•' Eave (typ) ATTACHMENT G 17