2007-0186 Lindstrom Remodel.doc City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: February 23, 2007 TO: Brian Duffy and Nancy Lindstrom brianfduffy@msn.com FROM: Jenny Readwin, Plans Examiner RE: Plan Check # 2007-0186 Project: Lindstrom Deck/Remodel th Project Address: 23511 74 Ave W During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1)Deck plan configuration does not match configuration shown on the site plan. Please coordinate plans to show actual proposed location. Also, show deck stairs on the site plan. 2)Label deck on the site plan as “existing deck to be replaced”. 3)Provide typical stair details showing rise, run, handrail, guardrail, etc. See attached deck handout for sample. 4)Specify size of existing deck footings. Minimum size is 12”x12”x12” poured concrete. If existing footings do not meet minimum requirements new footings will need to be poured or calculations stamped and signed by a Washington State Licensed Professional Engineer will need to be submit to justify existing footings. 5)Provide all dimensions on the framing plan to verify beam spans. Also show all posts and footings. See deck handout for sample framing plan.